PowerWAVE 9000 DPA UPS - Description
2-5
(Issue 2.1 Oct. 2009)
PowerWAVE DPA
Frames
CLASSIC
DPA-50
TRIPLE
DPA-150
UPGRADE
DPA-250
Capacity
Max.
1 module (30-45kVA)
280 x 7/9Ah batteries
3 modules (30-45kVA)
240x 7/9Ah batteries
5 modules (30-
45kVA) no batteries
Max. Power connection
kVA
50
150
250
Dimensions (WxHxD)
mm
730x1650x800
730x1975x800
730x1975x800
Weight of Empty Frame
kg
250
270
190
Weight of Frame with
modules and no batteries
kg
300 - 310
(with 1 Module)
420 - 450
(with 3 Modules)
440 - 490
(with 5 Modules)
Colours
Front: RAL 9007 + black (inlets). Sidewalls: Graffito grey
PowerWAVE DPA
MODULES
DPA 30
DPA 40
DPA 50
Output Apparent Power
KVA
30
40
45*
Output Active Power
KW
24
32
40
Output Power (PF=1)
KVA /
KW
24 / 24
32 / 32
40 /40
Number of 12V Battery
Blocks
No. 40-50
40-50
40-50
Dimensions (WxHxD)
mm
663 x 225 x 720
Weight UPS Module
kg
50
57
60
Colours
Front: RAL 9007
* On Inverter mode 50 KVA/40kW on Bypass mode 45 KVA/40kW