12
PCM500 SERIES
OPERATING MANUAL
The FA1 through FA5 alarms function for up to five fuse or circuit breaker
distribution panels. If any fuse or circuit breaker on any panel opens, this will
cause the FA (Fuse or Circuit Breaker Alarm) red LED to come on and the
FA Form C relay to change state. The LVDA1 and LVDA2 alarm-enable
switches are for one or two Low Voltage Disconnect panels. If either one of
these experience a disconnect, the LVDA (Low Voltage Disconnect Alarm)
red LED will come on and the LVDA Form C relay will change state.
15.0
VOLTAGE AND CURRENT MEASUREMENTS
15.1
Meters and Test Points. The meter panel option (Option MP) provides a
digital voltmeter and ammeter on the left front panel to monitor the battery
voltage and current.
15.2
Voltage. The digital voltmeter reads battery voltage directly, to tenths of a volt.
The “volts” test points on the right front panel also permit direct external
measurement of the battery voltage when the MP option is not taken.
15.3
Current. The digital ammeter is scaled at the factory to read amperes based
on a 50 millivolt external shunt and corresponding internal scale factor which
must be chosen at the time of ordering. The following table gives the amme-
ter shunt rating and ordering suffix code for the correct meter setting at the
factory. The external shunt must be connected with correct polarity
across the I+ and I- input terminals (TB1 terminals 41 and 8, respectively).
See Figure 4 and Section 13.2.
ALARM-ENABLE DIP SWITCHES
POS.
SW. NO.1
SW. NO.2
SW. NO.3
SW. NO.4
NO.
FUNCTION
FUNCTION
FUNCTION
FUNCTION
1
SR11
SR21
SR31
SR41
2
SR12
SR22
SR32
SR42
3
SR13
SR23
SR33
SR43
4
SR14
SR24
SR34
SR44
5
FA1
FA3
FA5
LVDA1
6
FA2
FA4
NC
LVDA2
External 50mV Shunt
AMMETER
SHUNT RATING
CODE
250
250A
300
300A
500
500A
1000
1000A
1500
1500A
2000
2000A
25
25A
30
30A
50
50A
75
75A
100
100A
150
150A
200
200A
AMMETER
SHUNT RATING
CODE
Summary of Contents for PCM500 Series
Page 3: ......