Page 5
DPP1U SERIES
OPERATING MANUAL
P O W E R I N G T E C H N O L O G Y
Document Number: DPP1U-MAN Rev. 7
dpp1u-man-Rev7-0422.indd
3.0 PRODUCT LINE
3.1
Standard Configurations
The following table lists the 8 available standard configurations of the DPP1U series.
MODEL
NUMBER
VOLTAGE
INPUT
FEEDS
MAX. #
BREAKERS
AMPS
EACH
FEED
TOTAL
AMPS
DPP1U-A1-B1
-48 / -24V
2
8 A Side
&
8 B Side
150
300
DPP1U-A4-B4
+24V / +48V
DPP1U-A5-B5
-12V
DPP1U-A6-B6
+12V
Notes:
1.
For single feed configurations add suffix
-S
to the above model
numbers. Single feed units have the input buses internally
connected together and the total amperage is limited to 150A.
2.
All panels are shipped with 15 breaker position blanking plates.
3.2
Available Breakers
AMPS
PART NUMBER
AMPS
PART NUMBER
AMPS
PART NUMBER
1
348-1436-0000
10
348-1436-0030
25
348-1436-0060
2.5
348-1436-0010
15
348-1436-0040
30
348-1436-0070
5
348-1436-0020
20
348-1436-0050
BLANK
348-1418-0000
Breakers need to be ordered individually and are shipped with each panel as separate items
for field installation.
4.0 SAFETY & INDUSTRY STANDARDS
4.1
DPP1U Series power distribution panels meet the following safety requirements:
STANDARD
UL60950-1, 2nd Edition
CSA22.2 No. 60950-1, 2nd Edition
EN60950-1, 2nd Edition
4.2
DPP1U Series power distribution panels are CE marked to indicate conformance to the
European Union’s Low Voltage Directive.
4.3
These Distribution Panels operate at voltages that could potentially be hazardous.
Furthermore, inadvertent short circuiting of the system battery and/or rectifier by mis-
connection or other error could be harmful. This product should be handled, tested and
installed only by qualified technical persons who are trained in the use of power systems
and are well aware of the hazards involved.