8: Specifications
70
UPS471-02-00 PW9000DPA User Manual UK Dated 06/08/14
8.4
Output
8.5
Environmental
Module Type
DPA 30
DPA 40
DPA 50
Output Rated Power per Module
kVA
30
40
45 1)
Output Rated Power per Module
KW
24
32
40
Output Current In @ cos
1.0 (400 V)
A
35
46.5
58
Output Rated Voltage
V
3x380/220V or 3x400/230V or 3x415/240V
Output Voltage Stability
%
Static: < +/- 1% Dynamic
(Step load 0%-100% or 100%-0%) < +/- 4%
Output Voltage Distortion
%
With Linear Load < +/- 2% With Non-linear Load
(EN62040-3:2001) < +/- 4%
Output Frequency
Hz
50 Hz or 60 Hz
Output Frequency Tolerance
%
Synchronized with mains < +/- 2 % (selectable) or
< +/- 4 % Free r/- 0.1 %
Bypass operation
At Nominal Input voltage of 3x400 V +/- 15 % or
190 V to 264 V ph-N
Permissible Unbalanced Load
(All 3 phases regulated independently)
%
100%
Phase Angle Tolerance
(With 100 % Unbalanced load)
Deg.
+/- 0 deg.
Overload Capability on Inverter
%
125 % load 10 min. 150 % load 60 sec.
Output short capability (RMS)
A
Inverter: 2 x In during 250 ms
Bypass: 10 x In during 10 ms
Crest - Factor
3 : 1
1) On Inverter mode 50 KVA/40kW on Bypass mode 45 KVA/40kW
Module Type
DPA 30
DPA 40
DPA 50
Audible Noise with 100% / 50% Load
dBA
59/51
65/55
65/55
Operation temperature
°C
0 - 40
Ambient Temperature for Batteries
°C
20 - 25 (recommended)
Storage Temperature
°C
-25 - +70
Battery Storage Time at Ambient Temperature
Max. 6 months
Max. altitude (above sea level)
m
1000m (3300ft) without de-rating
De-rating factor for use at altitudes greater than 1000m
above sea level (IEC 62040-3)
0.9 @ 1500m / 4850ft asl
0.91 @ 2000m / 6600ft asl
0.86 @ 2500m / 8250ft asl
0.82 @ 3000m / 9900ft asl
Relative Air-humidity
Max. 95% (non-condensing)
Accessibility
Totally front accessibility for service and maintenance (no
need for side, top or rear access)
Positioning
Min. 20 cm rear space (required for fan)
Input and Output Power Cabling
From the bottom on the front