background image

prevent slipping, but do not overtighten. Belt deflection should
be between 1/4 inch and 1/2 inch per foot.

NORMAL MAINTENANCE

CAUTION: Prior to any of the following maintenance proce-

dures, shut off all electric power to the unit to pre-
vent personal injury.

FILTERS - Inspect once a month. Replace disposable or clean
permanent type as necessary. DO NOT replace permanent
type with disposable. The dimensional size of the replacement
filter must be the same as the replaced filter.

MOTORS

Outdoor fan motors are permanently lubricated and require no
maintenance.

Indoor Blower Motor and Drive - The indoor blower motor
features ball bearings that do not require periodic lubrication.
Periodic lubrication of the motor and bearings can extend the
life of components but is optional.

CAUTION: Damage can occur if the bearings are overlubri-

cated. Use grease sparingly.

WARNING: Perform all maintenance operations on the blower

motor with electric power disconnected from the
unit. Do not attempt to lubricate bearings with the
unit in operation.

On an annual basis, check the motor for accumulations of dust,
etc. that may block the cooling slots in the motor shell. Check
for loose, damaged or misaligned drive components. Check
that all mounting bolts are tight. Replace defective parts as
required.

If desired, every three years remove both pipe plugs at each
end shell and clean out any hardened grease or foreign matter.

Replace one plug on each end with a clean grease fitting.
Using a low pressure grease gun, pump grease (Chevron SRI-
2 or equivalent) into the bearing cavity until new grease shows
at the open port. Do not over lubricate. Run the motor for ten
minutes until excess grease is purged from the cavity. Replace
the plugs.

On 20 ton only, units are supplied with blower shaft bearings
that do not require maintenance but may be relubricated if
desired. Every three years, using a low pressure grease gun,
pump grease into the bearing grease fitting until grease just
begins to show at the seals. Do not over lubricate. Use any
lithium base grease recommended for ball bearing service.

OUTDOOR COIL - Dirt should not be allowed to accumulate on
the outdoor coil surface or other parts in the air circuit. Cleaning
should be as often as necessary to keep coil clean. Use a
brush, vacuum cleaner attachment, or other suitable means. If
water is used to clean coil, be sure electric power to the unit is
shut off prior to cleaning.

NOTE: Exercise care when cleaning the coil so that the coil

fins are not damaged.

Do not permit the hot outdoor air discharge to be ob-
structed by overhanging structures of shrubs.

SECURE OWNER'S APPROVAL

When the system is functioning properly, secure the owner's approval. Show him the

location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust temperature set-
tings within the limitations of the system.

MAINTENANCE

Subject to change without notice.  Printed in U.S.A
Copyright

by Unitary Products Group 2000. All rights reserved.

530.22-N5W

Supersedes: 530.22-N5W
(1194)

Unitary
Products
Group

5005
York
Drive

Norman
Oklahoma
73069

Summary of Contents for DAHC180

Page 1: ...al for complete listing of replacement parts on this equipment All forms referenced in this instruction may be ordered from Standard Register 2101 West Tecumseh Road Norman Oklahoma 73069 Toll Free Fax 877 379 7920 Toll Free Phone 877 319 9675 APPROVALS Design certified by ETL CGA as follows 1 For use as a central cooling only unit with or without supple mental electric heat 2 For outdoor installa...

Page 2: ...ly Air Blower Perf 20 Ton 11 7 Static Resistances 12 8 Power Exhaust Performance 12 9 Blower Motor and Drive Data 12 10 Electrical Data Basic Units 13 11 Electrical Data Units w Elec Heat 13 12 Heat Anticipator Setpoints 15 FIGURES No Description Page 1 Typical Rigging 3 2 Center of Gravity 3 3 Fixed Outdoor Air Damper 4 4 Recommended Drain Piping 4 5 Typical Field Wiring 5 6 Adjusting Enthalpy Se...

Page 3: ...n the base rails Spreaders whose length exceeds the larger dimension across the unit MUST be used across the top of the unit Refer to Figure 1 Units may also be moved or lifted with a forklift from the front or rear only providing that an accessory skid is used LENGTH OF FORKS MUSTBE AMINIMUM OF 90 INCHES Refer to Table 4 for unit weights and to Figure 2 for approximate center of gravity CLEARANCE...

Page 4: ...it to an open drain An alternate drain connection one inch NPT female coupling is provided inboard on the same centerline as the exterior location NOTE The condensate drain line MUST be trapped to pro vide proper drainage See Figure 4 COMPRESSORS Units are shipped with compressor mountings factory adjusted and ready for operation CAUTION Do Not loosen compressor mounting bolts FILTERS Two inch fil...

Page 5: ......

Page 6: ...halpy setpoint may now be set by selecting the desired setpoint shown in Figure 8 Adjust by carefully turning the setpoint adjusting screw to the A B C or D setting corresponding to the lettered curve 7 To check that the damper blades move smoothly without binding carefully turn the minimum position adjusting screw fully clockwise and then energize and de energize terminals R to G With terminals R...

Page 7: ...Unitary Products Group 7 530 22 N5W FIG 6 ENTHALPY SETPOINT ADJUSTMENT ...

Page 8: ...20 FACE AREA Sq Ft Each 36 0 43 3 COMPRESSOR Qty Per Unit 10 TON TANDEM 1 2 5 TON HERMETIC 1 AIR FILTERS QUANTITY PER UNIT 16 X 20 X 2 4 QUANTITY PER UNIT 16 X 25 X 2 4 QUANTITY PER UNIT 18 X 24 X 2 5 TOTAL FACE AREA sq ft 15 0 20 0 CHARGE REFRIGERANT 22 lbs oz SYSTEM NO 1 20 8 18 8 SYSTEM NO 2 10 8 18 8 This compressor will be energized first OPERATING WEIGHTS LBS 15 TON 20 TON Basic Unit Cooling...

Page 9: ...of the unit RETURN AIR OUTDOOR AIR Economizer SUPPLY AIR CONDENSER AIR DETAIL X ACCESSORY SIDE SUPPLY AND RETURN AIR OPENINGS Front 36 Back 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Economizer 54 With Economizer Right Side Cond Coil 36 Below Unit1 20 Above Unit2 72 With 36 Maximum Horizontal Overhang For Condenser Air Discharge Outlet NOTE Unit and ductwork are approved...

Page 10: ... 4 6 1170 1 0 2 1 3 9 3 5 2 0 4 7 4 2 1 8 5 5 4 9 230 460 575 VOLT AND STANDARD DRIVE 870 6 0 1 0 2 4 2 2 0 8 3 1 2 8 0 6 3 5 3 1 0 2 4 1 3 7 915 5 0 1 1 2 6 2 4 0 9 3 3 3 0 0 7 3 7 3 3 0 3 4 4 3 9 0 2 4 5 4 0 965 4 0 1 2 2 9 2 6 1 0 3 6 3 2 0 8 4 0 3 6 0 5 4 7 4 2 0 4 5 0 4 4 980 3 5 1 3 3 0 2 7 1 1 3 7 3 3 0 9 4 1 3 7 0 6 4 8 4 3 0 5 5 1 4 6 1040 2 0 1 5 3 2 2 9 1 3 3 9 3 5 1 1 4 5 4 0 0 9 5 3 4...

Page 11: ...T AND STANDARD DRIVE 870 6 0 0 4 2 1 1 8 0 1 2 3 2 0 900 5 0 0 8 3 2 2 7 0 5 3 5 2 9 0 2 3 8 3 2 930 4 0 1 1 4 1 3 4 0 9 4 5 3 8 0 6 4 9 4 1 0 1 5 1 4 3 950 3 5 1 3 4 6 3 9 1 1 5 1 4 3 0 8 5 5 4 6 0 4 5 9 5 0 980 2 5 1 6 5 3 4 5 1 4 5 8 4 9 1 2 6 3 5 3 0 7 6 9 5 8 0 2 7 3 6 1 1015 1 5 1 9 5 9 5 0 1 7 6 5 5 5 1 5 7 0 5 9 1 0 7 7 6 5 0 6 8 2 6 9 1025 1 0 2 0 6 1 5 1 1 8 6 6 5 6 1 6 7 3 6 1 1 1 7 9 6...

Page 12: ...75 11 4 1 3 16 BX83 84 8 1 High Speed Access 950 1120 BK110 10 75 10 4 1 3 16 BX81 81 8 1 1 All motors have a nominal speed of 1800 RPM a 1 15 service factor and a solid base They can operate to the limit of their service factor because they are located in the moving air upstream of any heating device 2 Do NOT close this pulley below 1 turn open TABLE 9 BLOWER MOTOR AND DRIVE DATA EXTERNAL STATIC ...

Page 13: ... 0 40 6 54 1 1 2 2 2 37 5 75 1 112 6 150 1 77 0 11 8 158 7 168 1 90 125 175 200 3 2 00 00 230 3 60 E018 E036 E054 E072 18 0 36 0 54 0 72 0 1 2 2 2 43 3 86 6 129 9 173 2 77 0 126 3 147 9 191 2 90 150 175 225 4 1 0 000 W180A 460 3 60 E018 E036 E054 E072 18 0 36 0 54 0 72 0 1 2 2 2 21 7 43 3 65 0 86 6 42 9 63 1 74 0 95 6 50 70 90 110 8 6 4 3 X180A 575 3 60 E018 E036 E054 E072 18 0 36 0 54 0 72 0 1 2 ...

Page 14: ...t is set in the ON position ECONOMIZER WITH POWER EXHAUST This system operates as specified above with one addition The power exhaust motor is energized whenever the economizer is chosen by the enthalpy sensor for first stage cooling Y1 As always the R to G connection provides minimum position but does not provide power exhaust operation MOTORIZED OUTDOOR AIR DAMPERS This system operation is the s...

Page 15: ...n the equipment installer To check the supply air CFM after the initial balancing has been completed 1 Remove the two 5 16 inch dot plugs from the blower motor and the filter access panels shown in Figure 9 2 Insert at least 8 inches of 1 4 inch tubing into each of these holes for sufficient penetration into the air flow on both sides of the indoor coil NOTE The tubes must be inserted and held in ...

Page 16: ...n grease fitting Using a low pressure grease gun pump grease Chevron SRI 2 or equivalent into the bearing cavity until new grease shows at the open port Do not over lubricate Run the motor for ten minutes until excess grease is purged from the cavity Replace the plugs On 20 ton only units are supplied with blower shaft bearings that do not require maintenance but may be relubricated if desired Eve...

Reviews: