26
At this time, you can calibrate output voltage value in parameter 2
by pressing Up or Down according to the measurement from an
external voltage meter. The calibration result will be effective by
pressing Enter. The calibration range is limited /-9V. This
function is normally used for parallel operation.
21: Charging current setting
Interface
Setting
Parameter 2: It always shows CHG as Charging current.
After pressing the “Enter” button, it will show charging current
value in parameter 2. You may modify the current value by
pressing Up or Down button. The setting range is from 1A to 12A
and the default value is 1A.
22: Battery numbers setting
Interface
Setting
The Battery numbers setting menu will be displayed only after
entering the password. Please enter password “616” by pressing
“Up” and “OFF” button to access setting menu. Press “Up” and
“OFF” buttons at the same time to exit the menu.