background image

271001-UIM-A-0407

EFFICIENCY
RATING
CERTIFIED

ISO 9001

Certified Quality

Management System

HIGH EFFICIENCY
TUBULAR HEAT EXCHANGER SERIES

MODEL: AHV8*UH

(Two Stage Variable Speed Upflow / Horizontal / Low NOx)

57 - 120 MBH INPUT
(16.7 - 35.2 KW) INPUT

INSTALLATION MANUAL

SECTION I: SAFETY

This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.

Understand and pay particular attention to the signal words 

DANGER

,

WARNING

, or 

CAUTION

.

DANGER 

indicates an 

imminently

 hazardous situation, which, if not

avoided, 

will result in death or serious injury

.

WARNING 

indicates a 

potentially

 hazardous situation, which, if not

avoided, 

could result in death or serious injury

.

CAUTION 

indicates a potentially hazardous situation, which, if not

avoided 

may result in minor or moderate injury.

 It is also used to

alert against unsafe practices and hazards involving only property dam-
age.

Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.

This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.

LIST OF SECTIONS

SAFETY  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
DUCTWORK  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FILTERS   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
GAS PIPING   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
ELECTRICAL POWER   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

VENT SYSTEM   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
SAFETY CONTROLS   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . .20
WIRING DIAGRAM   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28

LIST OF FIGURES

Dimensions   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Typical Attic Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Typical Suspended Furnace / Crawl Space Installation  . . . . . . . . . . . . 7
Side Return Cutout Markings  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Upflow Gas Piping  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Horizontal Gas Piping   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Wiring  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Thermostat Chart - AC  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Thermostat Chart - HP  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Accessory Connections  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Vent Termination  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Vent Termination 10 ft. (3.0 m) or less . . . . . . . . . . . . . . . . . . . . . . . . 14
Vent Termination more than 10 ft. (3.0 m)  . . . . . . . . . . . . . . . . . . . . . 14

Typical Sidewall Vent Application  . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Typical Sidewall Vent and Termination Configuration   . . . . . . . . . . . .15
Home Layout   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Combustion Airflow Path Through The Furnace . . . . . . . . . . . . . . . . .17
Alternate Air Intake, Air Outlet and Chimney Connections  . . . . . . . . .17
Air Inlet, Outlet and Chimney Connections . . . . . . . . . . . . . . . . . . . . .17
Typical Chimney Connections   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Horizontal Air Inlet, Outlet and Chimney Connections  . . . . . . . . . . . .18
Outside and Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . .18
Pressure Switch Tubing Routing   . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Gas Valve  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Reading Gas Pressure  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Furnace Control Board  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Wiring Diagram  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28

LIST OF TABLES

Unit Clearances to Combustibles  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Minimum Duct Sizing For Proper Airflow  . . . . . . . . . . . . . . . . . . . . . . . 5
Round Duct Size   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Cabinet and Duct Dimensions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Filter Sizes  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Nominal Manifold Pressure - High Fire   . . . . . . . . . . . . . . . . . . . . . . . . 9
Nominal Manifold Pressure - Low Fire  . . . . . . . . . . . . . . . . . . . . . . . . . 9
Ratings & Physical / Electrical Data  . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Roof Pitch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Estimated Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Free Area  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Unconfined Space Minimum Area in Square Inch   . . . . . . . . . . . . . . .18
Inlet Gas Pressure Range   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Filter Performance - Pressure Drop Inches W.C. and (kPa) . . . . . . . .25
Air Flow Data   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Field Installed Accessories - Non Electrical  . . . . . . . . . . . . . . . . . . . .27

Summary of Contents for AHV8 UH

Page 1: ...ited to building electrical and mechanical codes LIST OF SECTIONS SAFETY 1 DUCTWORK 4 FILTERS 8 GAS PIPING 8 ELECTRICAL POWER 10 VENT SYSTEM 14 SAFETY CONTROLS 19 START UP AND ADJUSTMENTS 20 WIRING DI...

Page 2: ...s from combustible materials as listed under Clearances to Combustibles in Table 1 Provide clearances for servicing ensuring that service access is allowed for both the burners and blower These models...

Page 3: ...ed Never store items such as the following on near or in contact with the fur nace 1 Spray or aerosol cans rags brooms dust mops vacuum cleaners or other cleaning tools 2 Soap powders bleaches waxes o...

Page 4: ...erates at the specified external static pressure and within the air temperature rise specified on the nameplate Table 2 is a guide for determining whether the rectangular duct system that the furnace...

Page 5: ...supply plenum On all installations without a coil a removable access panel is recommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indi cate the...

Page 6: ...floor support with required service accessibility IMPORTANT If an external mounted filter rack is being used see the instructions provided with that accessory for proper hole cut size HORIZONTAL MODEL...

Page 7: ...removed and a new plenum installed that is the proper size for the new furnace Attach the return plenum to the furnace inlet duct flanges This is typi cally through the use of S cleat material when a...

Page 8: ...IV GAS PIPING GAS SAFETY IMPORTANT Plan your gas supply before determining the correct gas pipe entry Use 90 degree service elbow s or short nipples and con ventional 90 degree elbow s to enter throu...

Page 9: ...ing The gas valve body is a very thin casting that cannot take any external pressure Never apply a pipe wrench to the body of the gas valve when installing piping A wrench must be placed on the octag...

Page 10: ...er must take every precaution to insure that the furnace has been converted to the proper gas orifice size when the furnace is installed Do not attempt to drill out any orifices to obtain the proper o...

Page 11: ...ty is corrected Refer to FURNACE DIAGNOSTICS section of the User s Information Maintenance Service Manual provided with this furnace for symptoms of reversed power supply polarity LOW VOLTAGE CONTROL...

Page 12: ...Stage Cool Y2 Second Stage Cool W2 Second Stage Heat G Fan R 24 Volt Hot W First Stage Heat Y1 First Stage Cool R 24 Volt Hot Y Y2 Single Second Stage Cool Y2 Second Stage Cool W2 Second Stage Heat G...

Page 13: ...versing Valve Energized in Cool O Reversing Valve Energized in Cool O Reversing Valve Energized in Cool Y2 Second Stage Heat Cool DHM Dehumidistat HUM Dehumidification Open on Humidity Rise Y2 Second...

Page 14: ...ssory Connections FIGURE 12 Vent Termination 115 VOLT HUMIDIFER 115 VOLT ELECTRONIC AIR CLEANER EAC HOT HUM HOT BLK WHT EAC HUM NEUTRALS SWITCHED CIRCUITS BLK WHT LOWEST DISCHARGE OPENING LISTED CAP L...

Page 15: ...the authority having jurisdiction Venting into an unlined masonry chimney or concrete chimney is prohibited Whenever possible B 1 metal pipe should be used for venting Where use of an existing chimne...

Page 16: ...nd from any direction will not create a positive pressure in the vicinity of the vent FIGURE 17 Home Layout L E D B V V V X V B V J X B B B V V F V C B X V I V G H A M K OPERABLE FIXED CLOSED VENT TER...

Page 17: ...obtain proper air for combus tion and ventilation in confined spaces Combustion Air Source From Outdoors The blocking effects of louvers grilles and screens must be given con sideration in calculatin...

Page 18: ...el of the appliance Refer to COMBUSTION AIR SOURCE FROM OUTDOORS and VENT AND SUPPLY AIR SAFETY CHECK in these instructions for additional information and safety check procedure 2 The duct shall be ei...

Page 19: ...ustion air blower heat exchanger or a blocked vent pipe connection Corrective action is required These are manual reset controls that must be reset before operation can continue PRESSURE SWITCHES This...

Page 20: ...in w c 0 3 73 kPa in order to measure the gas line and the manifold pressures 4 You will need a 3 32 Allen wrench for the pressure port plugs in the gas valve 5 You will need 2 pieces of 1 8 0 3 cm ID...

Page 21: ...at the gas meter times a barometric pressure and temperature correction factor of 0 960 times 3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas mul...

Page 22: ...h low and high have been calibrated at the factory Additional pressure adjustment should not be necessary If adjustment is necessary set to the following specifications After adjustment check for gas...

Page 23: ...eed to the other Tap B is the humid profile This profile is best suited for installations where the humidity is frequently very high during cooling season such as in the southern part of the country O...

Page 24: ...pressure switch or miswiring 3 RED FLASHES This indicates the normally open pressure switch contact did not close after the inducer was energized This could be caused by a number of problems faulty i...

Page 25: ...ry the LED will flash two green flashes To clear the memory push the LAST ERROR button and hold it for more than five seconds The LED will flash three green flashes when the memory has been cleared th...

Page 26: ...47 5 30 9 47 5 30 9 1540 1001 1540 1001 C B 43 6 28 3 43 6 28 3 1440 936 1440 936 B C 40 8 26 5 40 8 26 5 1320 858 1320 858 D B 37 4 24 3 37 4 24 3 1400 910 1400 910 C A 39 6 25 8 39 6 25 8 1200 780 1...

Page 27: ...stem static from 0 60 w c 150 Pa and divide this by 0 1 w c 25 Pa 0 68 170 Pa 0 60 150 Pa 0 08 20 Pa 0 08 20 Pa 0 1 25 Pa 0 8 Multiply this by 2 to obtain the percentage reduction in airflow 0 8 x 0 0...

Page 28: ...Printed in U S A 271001 UIM A 0407 Copyright by York International Corp 2007 All rights reserved Supersedes 167187 UIM C 0806 Unitary 5005 Norman Product York OK Group Drive 73069 SECTION IX WIRING D...

Reviews: