Unitary Products Group

13

530.22-N5W

MODEL

POWER SUP-

PLY

COMPRESSORS

CONDENSER FAN

MOTORS

(#1 & #2)

SUPPLY AIR

BLOWER

MOTOR

MINIMUM

CIRCUIT

AMPACITY

(AMPS)

MAXIMUM

TIME DELAY

FUSE SIZE

(AMPS)

MINIMUM

WIRE
SIZE*

(AWG)

#1

#2

RLA LRA RLA LRA

HP

EACH

FLA

EACH

HP

FLA

75

°

C

DAHC180

208/230-3-60

33.4 300 16.7

150

1

4.2

5

14.4

77.0

90

4

460-3-60

19.2 146

9.6

73

1

2.1

5

7.2

42.7

50

8

575-3-60

12.8 124

6.4

62

1

2.0

5

5.9

30.7

35

8

DAHC240

208/230-3-60

16.0 274 16.0

274

1

4.2

7.5

19.4

96.8

110

3

460-3-60

9.0

138

9.7

138

1

2.1

7.5

9.7

52.2

60

6

575-3-60

6.6

116

6.6

116

1

2.0

7.5

7.8

40.2

45

8

*

Although these sizes are based on copper conductors, aluminum wire can be used.

Refer to the National Electric Code ( in U.S.A.) or the current Canadian Electrical Code
(in Canada) to determine the proper size.

TABLE 10 - ELECTRICAL DATA (BASIC UNITS)

VOLTAGE

LIMITATIONS**

POWER SUPPLY

VOLTAGE

MIN.

MAX.

208/230-3-60

187

253

460-3-60

414

506

575-3-60

518

630

**

Utilization Range “A” in accordance with ARI Standard 110.

MODEL

DAHC

POWER

SUPPLY

HEATER OPTION

MINIMUM

CIRCUIT

AMPACITY

(AMPS)

MAXIMUM

TIME DELAY

FUSE SIZE

(AMPS)

MINIMUM

WIRE SIZE

2

(AWG)

MODEL

KW

1

STAGES

AMPS

75

°

C

-T180A

208-3-60

E018
E036
E054
E072

13.5
27.0
40.6
54.1

1
2
2
2

37.5
75.1

112.6

150.1

77.0

11.8

158.7
168.1

90

125
175
200

3
2

00
00

230-3-60

E018
E036
E054
E072

18.0
36.0
54.0
72.0

1
2
2
2

43.3
86.6

129.9
173.2

77.0

126.3
147.9
191.2

90

150
175
225

4
1
0

000

-W180A

460-3-60

E018
E036
E054
E072

18.0
36.0
54.0
72.0

1
2
2
2

21.7
43.3
65.0
86.6

42.9
63.1
74.0
95.6

50
70
90

110

8
6
4
3

-X180A

575-3-60

E018
E036
E054
E072

18.0
36.0
54.0
72.0

1
2
2
2

17.3
34.6
52.0
69.3

30.7
50.7
59.3
76.7

35
60
70
90

8
6
6
4

-T240A

208-3-60

E018
E036
E054
E072

13.5
27.0
40.6
54.1

1
2
2
2

37.5
75.1

112.6

150.1

96.8

118.1

165.0
174.4

110

125
175
200

3
1

00
00

230-3-60

E018
E036
E054
E072

18.0
36.0
54.0
72.0

1
2
2
2

43.3
86.6

129.9
173.2

96.8

132.5
154.2
197.5

125
150
175
225

3
0

00

000

-W240A

460-3-60

E018
E036
E054
E072

18.0
36.0
54.0
72.0

1
2
2
2

21.7
43.3
65.0
86.6

52.2
66.3
77.1
98.7

60
70
90

110

6
4
4
3

-X240A

575-3-60

E018
E036
E054
E072

18.0
36.0
54.0
72.0

1
2
2
2

17.3
34.6
52.0
69.3

40.2
53.1
61.7
79.0

45
60
70
90

8
6
6
4

1

Electric Heat CORRECTION FACTORS:

TABLE 11 - ELECTRICAL DATA

2

Although these sizes are based on copper conductors, aluminum wire can be used.

Refer to the National Electric code ( in U.S.A.) or the current Canadian Electrical Code
(in Canada) to determine the proper size.

(UNITS w/SUPPLEMENTAL ELECTRIC HEAT)

NOMINAL VOLTAGE

VOLTAGE

KW CAP. MULTIPLIER

208

208

1.00

240

230

0.92

480

460

0.92

600

575

0.92

Summary of Contents for DAHC180

Page 1: ...al for complete listing of replacement parts on this equipment All forms referenced in this instruction may be ordered from Standard Register 2101 West Tecumseh Road Norman Oklahoma 73069 Toll Free Fax 877 379 7920 Toll Free Phone 877 319 9675 APPROVALS Design certified by ETL CGA as follows 1 For use as a central cooling only unit with or without supple mental electric heat 2 For outdoor installa...

Page 2: ...ly Air Blower Perf 20 Ton 11 7 Static Resistances 12 8 Power Exhaust Performance 12 9 Blower Motor and Drive Data 12 10 Electrical Data Basic Units 13 11 Electrical Data Units w Elec Heat 13 12 Heat Anticipator Setpoints 15 FIGURES No Description Page 1 Typical Rigging 3 2 Center of Gravity 3 3 Fixed Outdoor Air Damper 4 4 Recommended Drain Piping 4 5 Typical Field Wiring 5 6 Adjusting Enthalpy Se...

Page 3: ...n the base rails Spreaders whose length exceeds the larger dimension across the unit MUST be used across the top of the unit Refer to Figure 1 Units may also be moved or lifted with a forklift from the front or rear only providing that an accessory skid is used LENGTH OF FORKS MUSTBE AMINIMUM OF 90 INCHES Refer to Table 4 for unit weights and to Figure 2 for approximate center of gravity CLEARANCE...

Page 4: ...it to an open drain An alternate drain connection one inch NPT female coupling is provided inboard on the same centerline as the exterior location NOTE The condensate drain line MUST be trapped to pro vide proper drainage See Figure 4 COMPRESSORS Units are shipped with compressor mountings factory adjusted and ready for operation CAUTION Do Not loosen compressor mounting bolts FILTERS Two inch fil...

Page 5: ......

Page 6: ...halpy setpoint may now be set by selecting the desired setpoint shown in Figure 8 Adjust by carefully turning the setpoint adjusting screw to the A B C or D setting corresponding to the lettered curve 7 To check that the damper blades move smoothly without binding carefully turn the minimum position adjusting screw fully clockwise and then energize and de energize terminals R to G With terminals R...

Page 7: ...Unitary Products Group 7 530 22 N5W FIG 6 ENTHALPY SETPOINT ADJUSTMENT ...

Page 8: ...20 FACE AREA Sq Ft Each 36 0 43 3 COMPRESSOR Qty Per Unit 10 TON TANDEM 1 2 5 TON HERMETIC 1 AIR FILTERS QUANTITY PER UNIT 16 X 20 X 2 4 QUANTITY PER UNIT 16 X 25 X 2 4 QUANTITY PER UNIT 18 X 24 X 2 5 TOTAL FACE AREA sq ft 15 0 20 0 CHARGE REFRIGERANT 22 lbs oz SYSTEM NO 1 20 8 18 8 SYSTEM NO 2 10 8 18 8 This compressor will be energized first OPERATING WEIGHTS LBS 15 TON 20 TON Basic Unit Cooling...

Page 9: ...of the unit RETURN AIR OUTDOOR AIR Economizer SUPPLY AIR CONDENSER AIR DETAIL X ACCESSORY SIDE SUPPLY AND RETURN AIR OPENINGS Front 36 Back 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Economizer 54 With Economizer Right Side Cond Coil 36 Below Unit1 20 Above Unit2 72 With 36 Maximum Horizontal Overhang For Condenser Air Discharge Outlet NOTE Unit and ductwork are approved...

Page 10: ... 4 6 1170 1 0 2 1 3 9 3 5 2 0 4 7 4 2 1 8 5 5 4 9 230 460 575 VOLT AND STANDARD DRIVE 870 6 0 1 0 2 4 2 2 0 8 3 1 2 8 0 6 3 5 3 1 0 2 4 1 3 7 915 5 0 1 1 2 6 2 4 0 9 3 3 3 0 0 7 3 7 3 3 0 3 4 4 3 9 0 2 4 5 4 0 965 4 0 1 2 2 9 2 6 1 0 3 6 3 2 0 8 4 0 3 6 0 5 4 7 4 2 0 4 5 0 4 4 980 3 5 1 3 3 0 2 7 1 1 3 7 3 3 0 9 4 1 3 7 0 6 4 8 4 3 0 5 5 1 4 6 1040 2 0 1 5 3 2 2 9 1 3 3 9 3 5 1 1 4 5 4 0 0 9 5 3 4...

Page 11: ...T AND STANDARD DRIVE 870 6 0 0 4 2 1 1 8 0 1 2 3 2 0 900 5 0 0 8 3 2 2 7 0 5 3 5 2 9 0 2 3 8 3 2 930 4 0 1 1 4 1 3 4 0 9 4 5 3 8 0 6 4 9 4 1 0 1 5 1 4 3 950 3 5 1 3 4 6 3 9 1 1 5 1 4 3 0 8 5 5 4 6 0 4 5 9 5 0 980 2 5 1 6 5 3 4 5 1 4 5 8 4 9 1 2 6 3 5 3 0 7 6 9 5 8 0 2 7 3 6 1 1015 1 5 1 9 5 9 5 0 1 7 6 5 5 5 1 5 7 0 5 9 1 0 7 7 6 5 0 6 8 2 6 9 1025 1 0 2 0 6 1 5 1 1 8 6 6 5 6 1 6 7 3 6 1 1 1 7 9 6...

Page 12: ...75 11 4 1 3 16 BX83 84 8 1 High Speed Access 950 1120 BK110 10 75 10 4 1 3 16 BX81 81 8 1 1 All motors have a nominal speed of 1800 RPM a 1 15 service factor and a solid base They can operate to the limit of their service factor because they are located in the moving air upstream of any heating device 2 Do NOT close this pulley below 1 turn open TABLE 9 BLOWER MOTOR AND DRIVE DATA EXTERNAL STATIC ...

Page 13: ... 0 40 6 54 1 1 2 2 2 37 5 75 1 112 6 150 1 77 0 11 8 158 7 168 1 90 125 175 200 3 2 00 00 230 3 60 E018 E036 E054 E072 18 0 36 0 54 0 72 0 1 2 2 2 43 3 86 6 129 9 173 2 77 0 126 3 147 9 191 2 90 150 175 225 4 1 0 000 W180A 460 3 60 E018 E036 E054 E072 18 0 36 0 54 0 72 0 1 2 2 2 21 7 43 3 65 0 86 6 42 9 63 1 74 0 95 6 50 70 90 110 8 6 4 3 X180A 575 3 60 E018 E036 E054 E072 18 0 36 0 54 0 72 0 1 2 ...

Page 14: ...t is set in the ON position ECONOMIZER WITH POWER EXHAUST This system operates as specified above with one addition The power exhaust motor is energized whenever the economizer is chosen by the enthalpy sensor for first stage cooling Y1 As always the R to G connection provides minimum position but does not provide power exhaust operation MOTORIZED OUTDOOR AIR DAMPERS This system operation is the s...

Page 15: ...n the equipment installer To check the supply air CFM after the initial balancing has been completed 1 Remove the two 5 16 inch dot plugs from the blower motor and the filter access panels shown in Figure 9 2 Insert at least 8 inches of 1 4 inch tubing into each of these holes for sufficient penetration into the air flow on both sides of the indoor coil NOTE The tubes must be inserted and held in ...

Page 16: ...n grease fitting Using a low pressure grease gun pump grease Chevron SRI 2 or equivalent into the bearing cavity until new grease shows at the open port Do not over lubricate Run the motor for ten minutes until excess grease is purged from the cavity Replace the plugs On 20 ton only units are supplied with blower shaft bearings that do not require maintenance but may be relubricated if desired Eve...