5.DISPLAY SETTINGS
54
5-5. Zero Tracking (ZT)
Zero tracking automatically compensates slow system drift, as well as small
zero-point shift due to residue objects on the sale such as debris, dirt and dust.
10
0
10
-1
Zero tracking period
0.0-9.9 sec
10
3
10
2
10
1
10
0
Zero tracking range
0-9999
m+34
m+35
・
Zero tracking clear Final to zero at every specified period, if zero shift
during that period remains within the specified range.
・
Allowed tracking period is from 0.0 to 9.9 seconds, and Zero
tracking range is from 0 to 9999 in 1/4 of scale division unit.
(0002=0.5 divisions, 0012=3 divisions)
Zero tracking is disabled if zero is specified for the period or
range.
Boundary of zero track
Tracking period
Weighing value
Tracking range
+
0
-
Tracking period
From the point when it returned within the range,
counting will be resumed.