Aspiro 1U in 2U Enclosure Quick Install Guide - 5

© 2017 UNIPOWER LLC

This document is believed to be correct at time of publication and UNIPOWER LLC accepts no responsibility for consequences from printing errors or inaccuracies.  All specifications subject to change without notice.

    Technical Support

For more complete information relating to installation 
and operation of this system please read the Instruction 
Manual which can be downloaded from the UNIPOWER 
web site at:

http://www.unipowerco.com/pdf/PM110-6500-00-D1.pdf

For additional technical support or feedback, please visit 

www.unipowerco.com/contact/

 where you will find the 

phone number for your region.

Alternatively, email:

technical.support@unipowerco.com

 9  Commissioning Procedure

1.  Remove the alarm cover and check that 

all connections are made according to the 
installation drawing.  Verify that all connections 
are properly tightened with sufficient torque. 

2.  Ensure that load and battery MCB breakers are 

set to OFF position - ensuring the load and battery 
strings are connected.

3.  Ensure that all rectifier modules are removed.  If 

not, remove each one in turn starting from the 
rightmost position.

4.  Check the battery polarity with the multimeter 

at the SB-50 connector. Place the positive lead of 
the meter to the positive contact and the negative 
lead to the battery contact. The meter must now 
show a positive voltage. If the voltage is negative, 
change over the connection of the gray and black 
battery cables to the batteries.

5.  Plug in the AC power cord.
6.  Plug in the rectifier modules, starting from the left 

most position.  Make sure to fasten the rectifiers 
again.  The rectifiers will turn on automatically.  
Empty rectifier positions must be cover with 
rectifier blanks.

7.  Set all load breakers into the “1” (ON) position.
8.  The green LED on the controller should blink for 

approximately 20 sec.

9.  The output voltage will increase slowly to U1 (float 

charge voltage).

10.  Turn the battery breaker to the “1” (ON) position.
11.  If any alarms are present, they should be reset in 

accordance with the procedure for the installed 
controller, ACC Extended (ACX) or PCC.

12.  The system should now be without alarms.
13.  Attach all the system covers in their correct places.
14.  Check that all changes to drawings, if any, have 

been completed.

15.  Clean the site.
16.  Fill in the commissioning record (table 5-2 in 

section 5.8 in the instruction manual).

 10  EMC Considerations

This equipment has been tested and found to comply 
with the limits for a Class B digital device, pursuant 
to part 15 of the FCC Rules.  Please see the 

instruction 

manual

, section 3.1.8, for more details.

 11  PowCom Login

NOTE:

Remote access using PowCom software is only 
available when a controller is installed.

If you don’t have PowCom software you can 
download it from the UNIPOWER web site at:

www.unipowerco.com/powcom/PowCom_setup.zip

Once you have downloaded the file, you will need a 
license number to activate the software.  This can be 
found in the readme.txt file in the installation package.
To activate your PowCom software with your license, 
please follow the instructions below.
1.  Start PowCom and go to Communication/Properties 

in the menu.

2.  Click on the license tab in the Properties window. 

Copy and paste your license number and click on 
the Activate License button.

Please exit the program and restart it again in order to 
fully activate the license.
If any problem occurs do not hesitate to contact our 
technical support.
The PowCom user manual is available from the 
UNIPOWER web site at:

www.unipowerco.com/pdf/powcom-man.pdf