background image

Page 8

DPU1U SERIES

INSTALLATION & OPERATING MANUAL

P O W E R I N G   T E C H N O L O G Y

Document Number: DPU1U-MAN Rev. 4

dpu1u-man-rev1-0719.indd

6.3 

Alarm Circuits.

  The alarm circuits detect a tripped circuit breaker or blown and, in this 

event, turn on the red part of the LEDs.  The alarm circuits also each drive Form C relay 
contacts.  If one or more circuits open or if there is an input power failure, the relays are 

de-energized and the contacts are used to control external audible or visual alarms.  The A 

and B alarm circuits are also independent and isolated from each other.

LED STATE MEANINGS

LED State

Meaning

Green

OK

Red

Breaker Trip

or

Breaker OFF

or

Fuse Blown

OFF

No Input Power

Table 1.  LED State Definitions

7.0   SPECIFICATIONS

The following specifications are typical at 25°C unless otherwise noted.

INPUT / OUTPUT

Fuse & Breaker Capacity ..................................................................... 80A or 150A Per Bus

LVD Capacity ........................................................................................................................................ 70A

Fuse Configuration ..................................................................................................10 GMT Fuses

Breaker Configurations ......................................................................................1 to 6 Breakers

Voltage

     48V Nominal ...................................................................................................................42-60VDC

     24V Nominal .....................................................................................................................21-30VDC

     12V Nominal....................................................................................................................10.5-15VDC

Polarity ...........................................................................................Positive or Negative Ground

ALARMS

Alarm Indicator ................................................................................................LED on Each Side

LED Status

     Fuse & Breaker Sections ..........................................................................Green = Normal

                                                                                      Red = Alarm, Off = No Power

     LVD Section .............................Red = LVD Contactor or Battery Breaker Open

                                                                                                                     Off = Normal

Alarm Connections

     Fuse & Breaker ...............................................Two Form C Relay Contacts Per Bus

     LVD ......................Form C Relay Contacts for Disconnect or Battery Breaker

SAFETY STANDARDS

 .........................................UL1950, CSA22.2 No.950, EN60-950

ENVIRONMENTAL

Operating Temp. Range ....................................................................................-10°C to +70°C

Storage Temp. Range ....................................................................................... -40°C to + 85°C

Humidity .....................................................................................0% to 95%, Non-Condensing

PHYSICAL SPECIFICATIONS

Case Material .....................................................................................................................................Steel

Finish ........................................................................................................................Powder Coat Gray

Dimensions, Inches (mm) ........................................................1.75 H x 19.00 W x 9.00 D

                                                                                                             (44.5 x 483 x 229)

Weight ..........................................................................................8.76 - 9.73 lbs. (3.97 - 4.41 kg.)

Rack Mounting Width ........................................................................................ 19 or 23 Inches

CONNECTIONS

Input Connections.................................................... Crimp Type Lugs or ¼ - 20 Studs

Output Connections

     Fuse or Breaker ..............................................................................Barrier Terminal Strips

     LVD ................................................................................. Crimp Type Lugs or ¼ - 20 Studs

Battery Connection, LVD ..................................... Crimp Type Lugs or ¼ - 20 Studs

Chassis Ground Connection ............................................................................ No. 8-32 Stud

Alarm Connections ..................................................................... 0.045” sq. Wirewrap Pins

BASE

MODEL

SIDE

TOTAL 

AMPS

TYPE

DPU1U

A

80 

150

10 x GMT Fuses

1-6 x Breakers

B

80 

150

70

10 x GMT Fuses

1-6 x Breakers

1 x LVD

Note:

  Each side of the panel can be configured for only 

one of the available ‘types’ as shown.  To specify a 

complete model number see the configuration 

guide later in this manual.

Table 2.  Available Combinations

Summary of Contents for UNIFLEX DRU1U Series

Page 1: ...y can be mounted from the front of the rack with offsets every quarter inch from front to back to align with existing rack mounted equipment FEATURES One Mounting Position High 1 75 19 or 23 Inch Rack...

Page 2: ...w voltage disconnect specified by L 2 A bypass switch must also be designated YES or NO 3 For a breaker panel each breaker must be specified with highest current in position 1 down to lowest current i...

Page 3: ...N PANELS Document Number DPU1U MAN Rev 4 UNIPOWER LLC 65 Industrial Park Rd Dunlap TN 37327 Phone 1 954 346 2442 Toll Free 1 800 440 3504 Web site www unipowerco com 2019 UNIPOWER LLC All Rights Reser...

Page 4: ...TRODUCTION 4 2 0 FEATURES 5 3 0 PRODUCT DESCRIPTION 5 4 0 SAFETY INDUSTRY STANDARDS 6 5 0 WARRANTY summary 6 6 0 DESCRIPTION OF OPERATION 7 7 0 SPECIFICATIONS 8 8 0 FRONT PANEL DESCRIPTION 9 9 0 BACK...

Page 5: ...MT Fuse Section Front Panel View 9 Figure 6 LVD Front Panel View 9 Figure 7 Center Section Front Panel View 9 Figure 8 Back Panel View with LVD 10 Figure 9 Back Panel View with Dual Distribution 11 Fi...

Page 6: ...ng rackmounted equipment DPU1U Series provides a combination of circuit breaker or fuse distribution on the A side with an LVD or distribution on the B side Figure 1 shown the three possible combinati...

Page 7: ...GMT Fuses or Magnetic Circuit Breakers LVD Protection 70A Magnetic Circuit Breaker with Bypass Option Independent and Isolated Loads Input Connections Crimp Type Lugs Output Connections Barrier Termi...

Page 8: ...operating these combination anels the chassis ground terminal must be connected to the system frame ground or other proper safety ground for the protection of personnel 4 5 All connections to these co...

Page 9: ...S OPTION Figure 2 Distribution Block Diagram 6 2 LVD Circuits Figure 3 shows a simplified diagram of the LVD circuit The LVD is connected to a rectifier bus battery and distribution panel The contact...

Page 10: ...Alarm Indicator LED on Each Side LED Status Fuse Breaker Sections Green Normal Red Alarm Off No Power LVD Section Red LVD Contactor or Battery Breaker Open Off Normal Alarm Connections Fuse Breaker Tw...

Page 11: ...F O ON I 15 17 12 434 9 REAR VIEW FRONT VIEW Cas Figure 4 Distribution Section Front Panel View The front panel of the GMT fuse distribution section shown in Figure 5 below can each accommodate up to...

Page 12: ...Red 3 401 1500 0060 Blue 401 1500 0020 Brown 5 401 1500 0070 Green 1 401 1500 0030 Gray 10 401 1500 0080 Red White 11 3 401 1500 0040 White 12 401 1500 0090 Green Yellow 2 401 1500 0050 Orange DUMMY...

Page 13: ...o spring clamp terminal blocks for the Form C relay contact outputs Below these is a chassis ground terminal 9 2 Input Connections also Output Connections for LVD See Figure 10 The DC power inputs to...

Page 14: ...mum of two high current breakers is allowed 1 2 3 4 5 6 7 8 9 10 40 50A LOADS 10 32 1A to 30A LOADS 6 32 0 75 19 1 0 5 12 7 0 378 9 60 Figure 11 Output Barrier Strip Detail 9 5 Form C Relay Contact Ou...

Page 15: ...is either loss of input power one or more circuit breakers trip or the relay is de energized the normally open contacts close and the normally closed contacts open See table 6 RELAY STATE MEANINGS Rel...

Page 16: ...Mount it from the front of the rack using the correct offsets to align with existing rack mounted equipment The bracket offsets are every quarter inch from front to back 11 2 Power Connections Input c...

Page 17: ...asure the resistance between C and N O This which should read open Measure the resistance between C and N C This should read short Replace the blown fuse with a good one or reset the circuit breaker 1...

Page 18: ...d application 12 4 If the combination panel did not operate properly in the above tests go back and double check the connections and the polarity of the input source to make sure it is correct Please...

Reviews: