Page 5
DPP2U SERIES
OPERATING MANUAL
P O W E R I N G T E C H N O L O G Y
Manual No. DPP2U-MAN Rev. 5
dpp2u-man-rev5-0719.indd
3.0 PRODUCT LINE
3.1 Configurations
The following table lists the 5 available configurations of the DPP2U series.
STANDARD DUAL FEED CONFIGURATIONS
MODEL
NUMBER
VOLTS
EACH FEED
INPUT
FEEDS
MAX. #
BREAKERS
AMPS
EACH FEED
TOTAL
AMPS
DPP2U-A1-B1 48/24 - 48/24
2
10 A side
&
10 B side
450
900
DPP2U-A6-B6
12 - 12
DPP2U-A1-B6
48/24 - 12
OPTIONAL SINGLE FEED CONFIGURATIONS
MODEL
NUMBER
VOLTS
EACH FEED
INPUT
FEEDS
MAX. #
BREAKERS
AMPS
EACH FEED
TOTAL
AMPS
DPP2U-A1-B1-S
48/24
1
20
450
450
DPP2U-A6-B6-S
12
3.2 Available Breakers
1
AMPS
PART NUMBER
AMPS
PART NUMBER
2.5
348-1441-0020
50
348-1441-0500
5
348-1441-0050
60
348-1441-0600
10
348-1441-0100
80
348-1441-0800
15
348-1441-0150
100
348-1441-1000
20
348-1441-0200
125
2
775-1524-0000
25
348-1441-0250
150
2
775-1524-0010
30
348-1441-0300
200
2
775-1524-0020
40
348-1441-0400
NOTES:
1. Breakers need to be ordered individually and are shipped separately.
2. Require two positions. Includes paralleling bars to connect output load terminals.
3. Breakers are magnetic-hydraulic plug-in type with auxiliary contacts (Normally Open) and mid-trip
function. Only the following types may be installed.
2.5A to 100A:
CBI D-Frame Series single pole, D-2A23XANBSXXXXLXB-XXXXXWDVAX2-X
or
Carling C-Series Handle single pole, CT1-B2-14-XXX-A11-MJ
125A to 200A:
CBI D-Frame Series, parallel pole, D-2A23XBNBSXXXXLAM-XXXXXWDVAX3-X
or