3-18
PowerWAVE 9000 DPA UPS - Installation
(Issue 2.1 Oct. 2009)
3.7 Internal
Battery
Systems
In DPA 10kVA, DPA 15kVA, DPA 20kVA, 30-50 12V-battery blocks are
permitted (even numbers only).
In DPA 25kVA, DPA 30kVA and DPA 50kVA, 40-50 12V-battery blocks
are permitted (even numbers only). The correct number of battery
blocks is set up on Control Panel Menu: Service-Set-Up).
3.7.1 DPA-25
In a DPA-25 FRAME there is space for up to 200 x 9Ah internal batteries.
Figure 3.11 shows the different Battery and System configurations.
Figure 3.11: DPA-25 Battery Configurations
3.7.2 DPA-75
In a DPA-75 FRAME there is space for up to 180 x 9Ah internal batteries.
Figure 3.12 shows the different Battery and System configurations.
Batteries may be used as separate batches for each UPS-module or as a
common battery for all three UPS-Modules.
Figure 3.12: DPA-75 Battery Configurations
A
B
C
A
B
C
A
B
C
A
B
C
UPS Module
UPS Module
UPS Module
UPS Module
7
10x7Ah
2x5x7Ah
10x7Ah
6
10x7Ah
2x5x7Ah
10x7Ah
10x7Ah
5
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
2x5x7Ah
4
10x7Ah
2x5x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
3 2x5x7Ah
2x5x7Ah
2x5x7Ah
2x5x7Ah 2x5x7Ah 2x5x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
2
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
2x5x7Ah
1
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
(4x50)x7Ah (3x50)x7Ah
(3x40)x7Ah (2x30)x7Ah
A
B
C
A
B
C
A
B
C
UPS Module 3
UPS Module 3
UPS Module 3
UPS Module 2
UPS Module 2
UPS Module 2
UPS Module 1
UPS Module 1
UPS Module 1
6
10x7Ah
2x5x7Ah
10x7Ah
5 2x5x7Ah
2x5x7Ah
2x5x7Ah
10x7Ah
10x7Ah
10x7Ah
4
10x7Ah
2x5x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
3
10x7Ah
10x7Ah
10x7Ah
2x5x7Ah 2x5x7Ah 2x5x7Ah
10x7Ah
10x7Ah
10x7Ah
2 2x5x7Ah
2x5x7Ah
2x5x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
1
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
3x(2x30)x7Ah (3x50)x7Ah
(3x40)x7Ah