background image

290982-UIM-C-0907

6

Unitary Products Group

SUBCOOLING CHARGING METHOD - TXV INDOOR

The recommended subcooling is 10°F

1.

Set the system running in the cooling mode by setting the thermo-
stat at least 6°F below the room temperature.

2.

Operate the system for a minimum of 15-20 minutes.

3.

Refer to the tabular data sheet for the recommended airflow and
verify this indoor airflow (it should be about 400 SCFM per ton).

4.

Measure the liquid refrigerant pressure P and temperature T at the
service valve.

5.

Calculate the saturated liquid temperature ST from Table 2.

6.

Subcooling temperature TC = Saturated Temperature (ST) - Liquid
Temp (T).

Add charge if the calculated subcooling temperature TC in Step 6 is
lower than the recommended level. Remove and recover the refrigerant
if the subcooling TC is higher than the recommended level. See Table
2.

Check flare caps on service ports to be sure they are leak tight. DO
NOT OVERTIGHTEN (between 40 and 60 inch - lbs. maximum).

SECTION VIII: ELECTRICAL 

CONNECTIONS

GENERAL INFORMATION & GROUNDING

Check the electrical supply to be sure that it meets the values specified
on the unit nameplate and wiring label.

Power wiring, control (low voltage) wiring, disconnect switches and over
current protection must be supplied by the installer. Wire size should be
sized per NEC requirements.

The complete connection diagram and schematic wiring label is located
on the inside surface of the unit service access panel.

FIELD CONNECTIONS POWER WIRING

1.

Install the proper size weatherproof disconnect switch outdoors
and within sight of the unit.

2.

Remove the screws at the top and sides of the corner cover. Slide
corner cover down and remove from unit.

3.

Run power wiring from the disconnect switch to the unit.

4.

Route wires from disconnect through power wiring opening pro-
vided and into the unit control box as shown in Figure 6.

5.

Install the proper size time-delay fuses or circuit breaker, and
make the power supply connections.

Example: The pressure P and temperature T measured at the liq-
uid service port is 196 psig and 90°F, respectlvely. From Table 2, 
the saturated temperature for 196 psig is 100°F. The subcooling 
temperature TC = 100°-90°=10°F

TABLE 2: 

R-22 Saturated Properties

Pressure 

PSIG

Temp °F

Pressure 

PSIG

Temp °F

Pressure 

PSIG

Temp °F

Pressure 

PSIG

Temp °F

Pressure 

PSIG

Temp °F

Pressure 

PSIG

Temp °F

80

48

110

64

140

78

170

91

200

101

230

111

82

49

112

65

142

79

172

91

202

102

232

112

84

50

114

66

144

80

174

92

204

103

234

112

86

51

116

67

146

81

176

93

206

103

236

113

88

52

118

68

148

82

178

94

208

104

238

114

90

54

120

69

150

83

180

94

210

105

240

114

92

55

122

70

152

84

182

95

212

105

242

115

94

56

124

71

154

84

184

96

214

106

244

115

96

57

126

72

156

85

186

97

216

107

246

116

98

58

128

73

158

86

188

97

218

107

248

117

100

59

130

74

160

87

190

98

220

108

250

117

102

60

132

75

162

88

192

99

222

109

252

118

104

61

134

76

164

88

194

99

224

109

254

118

106

62

136

77

166

89

196

100

226

110

256

119

108

63

138

78

168

90

198

101

228

111

258

119

IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS-
CHARGE REFRIGERANT INTO THE OPEN AIR DURING
REPAIR, SERVICE, MAINTENANCE OR THE FINAL DISPOSAL
OF THIS UNIT.
WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND THE
OWNER HAS BEEN FULLY INSTRUCTED, SECURE THE
OWNER’S APPROVAL.

All field wiring must USE COPPER CONDUCTORS ONLY and be
in accordance with Local, National, Fire, Safety & Electrical Codes.
This unit must be grounded with a separate ground wire in accor-
dance with the above codes.

 FIGURE 6:  

Outdoor Unit Control Box

GROUND
LUG

“FINGERED”
BUSHING

LOW
VOLTAGE
BOX

REVERSIBLE HIGH
VOLTAGE CONDUIT PLATE

DUAL
RUN/FAN
CAPACITOR

CONTACTOR

Summary of Contents for 13 SEER GCGD12

Page 1: ...des and the limitations listed below 1 Limitations for the indoor unit coil and appropriate accessories must also be observed 2 The outdoor unit must not be installed with any duct work in the air str...

Page 2: ...osition The base pad should not come in contact with the foun dation or side of the structure because sound may be transmitted to the residence The length of the refrigerant tubing between the outdoor...

Page 3: ...ions orifice connections system charging traps etc PRECAUTIONS DURING BRAZING OF LINES All outdoor unit and evaporator coil connections are copper to copper and should be brazed with a phosphorous cop...

Page 4: ...e System Charge section for checking and recording system charge Supplied with the outdoor unit is a Schrader Valve Core and Orifice for highest sales volume indoor coil The valve core must be install...

Page 5: ...bove 500 microns SECTION VII SYSTEM CHARGE The factory charge in the outdoor unit includes enough charge for the unit a 15 ft line set and the smallest indoor coil match up Some indoor coil matches ma...

Page 6: ...switch to the unit 4 Route wires from disconnect through power wiring opening pro vided and into the unit control box as shown in Figure 6 5 Install the proper size time delay fuses or circuit breake...

Page 7: ...o not place it on an out side wall or where it is exposed to the radiant effect from exposed glass or appliances drafts from outside doors or supply air grilles 6 Route the 24 volt control wiring NEC...

Page 8: ...ric heat on thermostat is not necessary MA SHP AHP ID MODELS Other Part Numbers SAP Legacy 265902 031 09167 2 Part Numbers SAP Legacy 159480 031 09156 1 COM 24 Volt Common R 24 Volt Hot W2 Second Stag...

Page 9: ...gle Stage Compressor Y Y2 Second or Full Stage Compressor W1 First Stage Heat Y Full Stage Compressor G Fan BP11C50124 BN11C01124 DP11C40124 DN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt H...

Page 10: ...G Fan SINGLE STAGE PSC FURNACE Y1 Single Stage Compressor Other Part Numbers SAP Legacy 265902 031 09167 1 1 HM1 Humidistat Y Full Stage Compressor G Fan PP11C70224 THERMOSTAT RH 24 Volt Hot Heat XFMR...

Page 11: ...ssary C 24 Volt Common Y Full Stage Compressor G Fan BN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Heat Thermostat Installer Setup 1 System Type must be set to 0...

Page 12: ...r The installer should also instruct the owner on proper operation and maintenance of all other system components MAINTENANCE 1 Dirt should not be allowed to accumulate on the outdoor coils or other p...

Reviews: