035-16626-000-E-0103

18

Unitary Products Group

FIGURE 17 - UNIT DIMENSIONS FEH180

27-5/8

2-3/8

2-3/16

56-3/8

1

2-3/16

31-5/8

62-5/8

FILTER ACCESS PANEL
Filters can be removed
through either side of
the unit.

COIL
SECT.

BLOWER
SECTION

32-3/8

6

7-1/4

16-1/2

7/8

BLOWER MOTOR AND DRIVE ACCESS PANEL
(Always on the wiring connection side of unit)
Located on opposite side ONLY when the blower
section has been rotated 180  from position shown.

1-23/32" KNOCKOUT
Remove only when Electric
Heat Accessory is used.

7/8" KNOCKOUT FOR POWER WIRING
Do not remove this knockout when the unit is equipped with an Electric
Heat Accessory.  Refer to detail of the Heater Accessory for power
wiring access opening.

7/8" KNOCKOUT FOR
CONTROL WIRING

ALTERNATE
2-5/8" KNOCKOUT*

*Refer to INSTALLING REFRIGERANT MAINS in installation instruction
when piping through the opposite side of the unit.

AIR

IN

12-7/8

2-7/8

2-7/8

Ø 1-3/8

ALL DIMENSIONS ARE IN INCHES THEY
ARE SUBJECT TO CHANGE WITHOUT
NOTICE.  CERTIFIED DIMENSIONS WILL
BE PROVIDED UPON REQUEST.

ACCESSORIES

Electric Heaters - Add 14-1/4 inches to unit height when
using 10, 20, 30 or 50 kW heater.
Plenum - Add 27 inches to overall unit height when used.
Base Add 24 inches to overall unit height when used.

5-11/16

8-1/2

9-1/2

4

Ø 2"

Ø 2"

2-1/8

18-7/8

5-1/2

AIR

OUT

5-7/8

19-3/8

21-7/8

60-3/4

TABLE 12: FEH180/240 MINIMUM CLEARANCES

Side with RETURN AIR opening

24”

Side with SUPPLY AIR opening

24”

1

1.

Overall dimensions of the unit will vary if an electric
heater, a supply air plenum or a base is used.

Side with PIPING CONNECTIONS

61”

2

2.

This dimension is required for removal of the coil. Only
26” is required for normal service.

Side with access to both POWER & CONTROL WIRING

-

3

3.

If the coil has to be removed, this dimension is required
to loosen screws that secure the coil to the unit frame.
This dimension will also be required for blower motor
access if the piping connections are made on the oppo-
site side of the unit

Bottom

-

4

4.

Allow enough clearance to trap the condensate drain
line.

Summary of Contents for FEH180

Page 1: ...G Notes are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal injury and or equipment dam age may result if installation procedure is not handled properly INSTALLATION MANUAL CAUTION READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT SAVE THIS MANUAL SPLIT SYSTEM HEAT PUMPS INDOOR UNITS M...

Page 2: ...E FEH180 9 7 RETURN AIR GRILLE FEH240 9 8 BASE ACCESSORY FEH180 10 Fig Pg 9 BASE ACCESSORY FEH240 10 10 SUPPLY AIR PLENUM FEH 180 10 11 SUPPLY AIR PLENUM KNOCKOUTS FEH180 10 12 SUPPLY AIR PLENUM FEH240 10 13 RECOMMENDED DRAIN PIPING 12 14 TYPICAL MOTOR MOUNTING ASSEMBLY 13 15 HOLE LOCATIONS FOR PRESSURE DROP READINGS 13 16 CFM VS PRESSURE DROP 13 17 UNIT DIMENSIONS FEH180 18 18 UNIT DIMENSIONS FEH...

Page 3: ...of the matching outdoor unit refer to PN 035 16192 001 Installer should pay particular attention to the words NOTE CAUTION and WARNING Notes are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert the installer that personal injury and or equipment damage may result if the installation proce dure is not handled properly INS...

Page 4: ...ION These indoor units are not designed for outdoor instal lation They must be located within the building struc ture either inside or outside the conditioned space The units should be located as close to the outdoor units as practical and positioned to minimize bends in the refrigerant piping Units being installed vertically or horizontally can be set directly on a floor or platform or they can b...

Page 5: ...bs Motor Drive 3 HP 90 5 HP 120 Electric Heat 10 KW 63 20 KW 66 126 30 KW 71 129 40 KW 132 50 KW 80 137 Supply Air Plenum 114 150 Return Air Grille 20 15 Base 100 120 1 Refer to Blower Motor and Drive Data table for more information TABLE 2 UNIT APPLICATION DATA APPLICATION LIMITATIONS MIN MAX Voltage Variation 208 230 3 60 1 187 253 Voltage Variation 460 3 60 1 414 506 Ambient Air on Outdoor Coil...

Page 6: ... BLOWER SECTION 5 A D SUSPENSION CHANNEL HANGER RODS FIELD SUPPLIED C B ELECTRIC HEATER ACCESSORY 40 Lb SUPPLY AIR PLENUM ACCESSORY 100 Lb D 58 11 16 55 TABLE 3 FEH180 UNIT SUSPENSION WEIGHTS LBS SUSP N POINT W 3 HP MOTOR W HEATER ACCESS W PLENUM ACCESS W HEATER PLENUM ACCESS A 95 95 85 85 B 120 120 100 100 C 95 115 165 185 D 115 140 185 205 Total Wt 425 470 535 575 ...

Page 7: ... BLOWER SECTION HEATING COIL SUSPENSION CHANNEL 43 3 4 5 A B C D E F 55 HANGER RODS FIELD SUPPLIED ELECTRIC HEAT ACCESS 40lbs each TABLE 4 FEH240 UNIT SUSPENSION WEIGHTS LBS SUSPENSION POINT W 5HP MOTOR1 1 Motor location at suspension point F W HEATER ACCESS A 142 142 B 132 132 C 152 152 D 162 189 E 132 158 F 127 154 Total Weight 847 927 ...

Page 8: ...ule Although the unit is always shipped in the vertical position with a vertical air dis charge as shown in a the blower module can be reposi tioned in the field as shown in illustrations b and c for maxi mum flexibility TheSupply Air Plenum Return Air Grille and Base accessories can be applied on arrangement a TheReturn Air Grille and Base accessories can be applied on arrangement b TheSupply Air...

Page 9: ... wire sizes up through 0 AWG 50 KW Add a 1 1 4 inch conduit fitting to the 1 23 32 inch hole for wire sizes up through 1 AWG Remove the knockout ring and add a two inches conduit fitting to the 2 1 2 hole for wire sizes up through 000 AWG Used on FEH180 only TABLE 5 ELECTRIC HEATER DIMENSIONS FEH180 240 Heater Model1 Nom kW Heater Dimensions inches A B C D E F G H K L M 2HB04501025 46 10 27 1 4 25...

Page 10: ...he transmission of noise and vibration Insulate all ductwork running through the uncondi tioned areas to prevent moisture condensation and to provide more economical operation FIGURE 8 BASE ACCESSORY FEH180 FIGURE 9 BASE ACCESSORY FEH240 FIGURE 10 SUPPLY AIR PLENUM FEH 1801 1 Electric Heaters are NOT UL approved for installation within a SUPPLY AIR PLENUM 24 31 5 8 60 3 4 BASE 1 9 7 8 1 6 1 8 2 1 ...

Page 11: ...e matching outdoor unit for piping limitations line sizes and other design considerations INSTALLING REFRIGERANT MAINS The units are evacuated and dehydrated at the factory and shipped with a holding charge of Refrigerant 22 The vapor and liquid connections are sealed with cop per discs If the unit has already lost its holding charge it should be leak tested and the necessary repairs should be mad...

Page 12: ...llar the locking collar must be loosened to adjust the setting of the movable flange Note the following 1 The supply air CFM must be within the limitations shown in Tables 7 and 8 2 All pulleys can be adjusted in half turn increments 3 The tension on the belt should be adjusted for a deflection of 3 16 per foot of belt span with an applied force of 2 to 3 pounds This adjustment is made by moving t...

Page 13: ...g run 4 Knowing the pressure drop across a dry coil the actual CFM through the unit can be determined from the curve in Figure 16 If the CFM is above or below the specified value the supply air motor pulley may have to be re adjusted After one hour of operation check the belt and pulleys for tightness and alignment After readings have been obtained remove the tubes and seal up the drilled holes in...

Page 14: ...ntal configuration 2 Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit Refer to the respective tables for the resistance of these accessories and for additional motor and drive data 3 Motors can be selected to operate into their service factor because they are located in the moving airstream upstream of any heating device 4 kW is b...

Page 15: ...0 0 150 0 AWG 895 150 230 3 60 115 2 153 2 175 2 0 AWG 1073 150 460 3 60 57 6 76 6 80 4 AWG 1347 100 F1EH240A 5 20 KW 208 3 60 41 6 68 0 70 4 AWG 186 100 230 3 60 46 2 70 6 80 4 AWG 251 100 460 3 60 23 1 35 3 40 8 AWG 381 60 30 KW 208 3 60 62 5 94 1 100 3 AWG 233 100 230 3 60 69 3 99 4 100 3 AWG 315 100 460 3 60 34 6 49 7 50 8 AWG 381 60 40 KW 208 3 60 83 3 120 1 125 1 AWG 371 150 230 3 60 92 1 12...

Page 16: ...2 153 2 175 2 0 AWG 1073 150 460 3 60 57 6 76 6 80 4 AWG 1347 100 F1EH240A 5 20 KW 208 3 60 41 6 68 0 70 4 AWG 186 100 230 3 60 46 2 70 6 80 4 AWG 251 100 460 3 60 23 1 35 3 40 8 AWG 381 60 30 KW 208 3 60 62 5 94 1 100 3 AWG 233 100 230 3 60 69 3 99 4 100 3 AWG 315 100 460 3 60 34 6 49 7 50 8 AWG 381 60 40 KW 208 3 60 83 3 120 1 125 1 AWG 371 150 230 3 60 92 1 127 9 150 1 AWG 501 150 460 3 60 46 1...

Page 17: ...er motor are permanently lubricated and should not require any additional lubricant BELTS Maintain belt tension to extend belt life Replace the signs of failure begin to appear TABLE 11 TYPICAL FIELD WIRING Y1 W1 Y2 C R X O HC O HR G W1 Y2 Y1 R C X R C Y1 Y2 O W1 X G TB1 TB2 TERMINALS ON Supply Air Blower Motor Contactor 10M OR Terminal Block Electric Heat Control Box GROUND SCREW Heat Pump Only U...

Page 18: ...IMENSIONS ARE IN INCHES THEY ARE SUBJECT TO CHANGE WITHOUT NOTICE CERTIFIED DIMENSIONS WILL BE PROVIDED UPON REQUEST ACCESSORIES Electric Heaters Add 14 1 4 inches to unit height when using 10 20 30 or 50 kW heater Plenum Add 27 inches to overall unit height when used Base Add 24 inches to overall unit height when used 5 11 16 8 1 2 9 1 2 4 Ø 2 Ø 2 2 1 8 18 7 8 5 1 2 AIR OUT 5 7 8 19 3 8 21 7 8 60...

Page 19: ...035 16626 000 E 0103 Unitary Products Group 19 Clearances for FEH240 24 on one side for piping connection and access to blower motor 1 on opposite sides and rear FIGURE 18 UNIT DIMENSIONS FEH240 ...

Page 20: ...to change without notice Printed in U S A 035 16626 000 E 0103 Copyright by Unitary Products Group 2003 All rights reserved Supersedes 035 16626 000 D 0502 Unitary 5005 Norman Products York OK Group Drive 73069 ...