background image

270846-UTG-A-0407

Unitary Products Group

3

Nominal external static pressure is 0.50” w.c. at furnace outlet ahead of cooling coils.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.

RATINGS & PHYSICAL / ELECTRICAL DATA - UPFLOW MODELS

Models

Input

Output

Nominal Airflow Cabinet Width

Total

Unit

AFUE

Air Temp. 

Rise

MBH

MBH

CFM

In.

Amps

°F

GF8050B12MU11

50

40

1200

17-1/2

8.0

80.0

30-60

GF8075B12MU11

75

60

1200

17-1/2

8.0

80.0

35-65

GF8075C16MU11

75

60

1600

21

11.4

80.0

30-60

GF8100C16MU11

100

80

1600

21

11.4

80.0

40-70

GF8100D20MU11

100

80

2000

24 1/2

11.3

80.0

35-65

GF8125D20MU11

125

100

2000

24 1/2

11.3

80.0

40-70

GF8150D20UH11

150

120

2000

24 1/2

11.3

80.0

40-70

Models

Input

Max. Outlet

Air Temp

Blower

Blower

Size

Max 

Over-current

protect

Min.Wire Size 
(awg) @ 75 ft.

one way

Operation

Wt.

MBH

°F

Hp

Amps

In.

LBS

GF8050B12MU11

50

160

1/2

7.0

10 x 8

15

14

112

GF8075B12MU11

75

165

1/2

7.0

10 x 8

15

14

118

GF8075C16MU11

75

160

1/2

10.4

10 x 10

15

14

129

GF8100C16MU11

100

170

1/2

10.4

10 x 10

15

14

135

GF8100D20MU11

100

165

1

10.3

(2)10 x 6

15

14

149

GF8125D20MU11

125

170

1

10.3

(2)10 x 6

15

14

155

GF8150D20UH11

150

170

1

10.3

(2)10 x 6

15

14

165

Summary of Contents for GF8 SERIES

Page 1: ...20 year limited warranty on the heat exchanger 5 year limited parts warranty FEATURES 4 position MU upflow models allow horizontal left hori zontal right downflow and convertible applications 4 posit...

Page 2: ...8 19 0 42 GF8100C16MU111 1600 C 21 20 20 3 8 20 0 19 1 2 18 1 4 18 3 4 18 5 8 19 0 42 GF8100D20MU111 2000 D 24 5 23 1 2 20 3 8 20 0 23 21 3 4 18 3 4 22 1 8 19 0 42 GF8125D20MU111 2000 D 24 5 23 1 2 20...

Page 3: ...075B12MU11 75 60 1200 17 1 2 8 0 80 0 35 65 GF8075C16MU11 75 60 1600 21 11 4 80 0 30 60 GF8100C16MU11 100 80 1600 21 11 4 80 0 40 70 GF8100D20MU11 100 80 2000 24 1 2 11 3 80 0 35 65 GF8125D20MU11 125...

Page 4: ...2MU111 B High 1507 1433 1371 1300 1223 1132 1040 938 Med 1239 1215 1175 1144 1085 1012 938 838 Low 907 907 891 875 849 800 741 672 GF8075B12MU111 B High 1634 1562 1484 1417 1340 1238 1154 1030 Med 124...

Page 5: ...190 1175 1126 1041 937 GF8100C16MU111 C High 1997 1920 1822 1723 1620 1500 1355 1211 Med 1728 1679 1635 1556 1465 1359 1249 1117 Low 1131 1156 1181 1190 1171 1126 1049 926 GF8100D20MU112 D High 2327 2...

Page 6: ...24 GF8150D20UH11 150 2000 D 2 25 x 16 24 x 24 DOWNFLOW Models Input Air Flow Cabinet Size Top Return Downflow Cleanable Air Filters Top Return Downflow Disposable Air Filters MBH CFM in in GF8050B12MU...

Page 7: ...ow 0 30 w c to obtain actual airflow 0 38 in w c ESP 1408 52 1356 1 Special floor base or air conditioning coil required for use on combustible floor 2 Line contact only permitted between lines formed...

Page 8: ...change without notice Printed in U S A 270846 UTG A 0407 Copyright by York International Corp 2007 All rights reserved Supersedes 265923 BTG C 0806 Unitary 5005 Norman Products York OK Group Drive 73...