Aspiro 1U in 2U Enclosure Quick Install Guide - 4

  Continued from page 3 

 6  Alarm & Symmetry Connection

Alarm and Symmetry Connections are situated at the 
rear of the system. There are connections for the 4 alarm 
contacts and 2 x 3 way connections for the symmetry.  
Multi Purpose connections 7-12 can be reconfigured as 
external analog inputs.

7

7

8

8

9

9

4

4

5

5

6

6

 

 

 

 

1

1

2

2

3

3

X9

X10

Multipurpose 10 Multipurpose 1

1

Multipurpose 12

10 11 12 13 14 15 16 17 18

10 11 12 13 14 15 16 17 18

0V Sense +5V

0V Sense +5V

Battery

Temp.

Ambient

Temp.

Alarm 4 - C Alarm 4 - NC Alarm 4 - NO

Alarm 1 - C Alarm 1 - NC Alarm 1 - NO

Alarm 2 - C Alarm 2 - NC Alarm 2 - NO

Alarm 3 - C Alarm 3 - NC Alarm 3 - NO

Multipurpose 1 Multipurpose 2 Multipurpose 3

Multipurpose 4 Multipurpose 5 Multipurpose 6

Multipurpose 7 Multipurpose 8 Multipurpose 9

Digital In 1 Digital In 2 Digital Out 1

Digital Out 2 - V Sys. +V Sys.

Alarm Condition Shown

C
NC
NO

WARNING!

Multi Purposes 7-12, Digital In/Outs and Ambient 
Temperature are not available with the PCC controller.

NOTE:

The configuration of alarms and symmetry connections 
may vary depending on the controller configuration, if 
fitted.

 7  Symmetry Connection

1.  Attach the inter-block connections plates between 

the batteries.

2.  Insert the correct sized cable lug that fits the bolt 

into one pole of the inter-block connection plate. 
Fasten the lugs and plates to individual battery 
poles.

3.  For 4-block measurement fix 3 wires of symmetry 

cable to individual cable lugs.

 8  Temperature Sensor(s)

Temperature Sensor Connection for supervising battery 
temperature is usually delivered pre-installed when used.  
If it is added later, use a three-pin plug and connect to 
terminals 13-15 on connector X9 at the rear of the system. 
The sensor itself should be fastened to the battery after 
battery installation: Unwind the cable, remove the paper 
covering the adhesive for the sensor and fasten the 
sensor to the battery.

Temp. Sensor

If an external temperature sensor is to be used this 
should be connected in the same way to terminals 16-
18 on connector X9.