background image

035-17438-001 Rev. A (901)

22

Unitary Products Group

Cleaning the Heat Exchanger

Lower Heat Exchanger Access

1.

Turn off the electrical power to the unit and turn off gas 
supply at the shutoff valve.

2.

Remove the blower and burner compartment access 
doors. Disconnect the gas supply piping at the union to 
permit removal of the entire burner and gas control 
assembly from the vestibule panel. Use the wrench boss 
on the gas valve when removing or installing this piping.

3.

Unplug the ignitor from the wire harness. Disconnect 
sensor and rollout switch wires located on top of the air 
shield. Identify and note the location of all leads for ease 
of reinstallation. Also disconnect the wires at the side 
rollout switches (upflow only) and the gas valve wires.

4.

Remove the screws holding the burner assembly to the 
vestibule panel and remove this assembly. Handle the 
assembly carefully since it contains the ignitor which is 
fragile and easily broken. The lower portion of the heat 
exchanger will now be exposed. To clean the burner 
assembly, use a vacuum cleaner, or remove the burners 
as outlined in burner cleaning, and clean in hot water.

Upper Heat Exchanger Access

1.

Perform steps 1 thru 4 above.

2.

Disconnect vent piping from the vent motor assembly at 
the top panel on the furnace (upflow only). On downflow 
installations this is not necessary.

3.

Unplug the ventor motor wires and ground wire. Remove 
the pressure switch tubing at the tap on the ventor motor 
housing.

NOTE:  

It is recommended that replacement gaskets be

available before removing ventor motor.

4.

Remove six mounting screws that hold the ventor motor 
to the restrictor plate. The surface is gasketed and gas-
ket can be reused if it is carefully removed. It is neces-
sary to remove this assembly to gain access to the 
restrictor plate mounting holes. The ventor assembly 
may be vacuumed if cleaning is necessary. If any vent 
assembly parts are damaged, replace with an entire new 
assembly (except for gaskets).

5.

Remove the perimeter screws attaching the restrictor 
plate assembly to the vestibule panel. The surface is 
also gasketed. The assembly, including the flue baffle 
plate (rear) may be vacuumed or cleaned with hot water 
if necessary.

6.

The upper portion of the heat exchanger is now accessi-
ble. With a long flexible wire brush, clean inside each 
tube at both the top and bottom. The brush must pass 
around the rear heat exchanger tubes. Vacuum loose 
scale and dirt from each tube.

7.

Replace all components in reverse order. Regasket all 
surfaces which required a gasket. Reconnect all wiring. 
Reattach vent pipe and gas supply lines before restoring 
service to furnace. Restore electrical power, check gas 
supply piping for leaks, then verify furnace operation.

TROUBLESHOOTING

The following visual checks should be made before trouble-
shooting:

1.

Check to see that the power to the furnace and the igni-
tion control module is ON.

2.

The manual shutoff valves in the gas line to the furnace 
must be open.

3.

Make sure all wiring connections are secure.

4.

Review the sequence of operation.

Start the system by setting the thermostat above the room
temperature. Observe the system's response. Then use the
troubleshooting section in this manual to check the system's
operation.

TROUBLESHOOTING THE BLOWER ASSEMBLY

Check to see that there is power to the furnace and the igni-
tion circuit module by turning the furnace power OFF for 5
seconds then ON. the red ignition control LED should light for
an instant then go out.

NO AIRFLOW OR MOTOR DOESN’T RUN

Verify that the blower wheel is properly tightened on the 
motor shaft.

Verify 115 Volts AC at the power connector at the motor.

Be sure the connectors at the motor, ignition control and 
CFM Selection Board are properly connected and fully 
seated.

Switch the thermostat to CONTINUOUS FAN mode. If 
the motor does not run, verify 24 VAC on the R to C 
lines. If there is no voltage correct the cable/wiring, trans-
former fault. If there is voltage at the connector, the 
motor has failed.

Check High Heat, Low Heat or Cool output terminals for 
24 volts.

Check motor for tight shaft.

Perform Moisture Check. Be sure motor connectors are 
facing down. Arrange the wire harness to create a drip 
loop under the motor. Check for plugged condensate 
drain. Check for low airflow. Check and plug leaks in 
return ducts.

MOTOR ROCKS BUT WON’T START

Check for loose or compliant motor mount.

Perform motor/control replacement check.

Summary of Contents for G8V08012UHA11

Page 1: ...035 17438 001 Rev A 901 EFFICIENCY RATING CERTIFIED CAUTION READ ALL SAFETY GUIDES BEFORE YOU START TO INSTALL YOUR FURNACE SAVE THIS MANUAL TABLE OF CONTENTS GENERAL INFORMATION 2 UNIT INSTALLATION 3...

Page 2: ...PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE REFER TO THIS MANUAL FOR ASSISTANCE OR AD...

Page 3: ...ptable heat loss calculation for the structure ACCA Manual J or other approved methods may be used The furnace should be located using these guidelines 1 Where a minimum amount of vent piping and elbo...

Page 4: ...the total input rating of all equipment located in the enclosure b Not less than the sum of the areas of all vent con nectors in the confined space 3 Louvers Grilles and Screens a In calculating free...

Page 5: ...nds in a general vertical direction and does not con tain offsets exceeding 45 degrees except that a vent system having not more than one 60 degree offset is permitted NOTE This appliance may be commo...

Page 6: ...nce being operated in operation Adjust thermostat so appli ance will operate continuously 5 Test for draft hood equipped appliance spillage at the draft hood relief opening after 5 minutes of main bur...

Page 7: ...V UH INPUT MBH H L OUTPUT MBH H L NOM CFM CABINET WIDTH IN AFUE1 LOW FIRE TEMP RISE F HIGH FIRE TEMP RISE MAX OUTLE AIR TEMP F BLOWER TOTAL UNIT AMPS MAX OVER CURRENT PROPECT2 MIN WIRE SIZE AWG 75 FT...

Page 8: ...removable access panel is recommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indi cate the presence of leaks in the heat exchanger This access...

Page 9: ...and notes on blower perfor mance tables in this manual Where the return duct system is not complete the return con nection must run full size to a location outside the utility room or basement For fur...

Page 10: ...s is recommended Refer to Fig ure 6 on page 10 NOTE See crawl space installation for suspending the fur nace in attic installations CRAWL SPACE INSTALLATION The furnace can be hung from floor hoists o...

Page 11: ...cordance with instructions Specific electrical data is given on the furnace rating plate Provide a power supply separate from all other circuits Install overcurrent protection and disconnect switch pe...

Page 12: ...OFF position and the main electrical source disconnected complete the low voltage wiring from the ther mostat to the terminal board on the CFM programmable board Connect Class 2 control wiring see Fig...

Page 13: ...nt 1 Blockage of internal flue gas passage ways 2 Blockage of vent piping 3 Failure of combustion air blower motor Limit Control The high temperature limit control is located on the furnace vestibule...

Page 14: ...increment find the cubic feet of gas consumed per hour from Table 4 on page 15 NOTE To find the Btuh input multiply the number of cubic feet of gas consumed per hour by the BTU content of the gas in y...

Page 15: ...cement The temperature rise or temperature difference between the return air and the heated air from the furnace must be within the range shown on the furnace rating plate Application limi tations are...

Page 16: ...uction for the recommended airflow and Table 6 on page 17 The DELAY Tap should be set in the B position for a two stage condenser This results in a 45 second off delay at 82 of the programmed cooling...

Page 17: ...002UHC11 L8V1002UHC11 P DUC20V09601 G8V12020UHC11 L8V12020UHC11 COOL TAP ADJ TAP High Low High Low High Low High Low 1340 740 1675 920 2050 1135 2020 1130 A B 1155 635 1555 850 1860 980 1855 960 B B 1...

Page 18: ...is fixed at 60 seconds for SEER enhance ment HEATING OPERATIONAL SEQUENCE Two Stage Thermostat The ignition control in this furnace is unique to this product The control allows for a 24 volt or a 115...

Page 19: ...gas valve When power is restored the gas valve will remain deener gized and a restart of the ignition sequence will begin imme diately A momentary loss of gas supply flame blowout or a shorted or open...

Page 20: ...LOW INDUCER LOW STAGE PRESSURE SWITCH HSI 1ST STAGE MAIN VALVE FLAME SENSE LOW CIRCULATOR HEAT SPEED 1ST STAGE LOW PRESSURE SWITCH CLOSE RECOGNITION HSI WARM UP 17 SEC IGNITION ACTIVATION PERIOD 4 SE...

Page 21: ...bly for cleaning is as follows 1 Disconnect the power supplied to the furnace 2 Remove the vest and blower panels 3 Disconnect the motor control harness and the power har ness from the motor 4 Remove...

Page 22: ...including the flue baffle plate rear may be vacuumed or cleaned with hot water if necessary 6 The upper portion of the heat exchanger is now accessi ble With a long flexible wire brush clean inside ea...

Page 23: ...R REMOVAL FOR CONTROLLER REPLACEMENT Refer to BLOWER CARE on page 21 of this manual for blower removal instructions Rest the blower on its side so the end of the motor is accessible and facing up Wait...

Page 24: ...ehind a clear view port in the blower compartment door DO NOT remove the furnace blower compartment panel OR turn off furnace power as either action will clear the control s memory of the fault The co...

Page 25: ...y low gas pressure faulty gas valve faulty hot surface ignitor reversed line polarity or burner problem 8 FLASH This fault is indicated if the flame is lost 5 times during the heating cycle This could...

Page 26: ...NTROL BOARD P3 S3 2 PIN PLUG SOCKET AT HOT SURFACE IGNITOR P4 S4 3 PIN PLUG SOCKET AT INDUCER MOTOR P5 S5 3 PIN PLUG SOCKET ON VALVE P6 S6 6 PIN PLUG SOCKET ON CFM TIMER BOARD P7 S7 16 PIN PLUG SOCKET...

Page 27: ...035 17438 001 Rev A 901 Unitary Products Group 27 SERVICE RECORDS...

Page 28: ...hange without notice Printed in U S A 035 17438 001 Rev A 901 Copyright by York International Corp 2001 All rights reserved Supersedes 035 17438 001 Rev A 801 Unitary 5005 Norman Product York OK Group...

Reviews: