UPS471-02-00 PW9000DPA User Manual UK Dated 06/08/14
69
8: Specifications
8.2
Input Characteristics
8.3
Battery
Module Type
DPA 30
DPA 40
DPA 50
Output Rated Power per Module cos
0.8
kVA
30
40
45
1
Output Rated Power per Module cos
1.0
KW
24
32
40
Nominal Input Voltage
V
3x380/220V+N, 3x400V/230V+N, 3x415/240V+N
Input Voltage Tolerance
(ref to 3x400/230V) for Loads in %:
V
(-23%/+15%) 3x308/177 V to 3x460/264 V for <100 % load
(-30%/+15%) 3x280/161 V to 3x460/264 V for < 80 % load
(-40%/+15%) 3x240/138 V to 3x460/264 V for < 60 % load
Input Frequency
Hz
35 - 70
Input Power Factor
PF=0.99 @ 100 % load
Inrush Current
A
limited by soft start / max. In
Input Distortion THDI
Sine-wave THDi = < 2 % @ 100% load
Max. Input Power with rated output power and charged
battery per Module
(output Cos
= 1.0)
kW
25.4
33.9
42.9
Max. Input Current with rated output power and charged
battery per Module
(output Cos
= 1.0)
A
36.8
49.1
62.1
Max. Input Power with rated output power and discharged
battery per Module
(output Cos
= 1.0)
kW
27.8
37.1
46.9
Max. Input Current with rated output power and
discharged battery per Module
(output Cos
= 1.0)
A
40.3
53.7
68.0
1) On Inverter mode 50 KVA/40kW on Bypass mode 45 KVA/40kW
Module Type
DPA 30
DPA 40
DPA 50
Variable Number of 12V Battery Blocks
No.
40-50
40-50
40-50
Maximum Battery Charger Current
A
10A Standard (15 A optional)
Battery Charging Curve
Ripple free; IU (DIN 41773)
Temperature compensation
Standard (temp. sensor optional)
Battery Test
Automatic and periodically (adjustable)
Battery Type
Maintenance free VRLA or NiCd