background image

272317-UIM-A-0407

Unitary Products Group

7

NOTES: 

1. Air velocity through throwaway type filters may not exceed 300 feet per minute. All velocities over this require the use of high velocity filters.
2. Air flows above 1800 CFM require either return from two sides or one side plus bottom.

SIDE RETURN - FILTER INSTALLATION

Locate and mark the side return opening. Refer to Figure 1 for dimen-
sions of the cutout.

Install the side filter rack following the instructions provided with that
accessory. If a filter(s) is provided at another location in the return air
system, the ductwork may be directly attached to the furnace side
panel.If not provided with the furnace, an accessory filter rack is avail-
able for mounting the filter external to the cabinet.

IMPORTANT: 

Some accessories such as electronic air cleaners and

pleated media may require a larger side opening. Follow the instruc-
tions supplied with that accessory for side opening requirements. Do
not cut the opening larger than the dimensions shown in Figure 1.

SECTION IV: GAS PIPING

GAS SAFETY

IMPORTANT: 

Plan your gas supply before determining the correct gas

pipe entry. Use 90-degree service elbow(s), or short nipples and con-
ventional 90-degree elbow(s) to enter through the cabinet access holes.

GAS PIPING INSTALLATION

Properly sized wrought iron, approved flexible or steel pipe must be
used when making gas connections to the unit. If local codes allow the
use of a flexible gas appliance connection, always use a new listed con-
nector. Do not use a connector that has previously serviced another gas
appliance.

Some utility companies or local codes require pipe sizes larger than the
minimum sizes listed in these instructions and in the codes. The furnace
rating plate and the instructions in this section specify the type of gas
approved for this furnace - only use those approved gases. The instal-
lation of a drip leg and ground union is required. Refer to Figure 3.

IMPORTANT: 

An accessible manual shutoff valve must be installed

upstream of the furnace gas controls and within 6 feet (1.8 m) of the fur-
nace.

The furnace must be isolated from the gas supply piping system by
closing its individual external manual shutoff valve during any pressure
testing of the gas supply piping system at pressures equal to or greater
than 1/2 psig (3.5 kPa).

Gas piping may be connected from either side of the furnace using any
of the gas pipe entry knockouts on both sides of the furnace. Refer to
Figure 1 dimensions.

The inlet to the gas valve lines up directly with the opening in the left
side of the furnace casing. To line up with the opening in the right side
of the casing, two street ells should be used.

TABLE 4: 

Recommended Filter Sizes

Input

BTU/H (kW)

CFM 

(m

3

/min)

Cabinet 

Size

Side Return 

Filter in. (cm)

Bottom Return 

Filter in. (cm)

40 (11.7)

1200 (34.0)

A

16 x 25 (41 x 64)

14 x 25 (36 x 64)

60 (17.8)

1200 (34.0)

B

16 x 25 (41 x 64)

16 x 25 (41 x 64)

80 (23.4)

1200 (34.0)

B

16 x 25 (41 x 64)

16 x 25 (41 x 64)

80 (23.4)

1600 (45.3)

C

16 x 25 (41 x 64)

20 x 25 (51 x 64)

100 (29.3)

1600 (45.3)

C

16 x 25 (41 x 64)

20 x 25 (51 x 64)

100 (29.3)

2000 (56.6)

C

16 x 25 (41 x 64)

20 x 25 (51 x 64)

120 (35.1)

2000 (56.6)

D

(2) 16 x 25 (2) (41 x 64)

22 x 25 (56 x 64)

All installations must have a filter installed.

An overpressure protection device, such as a pressure regulator,
must be installed in the gas piping system upstream of the furnace
and must act to limit the downstream pressure to the gas valve so it
does not exceed 0.5 PSI {14" w.c. (3.48 kPa)}. Pressures exceed-
ing 0.5 PSI {14” w.c. (3.48 kPa)} at the gas valve will cause damage
to the gas valve, resulting in a fire or explosion or cause damage to
the furnace or some of its components that will result in property
damage and loss of life.

 FIGURE 2:  

Gas Valve

INLET

WRENCH
BOSS

INLET
PRESSURE
PORT

ON OFF
SWITCH

LOW STAGE REGULATOR
ADJUSTMENT

OUTLET

OUTLET
PRESSURE
PORT

VENT
PORT

HIGH STAGE REGULATOR
ADJUSTMENT

 FIGURE 3:  

Gas Piping

Never apply a pipe wrench to the body of the gas valve when
installing piping. A wrench must be placed on the octagonal hub
located on the gas inlet side of the valve. Placing a wrench to the
body of the gas valve will damage the valve causing improper oper-
ation and/or the valve to leak.

EXTERNAL MANUAL
SHUTOFF VALVE

TO GAS
SUPPLY

TO GAS
SUPPLY

GROUNDED JOINT UNION
MAY BE INSTALLED
INSIDE OR OUTSIDE UNIT.

DRIP
LEG

Summary of Contents for GM9T-UP

Page 1: ...NG 7 ELECTRICAL POWER 8 COMBUSTION AIR AND VENT SYSTEM 13 CONDENSATE PIPING 20 SAFETY CONTROLS 21 START UP AND ADJUSTMENTS 21 WIRING DIAGRAM 29 LIST OF FIGURES Dimensions 6 Gas Valve 7 Gas Piping 7 El...

Page 2: ...ible materials as listed under Clearances to Combustibles in Table 1 Provide clearances for servicing ensuring that service access is allowed for both the burners and blower These models ARE NOT CSA l...

Page 3: ...or and the furnace must be located or protected to avoid physical damage by vehicles The furnace area must not be used as a broom closet or for any other storage purposes as a fire hazard may be creat...

Page 4: ...TE When attaching duct flange do not shoot the screw down into the casing Use the formed flange intended for duct flange attachment The duct system is a very important part of the installation If the...

Page 5: ...er This access cover shall be attached in such a manner as to prevent leaks TABLE 2 Minimum Duct Sizing For Proper Airflow Input Airflow Return1 Rectangular2 Round2 Supply3 Rectangular2 Round2 BTU H k...

Page 6: ...combustibles and have floor support with required service accessibility IMPORTANT If an external mounted filter rack is being used see the instructions provided with that accessory for proper hole cu...

Page 7: ...m of the fur nace The furnace must be isolated from the gas supply piping system by closing its individual external manual shutoff valve during any pressure testing of the gas supply piping system at...

Page 8: ...67 1100 3 2 2 7 2 4 41 0 0 80 0 66 0 61 2500 LP 9 8 8 2 7 5 93 2 LP 2 44 2 03 1 86 TABLE 6 Nominal Manifold Pressure Low Fire First Stage Manifold Pressures in wc First Stage Manifold Pressures kpa A...

Page 9: ...wiring connections on the thermostat to the terminal board on the ignition module as shown in Figures 5 6 Electronic thermostats may require the common wire to be connected as shown in Figures 5 6 Ap...

Page 10: ...unction Light E W1 First Stage Heat G Fan G Fan Connection of the C Termainal 24 Volt Common is optional when used with batteries Thermostat Installer Setup Number 1 System Type must be set to 6 2 Hea...

Page 11: ...SG Bonnet Sensor Bonnet Sensor Optional BS Bonnet Sensor W2 Second Stage Auxiliary Heat W2 Second Stage Auxiliary Heat AUX Auxiliary Heat E W1 First Stage Auxiliary Heat E W1 First Stage Auxiliary Hea...

Page 12: ...gas supplies must be provided as specified with these instruc tions Since the furnaces are side by side with no space between gas supplies must enter on the right and left respectively All gas piping...

Page 13: ...e with Section 5 3 Air for Combustion and Ventilation of the National Fuel Gas Code Z223 1 NFPA 54 latest edition or Sections 7 2 7 3 or 7 4 of CSA B149 1 National Gas and Propane Codes latest edition...

Page 14: ...or horizontal models the transition from 2 to 3 pipe should be done immediately after the drain tee or drain elbow 7 In Canada vents shall be certified to ULC S636 Standard for Type BH Gas Venting Sys...

Page 15: ...the following systems A Sealed combustion air systems from the furnace to the out side termination B Ventilated combustion air systems from the furnace to the attic or crawl space termination 6 Disas...

Page 16: ...ons 9 inches 23 cm for models 50 000 BTUH 15 kW 12 inches 30 cm for models 50 000 BTUH 15 kW C Clearance to permanently closed window 12 inches 30 cm 12 inches 30 cm D Vertical clearance to ventilated...

Page 17: ...r systems must be installed so the vent and the combustion air pipes terminate in the same atmospheric zone Refer to Figures 14 or 15 VENTING MULTIPLE UNITS Multiple units can be installed in a space...

Page 18: ...e The combustion air intake pipe should be located either through the wall horizontal or side vent or through the roof vertical vent Care should be taken to locate side vented systems where trees or s...

Page 19: ...cm2 60 000 60 387 cm2 80 000 80 516 cm2 100 000 100 645 cm2 120 000 120 774 cm2 FIGURE 20 Outside and Ambient Combustion Air GABLE VENT GAS VENT SOFFIT VENT VENTILATED ATTIC TOP ABOVE INSULATION OPTIO...

Page 20: ...Air The ventilated attic space or a crawl space from which the combustion air is taken must comply with the requirements specified in AIR SOURCE FROM OUTDOORS in this instruction or in Section 5 3 Air...

Page 21: ...e controls are mounted on the burner box assembly If the temper ature in the burner box exceeds its set point the ignition control and the gas valve are de energized The operation of this control indi...

Page 22: ...ll start and come up to speed Shortly after inducer start up the hot surface igniter will glow for about 17 seconds b After this warm up the ignition module will energize open the main gas valve c Aft...

Page 23: ...3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 15 times 0 10 m3 of gas measured at the...

Page 24: ...shown in Figure 24 The procedure below is used to adjust either the high fire manifold pressure or the low fire manifold pressure IMPORTANT The cap for the pressure regulator must be removed entirely...

Page 25: ...The furnace control board also allows user selection of the blower speed that is energized during continuous fan operation Place jumper on the HI COOL LO COOL or HEAT pins WITH BURNER BOX COVER IN PL...

Page 26: ...out Low gas pressure faulty gas valve faulty hot surface ignitor or burner problem may cause this The furnace will lock out for one hour and then restart 8 RED FLASHES This fault is indicated if the...

Page 27: ...35 33 31 30 28 25 25 22 100 1600 C 80 1600 C High 1960 1955 1925 1890 1830 1765 1695 1615 1600 1485 56 55 55 54 52 50 48 46 45 42 Med High 1565 1560 1560 1575 1545 1530 1475 1425 1365 1260 44 44 44 4...

Page 28: ...50 w c 125 Pa from the airflow 0 60 w c 150 Pa to obtain airflow difference 2175 2285 110 CFM 3 11 m3 min Subtract the total system static from 0 50 w c 125 Pa and divide this difference by the differ...

Page 29: ...272317 UIM A 0407 Unitary Products Group 29 SECTION X WIRING DIAGRAM FIGURE 27 Wiring Diagram...

Page 30: ...272317 UIM A 0407 30 Unitary Products Group NOTES...

Page 31: ...272317 UIM A 0407 Unitary Products Group 31 NOTES...

Page 32: ...t to change without notice Printed in U S A 272317 UIM A 0407 Copyright by York International Corp 2007 All rights reserved Supersedes 167488 UIM B 0806 Unitary 5005 Norman Product York OK Group Drive...

Reviews: