5-6
PowerWAVE 9000 DPA UPS - UPS Module Replacement
(Issue 2.1 Oct. 2009)
9.
Transfer load to Inverter Mode by means of COMMAND “LOAD TO
INVERTER” of the control panel. LED display will indicate as
shown below:
10. Stop the module by pressing simultaneously both “ON/OFF” buttons.
11. Close the Parallel Isolator Switch IA2 corresponding to the module.
LCD panel must show the message PARALLEL SW CLOSED.
12. Press simultaneously both “ON/OFF” buttons.
Module will restart automatically connecting load to inverter and run
in parallel with other ON LINE modules. LCD panel must show
LOAD PROTECTED indication.
THE LOAD IS NOW PROTECTED BY THE UPS
LED Indicator
Colour
LINE 1
Green
LINE 2
Green
BYPASS
OFF
INVERTER
Green
BATTERY
Green