User guide and technical documentation
Page
24
of
29
4.4
Analog outputs
4.5
Relay outputs
Section 1 (AO1)
Section 2, 3
Output terminals
AOR
AOV
Common conductor
AGND
AGND
Galvanic isolation
No
Yes
Output functions
0–10 V voltage source,
0–20 mA current source,
Resistance measurement: 0–2 k
Ω
(Ni1000,
PT1000)
0–10 V voltage source
Resolution
12 bits
12 bits
Conversion
1 ms
300 µs
Protection type
Integrated overvoltage protection
Integrated overvoltage
protection
Output voltage range
0–10 V
0–10 V
Output current range
0–20 mA
Output accuracy
±0.5 %
±0.5 %
Output terminal
RO
Common terminal
COM
Galvanic isolation
Yes
Output type
Electro-mechanic non-shielded relay
Switching voltage
250 V
∿
/ 30 V
⎓
Switching current
5 A
Short-term current overload
5 A
Common terminal current
10 A
Switching speed
10 ms
Mechanical lifespan
5 000 000
Electrical lifespan
100 000
Short circuit protection
No
Overvoltage protection
No
Load handling
External – RC, varistor, diode, thermistor
Isolation voltage
4000 V
∿