PowerWAVE 9000 DPA UPS - Safety
(Issue 2.1 Oct. 2009)
1.2 Operator
Precautions
The only user operations permitted are:
•
Use of the LCD control panel (LCD Display) and of the
Maintenance Bypass
•
Start up and shut down of the UPS (excluding the commissioning
start up)
•
Operation of additional connectivity modules
•
SNMP adapters and their software
•
Modem/GSM or Modem/Ethernet adapters and their software
•
Multidrop Kit for paralleling connectivity information between
multi-frame configurations
The user must adhere to the instructions in this manual, follow the
precautions and only perform the described operations. Any deviation from
the instructions may be dangerous to the user or cause accidental load loss.
1.3 Environmental
Considerations
The UPS must be installed according to the recommendations in this
manual. To operate the UPS at peak efficiency, the installation should meet
the environmental parameters outlined in this manual. Excessive dust in the
operating environment of UPS may cause damage or lead to malfunction.
The UPS should be always protected from the outside weather and
sunshine. If you intend to operate the system at an altitude higher than 1000
meters, contact your local sales or service office for important information
about high altitude operation. The operating environment must meet the
weight, airflow, size and clearance requirements specified in the technical
datasheet.
Under no circumstances the UPS should be installed in an airtight room, in
the presence of flammable gases, or in an environment exceeding the
specification.
The basic environmental requirements of the UPS system are:
•
Ambient Temperature Range: 0 to +40°C (32 – 104°F)
•
Recommended Operating Range: +20 to +25°C (68 – 77°F)
•
Maximum Relative Humidity: 95% (non-condensing)
The UPS cabinet uses forced air cooling to regulate internal component
temperature. Air inlets are in the bottom sides and front of the cabinet, and
outlets in the rear of the cabinet. You must allow clearance at the back of
the cabinet for proper air circulation. Refer to XXX for clearance
requirements.