Page 35
P O W E R I N G T E C H N O L O G Y
Manual No. PM110-6500-00 rev-2a
PM110-6500-00-rev2a-0117.indd
Fault
Possible Cause
Suggestion/Solution
Load/Battery
Disconnection
System voltage drops below the set
limit.
System shutdown.
Check the battery condition.
Check the AC mains connection.
Check the input breaker.
Check the rectifier modules.
Communication
Failure
Module failure.
Modules not installed in the correct
position.
Broken or disconnected
communication wire.
If the rectifier address does not
communicate re-install the module
and wait for 5 minutes.
Verify, if the controller is operating
properly. If not, replace the
controller.
Distribution
Fuse Failure
Tripped load breaker / blown load
fuse.
Verify there is no short circuit in load
cabling.
Reset the breaker, if it trips again,
there is a problem with the load or a
breaker itself.
Return the system to the factory for
repair
Battery Fuse
Failure
Tripped load breaker / blown load
fuse
Verify there is no short circuit in load
or battery cabling.
Verify the breaker / fuse is correctly
rated.
Reset the breaker, if it trips again,
there is a problem with the load or
battery or a breaker itself.
Return the system to the factory for
repair.
Symmetry Fault
Battery at end of life.
Wrong symmetry cable connection.
Wrongly set Symmetry limit value.
Verify the battery condition.
Verify the symmetry cable
connection.
Verify the Symmetry limit value.
Low Battery
Temperature
Battery temperature drops below the
set Low battery temperature limit.
Check the heating of the system.
Check the ambient temperature
(it should not be lower than
recommended battery temperature).