4. Trouble Shooting 
 

Symptom 

Possible Cause 

Remedy 

No LED display 
on the front 
panel. 

1. Missing battery. 

1.  Charge  battery  up  to  8 
hours. 

2. Battery defect. 

2. Replace with the same type 
of   

battery. 

3. Power switch is not 

pressed. 

3. Press a power switch again. 

Alarm buzzer 
beeps 
continuously 
when AC 
supply is 
normal. 

Overload of the UPS. 

Verify that the load matches 
the UPS capability specified in 
the specs. 

When power 
failure, back-up 
time is shorten. 

1. Overload of the UPS. 

1.  Remove  some  noncritical 
load. 

2. Battery voltage is too low.  2.  Charge  battery  8  hours  or 

more. 

3. Battery defect due to high 

temperature operation 
environment, or improper 
operation to battery. 

3. Replace with the same type 

of battery. 

Mains normal 
but LED is 
flashing. 

1. Fuse is blown. 

1.  Replace  the  same  type  of 
fuse. 

2. Power cord is loose. 

2. Reconnect the power cord 

properly. 

If any abnormal situations occur that are not listed above, please call service 
people immediately.

 

Summary of Contents for 400

Page 1: ...USER MANUAL Line Interactive UPS Uninterruptible Power System ...

Page 2: ...FETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models Line Interactive 400 600 and 800 that should be followed during installation and maintenance of the UPS and batteries ...

Page 3: ...cessive humidity Do not plug the UPS input into its own output Do not attach a power strip or surge suppressor to the UPS Do not attach non computer related items such as medical equipment life support equipment microwave ovens or vacuum cleaners to UPS To reduce the risk of overheating the UPS do not cover the UPS cooling vents and avoid exposing the unit to direct sunlight or installing the unit...

Page 4: ...cted in the plus and minus pole of the battery when maintenance or service work inside the UPS is necessary The mains socket outlet that supplies the UPS shall be installed near the UPS and shall be easily accessible Wichtige Sicherheitshinweise Bitte lesen Sie diese Hinweis sorgfaltig durch Vor jedem rcinigen ist das Gerät vom Stromnetz zu trennen Verwenden Sie Keine Flüssig oder Aerosolreiniger ...

Page 5: ...s monitor UPS inside status The main features of the UPS are listed below Microprocessor control guarantees high reliability Equipped with Boost and Buck AVR Built in RS 232 Communication Port Free Software Download from the Internet Please check Free Software Download in Installation Operation for detail information Green Power Function for energy saving DC Start Function Auto restart while AC re...

Page 6: ...plugged in for at least 8 hours with no load no electrical devices such as computers monitors etc connected 3 Placement Install the UPS unit in any protected environment that provides adequate airflow around the unit and is free from excessive dust corrosive fumes and conductive contaminants Do not operate your UPS in an environment where the ambient temperature or humidity is high On the other ha...

Page 7: ...unction This UPS is equipped with Green Power Function For saving power and protecting battery the method of deep discharging protection is adopted on inverter mode 8 Free Download Software WinPower Go to the website http www ups software download com winpower htm Choose the operation system you need and follow the instruction described on the website to download the software When downloading all ...

Page 8: ...ption Front panel 1 Power Switch 2 LED Indicators AC Mode Green lighting Battery Mode Green flashing Back Panel 1 Output receptacles 2 AC input with AC fuse 3 Modem Phoneline Surge Protection 4 USB Communication Port ...

Page 9: ...capability specified in the specs When power failure back up time is shorten 1 Overload of the UPS 1 Remove some noncritical load 2 Battery voltage is too low 2 Charge battery 8 hours or more 3 Battery defect due to high temperature operation environment or improper operation to battery 3 Replace with the same type of battery Mains normal but LED is flashing 1 Fuse is blown 1 Replace the same type...

Page 10: ...tor 12 minutes 23 minutes 34 minutes Recharge Time 8 hours to 90 after complete discharge TRANSFER TIME Typical 2 6 ms INDICATOR AC Mode Green lighting Backup Mode Green flashing AUDIBLE ALARM Backup Mode Sounding every 10 seconds Low Battery Sounding every second Overload Sounding every 0 5 second Battery Replacement Sounding every 2 seconds Fault Continuously sounding PROTECTION Full Protection ...

Reviews: