Deluxe Media Air Cleaners

Model 1625 & 2025

READ INSTRUCTIONS BEFORE BEGINNING INSTALLATION

Safety and Installation Manual

Model 1625 & 2025 Deluxe Media Air Cleaner

WARNING

120/220 Volts may cause serious injury from electrical
shock.

Disconnect power to the furnace/air conditioner before

starting installation.

Sharp edges may cause injury from cuts.

Use care when

cutting and handling sheet metal.

CAUTION

To prevent component failure, do not install the air
cleaner on the warm air supply or in an area where
the temperature may exceed 180°F. This may include
areas above heat exchangers in downflow furnaces or
above exhaust flues in lowboy furnace cold air returns.

IMPORTANT

• The Model 1625 and 2025 Deluxe Media Air Cleaners are designed for systems with airflow up to 2000 cfm. Follow the furnace

manufacturer’s recommendations for the number of return air plenums and install one Model 1625/2025 Deluxe Media Air Cleaner
in each.

• The air cleaner can be installed horizontally, vertically or at an angle depending on furnace type. See 

Figures 1, 2, 3 and 4

on

reverse side for orientation with various types of applications. Note airflow direction arrows on inner assembly and outer housing.

• Allow 29” clearance in front of Model 1625 and 26” in front of Model 2025 for media replacement.

• 

Figure 5

shows the dimensions for both air cleaners. If a transition duct is required, see 

Figure 4

for recommended duct angles.