background image

290982-UIM-C-0907

4

Unitary Products Group

4.

Braze the liquid line to the evaporator liquid connection. Nitrogen
should be flowing through the evaporator coil.

5.

Slide the grommet away from the vapor connection at the indoor
coil. Braze the vapor line to the evaporator vapor connection. After
the connection has cooled, slide the grommet back into original
position.

6.

Protect the vapor valve with a wet rag and braze the vapor line
connection to the outdoor unit. The nitrogen flow should be exiting
the system from the vapor service port connection. After this con-
nection has cooled, remove the nitrogen source from the liquid fit-
ting service port.

7.

Replace the Schrader core in the liquid and vapor valves.

8.

Go to “SECTION V” or “SECTION IV” for orifice or TXV installation
depending on application.

9.

Leak test all refrigerant piping connections including the service
port flare caps to be sure they are leak tight. DO NOT OVER-
TIGHTEN (between 40 and 60 inch - lbs. maximum).

NOTE: 

Line set and indoor coil can be pressurized to 250 psig with dry

nitrogen and leak tested with a bubble type leak detector. Then release
the nitrogen charge.

NOTE: 

Do not use the system refrigerant in the outdoor unit to purge or

leak test.

10. Evacuate the vapor line, evaporator, and liquid line to 500 microns

or less.

11.

Replace cap on service ports. Do not remove the flare caps from
the service ports except when necessary for servicing the system.

12. Release the refrigerant charge into the system. Open both the liq-

uid and vapor valves by removing the plunger cap and with an
allen wrench back out counter-clockwise until valve stem just
touches the chamfered retaining wall. See Page 3 "PRECAU-
TIONS DURING BRAZING SERVICE VALVE".

13. Replace plunger cap finger tight, then tighten an additional 1/12

turn (1/2 hex flat). Cap must be replaced to prevent leaks.

See "System Charge” section for checking and recording system
charge.

Supplied with the outdoor unit is a Schrader Valve Core and Orifice for
highest sales volume indoor coil.  The valve core must be installed in
equalizer fitting of the indoor coil.

SECTION IV: ORIFICE INSTALLATION

Install Schrader Valve Core as follows:

1.

Slide indoor coil out of cabinet far enough to gain access to equal-
izer fitting on the suction line.

2.

After holding charge is completely discharged remove black plas-
tic cap on equalizer fitting.

3.

Install Schrader Valve Core supplied with the outdoor unit into
equalizer fitting using a valve core tool.

4.

Loosen and remove the liquid line fitting from the orifice distributor
assembly.  Note that the fitting has right hand threads.

5.

Install proper size orifice supplied with outdoor unit.  Refer to sup-
plied Tabular Data Sheet for specific orifice size and indoor coil
match up.

6.

After orifice is installed reinstall the liquid line to the top of the ori-
fice distributor assembly.  Hand tighten and turn an additional 1/8
turn to seal.  Do not over tighten fittings.

7.

Leak test system.

8.

Replace black plastic cap on equalizer fitting.

9.

Slide indoor coil back into cabinet.

 FIGURE 4:  

Heat Protection

Do not install any coil in a furnace which is to be operated during
the heating season without attaching the refrigerant lines to the coil.
The coil is under 30 to 35 psig inert gas pressure which must be
released to prevent excessive pressure build-up and possible coil
damage.

 Do not connect manifold gauges unless trouble is suspected.
Approximately 3/4 ounce of refrigerant will be lost each time a stan-
dard manifold gauge is connected.

Never attempt to repair any brazed connections while the system is
under pressure. Personal injury could result.

Failure to install Schrader Valve Core on orifice applications could
result in total refrigerant loss of the system!

 FIGURE 5:  

Orifice Installation

LIQUID LINE
SWIVEL COUPLING
(This fitting is a right-hand thread,
turn counter-clockwise to remove)

ORIFICE

DISTRIBUTOR

Summary of Contents for 13 SEER GCGD12

Page 1: ...des and the limitations listed below 1 Limitations for the indoor unit coil and appropriate accessories must also be observed 2 The outdoor unit must not be installed with any duct work in the air str...

Page 2: ...osition The base pad should not come in contact with the foun dation or side of the structure because sound may be transmitted to the residence The length of the refrigerant tubing between the outdoor...

Page 3: ...ions orifice connections system charging traps etc PRECAUTIONS DURING BRAZING OF LINES All outdoor unit and evaporator coil connections are copper to copper and should be brazed with a phosphorous cop...

Page 4: ...e System Charge section for checking and recording system charge Supplied with the outdoor unit is a Schrader Valve Core and Orifice for highest sales volume indoor coil The valve core must be install...

Page 5: ...bove 500 microns SECTION VII SYSTEM CHARGE The factory charge in the outdoor unit includes enough charge for the unit a 15 ft line set and the smallest indoor coil match up Some indoor coil matches ma...

Page 6: ...switch to the unit 4 Route wires from disconnect through power wiring opening pro vided and into the unit control box as shown in Figure 6 5 Install the proper size time delay fuses or circuit breake...

Page 7: ...o not place it on an out side wall or where it is exposed to the radiant effect from exposed glass or appliances drafts from outside doors or supply air grilles 6 Route the 24 volt control wiring NEC...

Page 8: ...ric heat on thermostat is not necessary MA SHP AHP ID MODELS Other Part Numbers SAP Legacy 265902 031 09167 2 Part Numbers SAP Legacy 159480 031 09156 1 COM 24 Volt Common R 24 Volt Hot W2 Second Stag...

Page 9: ...gle Stage Compressor Y Y2 Second or Full Stage Compressor W1 First Stage Heat Y Full Stage Compressor G Fan BP11C50124 BN11C01124 DP11C40124 DN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt H...

Page 10: ...G Fan SINGLE STAGE PSC FURNACE Y1 Single Stage Compressor Other Part Numbers SAP Legacy 265902 031 09167 1 1 HM1 Humidistat Y Full Stage Compressor G Fan PP11C70224 THERMOSTAT RH 24 Volt Hot Heat XFMR...

Page 11: ...ssary C 24 Volt Common Y Full Stage Compressor G Fan BN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Heat Thermostat Installer Setup 1 System Type must be set to 0...

Page 12: ...r The installer should also instruct the owner on proper operation and maintenance of all other system components MAINTENANCE 1 Dirt should not be allowed to accumulate on the outdoor coils or other p...

Reviews: