background image

The thermostat will cycle the electric heat to satisfy the
heating requirements of the conditioned space.

HEAT ANTICIPATOR SETPOINTS

It is important that the anticipator setpoint be correct. Too high
of a setting will result in longer heat cycles and a greater
temperature swing in the conditioned space. Reducing the
value below the correct setpoint will give shorter “ON” cycles

and may result in the lowering of the temperture within the
conditioned space. Refer to Table 12 for the required heat
anticipator setting.

CHECKING SUPPLY AIR CFM

The RPM of the supply air blower will depend on the required
CFM, the unit options/accessories and the static resistances of
both the supply and the return air duct systems. With this
information, the RPM for the supply air blower and the motor
pulley adjustment (turns open) can be determined from the
blower performance data in Tables 5 and 6.
High speed drive accessories (containing a smaller blower
pulley and a shorter belt) are available for applications
requiring the supply air blower to produce higher CFM's and/or
higher static pressures. Use Model 1LD0416 for 15 ton units
and Model 1LD0417 for 20 ton units. Refer to Table 9 for blower
motor and drive data.
Note the following:

1. The supply air CFM must be within the limitations shown in

Table 1.

2. Pulleys can be adjusted in half turn increments.
3. The tension on the belt should be adjusted as shown in

Figure 10.

Start the supply air blower motor. Adjust the resistances in both
the supply and the return air duct systems to balance the air
distribution throughout the conditioned space. The job
specifications may require that this balancing be done by
someone other than the equipment installer.
To check the supply air CFM after the initial balancing has been
completed:

1. Remove the two 5/16 inch dot plugs from the blower motor

and the filter access panels shown in Figure 9.

2. Insert at least 8 inches of 1/4 inch tubing into each of these

holes for sufficient penetration into the air flow on both sides
of the indoor coil.

NOTE: The tubes must be inserted and held in a position per-

pendicular to the air flow so that velocity pressure will
not affect the static pressure readings.

3. Using an inclined manometer, determine the pressure drop

across a dry indoor coil. Since the moisture on an indoor
coil may vary greatly, measuring the pressure drop across a
wet coil under field conditions would be inaccurate. To
assure a dry coil, the compressors whould be de-activated
while the test is being run.

4. Knowing the pressure drop across a dry coil, the actual

CFM through the unit and clean two-inch filters, can be
determined from the curve in Figure 11.

WARNING: Failure to properly adjust the total system air

quantity can result in extensive blower damage.

After readings have been obtained, remove the tubes and
reinstall the two 5/16 inch dot plugs that were removed in Step
1.

NOTE:

DE-ENERGIZE THE COMPRESSORS BEFORE TAKING
ANY TEST MEASUREMENTS TO ASSURE A DRY IN-
DOOR COIL.

BELT DRIVE BLOWER

All units have belt drive single-speed blower motors. The
variable pitch pulley on the blower motor can be adjusted to
obtain the desired supply air CFM. Tighten belts enough to

Unitary Products Group

15

530.22-N5W

FIG.[f#] - BELT ADJUSTMENT

HEATER

KW

VOLTAGE

SETTING, AMPS

TH1

TH2

18

208/230-3-60

0.29

-

36

0.29

0.29

54

0.29

0.58

72

0.58

0.58

18

460-3-60

0.29

-

36

0.29

0.29

54

0.29

0.29

72

0.29

0.29

18

575-3-60

0.29

-

36

0.29

0.29

54

0.29

0.29

72

0.29

0.29

TABLE 12 - HEAT ANTICIPATOR SETTING

FIG. 9 - PRESSURE DROP ACROSS A DRY INDOOR

COIL VS SUPPLY AIR CFM

Summary of Contents for DAHC180

Page 1: ...al for complete listing of replacement parts on this equipment All forms referenced in this instruction may be ordered from Standard Register 2101 West Tecumseh Road Norman Oklahoma 73069 Toll Free Fax 877 379 7920 Toll Free Phone 877 319 9675 APPROVALS Design certified by ETL CGA as follows 1 For use as a central cooling only unit with or without supple mental electric heat 2 For outdoor installa...

Page 2: ...ly Air Blower Perf 20 Ton 11 7 Static Resistances 12 8 Power Exhaust Performance 12 9 Blower Motor and Drive Data 12 10 Electrical Data Basic Units 13 11 Electrical Data Units w Elec Heat 13 12 Heat Anticipator Setpoints 15 FIGURES No Description Page 1 Typical Rigging 3 2 Center of Gravity 3 3 Fixed Outdoor Air Damper 4 4 Recommended Drain Piping 4 5 Typical Field Wiring 5 6 Adjusting Enthalpy Se...

Page 3: ...n the base rails Spreaders whose length exceeds the larger dimension across the unit MUST be used across the top of the unit Refer to Figure 1 Units may also be moved or lifted with a forklift from the front or rear only providing that an accessory skid is used LENGTH OF FORKS MUSTBE AMINIMUM OF 90 INCHES Refer to Table 4 for unit weights and to Figure 2 for approximate center of gravity CLEARANCE...

Page 4: ...it to an open drain An alternate drain connection one inch NPT female coupling is provided inboard on the same centerline as the exterior location NOTE The condensate drain line MUST be trapped to pro vide proper drainage See Figure 4 COMPRESSORS Units are shipped with compressor mountings factory adjusted and ready for operation CAUTION Do Not loosen compressor mounting bolts FILTERS Two inch fil...

Page 5: ......

Page 6: ...halpy setpoint may now be set by selecting the desired setpoint shown in Figure 8 Adjust by carefully turning the setpoint adjusting screw to the A B C or D setting corresponding to the lettered curve 7 To check that the damper blades move smoothly without binding carefully turn the minimum position adjusting screw fully clockwise and then energize and de energize terminals R to G With terminals R...

Page 7: ...Unitary Products Group 7 530 22 N5W FIG 6 ENTHALPY SETPOINT ADJUSTMENT ...

Page 8: ...20 FACE AREA Sq Ft Each 36 0 43 3 COMPRESSOR Qty Per Unit 10 TON TANDEM 1 2 5 TON HERMETIC 1 AIR FILTERS QUANTITY PER UNIT 16 X 20 X 2 4 QUANTITY PER UNIT 16 X 25 X 2 4 QUANTITY PER UNIT 18 X 24 X 2 5 TOTAL FACE AREA sq ft 15 0 20 0 CHARGE REFRIGERANT 22 lbs oz SYSTEM NO 1 20 8 18 8 SYSTEM NO 2 10 8 18 8 This compressor will be energized first OPERATING WEIGHTS LBS 15 TON 20 TON Basic Unit Cooling...

Page 9: ...of the unit RETURN AIR OUTDOOR AIR Economizer SUPPLY AIR CONDENSER AIR DETAIL X ACCESSORY SIDE SUPPLY AND RETURN AIR OPENINGS Front 36 Back 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Economizer 54 With Economizer Right Side Cond Coil 36 Below Unit1 20 Above Unit2 72 With 36 Maximum Horizontal Overhang For Condenser Air Discharge Outlet NOTE Unit and ductwork are approved...

Page 10: ... 4 6 1170 1 0 2 1 3 9 3 5 2 0 4 7 4 2 1 8 5 5 4 9 230 460 575 VOLT AND STANDARD DRIVE 870 6 0 1 0 2 4 2 2 0 8 3 1 2 8 0 6 3 5 3 1 0 2 4 1 3 7 915 5 0 1 1 2 6 2 4 0 9 3 3 3 0 0 7 3 7 3 3 0 3 4 4 3 9 0 2 4 5 4 0 965 4 0 1 2 2 9 2 6 1 0 3 6 3 2 0 8 4 0 3 6 0 5 4 7 4 2 0 4 5 0 4 4 980 3 5 1 3 3 0 2 7 1 1 3 7 3 3 0 9 4 1 3 7 0 6 4 8 4 3 0 5 5 1 4 6 1040 2 0 1 5 3 2 2 9 1 3 3 9 3 5 1 1 4 5 4 0 0 9 5 3 4...

Page 11: ...T AND STANDARD DRIVE 870 6 0 0 4 2 1 1 8 0 1 2 3 2 0 900 5 0 0 8 3 2 2 7 0 5 3 5 2 9 0 2 3 8 3 2 930 4 0 1 1 4 1 3 4 0 9 4 5 3 8 0 6 4 9 4 1 0 1 5 1 4 3 950 3 5 1 3 4 6 3 9 1 1 5 1 4 3 0 8 5 5 4 6 0 4 5 9 5 0 980 2 5 1 6 5 3 4 5 1 4 5 8 4 9 1 2 6 3 5 3 0 7 6 9 5 8 0 2 7 3 6 1 1015 1 5 1 9 5 9 5 0 1 7 6 5 5 5 1 5 7 0 5 9 1 0 7 7 6 5 0 6 8 2 6 9 1025 1 0 2 0 6 1 5 1 1 8 6 6 5 6 1 6 7 3 6 1 1 1 7 9 6...

Page 12: ...75 11 4 1 3 16 BX83 84 8 1 High Speed Access 950 1120 BK110 10 75 10 4 1 3 16 BX81 81 8 1 1 All motors have a nominal speed of 1800 RPM a 1 15 service factor and a solid base They can operate to the limit of their service factor because they are located in the moving air upstream of any heating device 2 Do NOT close this pulley below 1 turn open TABLE 9 BLOWER MOTOR AND DRIVE DATA EXTERNAL STATIC ...

Page 13: ... 0 40 6 54 1 1 2 2 2 37 5 75 1 112 6 150 1 77 0 11 8 158 7 168 1 90 125 175 200 3 2 00 00 230 3 60 E018 E036 E054 E072 18 0 36 0 54 0 72 0 1 2 2 2 43 3 86 6 129 9 173 2 77 0 126 3 147 9 191 2 90 150 175 225 4 1 0 000 W180A 460 3 60 E018 E036 E054 E072 18 0 36 0 54 0 72 0 1 2 2 2 21 7 43 3 65 0 86 6 42 9 63 1 74 0 95 6 50 70 90 110 8 6 4 3 X180A 575 3 60 E018 E036 E054 E072 18 0 36 0 54 0 72 0 1 2 ...

Page 14: ...t is set in the ON position ECONOMIZER WITH POWER EXHAUST This system operates as specified above with one addition The power exhaust motor is energized whenever the economizer is chosen by the enthalpy sensor for first stage cooling Y1 As always the R to G connection provides minimum position but does not provide power exhaust operation MOTORIZED OUTDOOR AIR DAMPERS This system operation is the s...

Page 15: ...n the equipment installer To check the supply air CFM after the initial balancing has been completed 1 Remove the two 5 16 inch dot plugs from the blower motor and the filter access panels shown in Figure 9 2 Insert at least 8 inches of 1 4 inch tubing into each of these holes for sufficient penetration into the air flow on both sides of the indoor coil NOTE The tubes must be inserted and held in ...

Page 16: ...n grease fitting Using a low pressure grease gun pump grease Chevron SRI 2 or equivalent into the bearing cavity until new grease shows at the open port Do not over lubricate Run the motor for ten minutes until excess grease is purged from the cavity Replace the plugs On 20 ton only units are supplied with blower shaft bearings that do not require maintenance but may be relubricated if desired Eve...

Reviews: