background image

268894-UIM-A-0407

Unitary Products Group

5

Table 2 is a guide for determining whether the rectangular duct system
that the furnace is being connected to be of sufficient size for proper fur-
nace operation.

Use the Example below to help you in calculating the duct area to deter-
mine whether the ducts have sufficient area so that the furnace oper-
ates at the specified external static pressure and within the air
temperature rise specified on the nameplate.

The following are general duct sizing guidelines that may not serve to
requirements of every application.

Example: The furnace input is 80,000 BTUH with 1,200 CFM blower
requirement. The recommended duct area is 216 sq. in, there are two 8
x 12 rectangular ducts attached to the plenum and there are two 7 inch
round ducts attached to the furnace.

1.

Take 8 x 12, which equals 96 sq. in. X 2, which equals 192 square
inches then go to round duct size located in Table 3.

2.

The square inch area for 7 inch round ducts is 38.4 sq. in. x 2 =
76.8 square inches.

3.

Then take the 192 square inch from the rectangular duct and add it
to the 76.8 sq. in. of round duct. The total square inch of duct
attached to the furnace supply plenum is 268.8 total square
inches. This exceeds the recommended 216 square inch of duct.

In this example, the duct system attached to the plenum has a sufficient
area so that the furnace operates at the specified external static pres-
sure and within the air temperature rise specified on the nameplate,
providing the return duct is properly sized as well.

1.

The Air Temperature Rise is determined by subtracting the Return
Air Temperature Reading from the Supply Air Temperature Read-
ing.

2.

The External Static Pressure is determined by adding the Supply
Duct Static Pressure reading to the Return Duct Static Pressure
reading and adding the pressure drop across any applied a-coil
and return air filter.

Tables 2 and 3 are to be used as a guide only to help the installer deter-
mine if the duct sizes are large enough to obtain the proper air flow
(CFM) through the furnace. Tables 2 and 3 ARE NOT to be used to
design ductwork for the building where the furnace is being installed.
There are several variables associated with proper duct sizing that are
not included in the tables. To properly design the ductwork for the build-
ing, refer to the ASHRAE Fundamentals Handbook, chapter on “DUCT
DESIGN” or a company that specializes in Residential and Modular

Home duct designs.

IMPORTANT: 

If the supply air duct is being connected to the furnace

without the use of an accessory duct connector, then a transition duct
must be installed with flanges or tabs that are securely attached and
sealed to the supply air duct and to the base of the furnace. The transi-
tion duct must have insulation between the transition duct and any com-
bustible material.

The transition duct must be the same dimensional size as the rectangu-
lar opening in the base of the furnace.

TABLE 2: 

Minimum Duct Sizing For Proper Airflow

Input/Cabinet

Airflow

Return

1

Rectangular

2

Round

2

Supply

3

Rectangular

2

Round

2

BTU/H (kW)

CFM (m³)

In² (cm²)

in. x in. (cm x cm)

in. (cm) dia.

In² (cm²)

in. x in. (cm x cm)

in. (cm) dia.

40/A (11.7)

1200 (34.0)

280 (1806)

14 x 20 (35.6 x 50.8)

18 (45.7)

216 (1394)

12 x 18 (30.5 x 45.7)

16 (40.6)

60/A (17.6)

1200 (34.0)

280 (1806)

14 x 20 (35.6 x 50.8)

18 (45.7)

216 (1394)

12 x 18 (30.5 x 45.7)

16 (40.6)

80/A (23.4)

1200 (34.0)

280 (1806)

14 x 20 (35.6 x 50.8)

18 (45.7)

216 (1394)

12 x 18 (30.5 x 45.7)

16 (40.6)

80/B (23.4)

1600 (45.3)

360 (2322)

18 x 20 (45.7 x 50.8)

22 (55.8)

280 (1806)

14 x 20 (35.6 x 50.8)

18 (45.7)

80/C (23.4)

1600 (45.3)

360 (2322)

18 x 20 (45.7 x 50.8)

22 (55.8)

280 (1806)

14 x 20 (35.6 x 50.8)

18 (45.7)

100/B (29.3)

1200 (34.0)

280 (1806)

14 x 20 (35.6 x 50.8)

18 (45.7)

216 (1394)

12 x 18 (30.5 x 45.7)

16 (40.6)

100/C (29.3)

1600 (45.3)

360 (2322)

18 x 20 (45.7 x 50.8)

22 (55.8)

280 (1806)

14 x 20 (35.6 x 50.8)

18 (45.7)

100/C (29.3)

2000 (56.6)

440 (2834)

20 x 22 (50.8 x 55.8)

24 (60.9)

390 (2516)

16 x 22 (40.6 x 55.8)

22 (55.8)

115/C (33.7)

1600 (45.3)

360 (2322)

18 x 20 (45.7 x 50.8)

22 (55.8)

280 (1806)

14 x 20 (35.6 x 50.8)

18 (45.7)

115/C (33.7)

2000 (56.6)

440 (2834)

20 x 22 (50.8 x 55.8)

24 (60.9)

390 (2516)

16 x 22 (40.6 x 55.8)

22 (55.8)

130/D (38.1)

2000 (56.6)

440 (2834)

20 x 22 (50.8 x 55.8)

24 (60.9)

390 (2516)

16 x 22 (40.6 x 55.8)

22 (55.8)

NOTE: This chart does not replace proper duct sizing calculations or take into account static pressure drop for run length and fittings. Watch out for the temperature rise and static pressures.

1.

Maximum return air velocity in rigid duct @ 700 

feet per minute (213 m/min).

2.

Example return main trunk duct minimum dimensions.

3.

Maximum supply air velocity in rigid duct @ 900 

feet per minute (274 m/min).

TABLE 3: 

Round Duct Size

Round Duct Size

Calculated Area For Each Round Duct Size

inches (cm)

Sq.in (cm

2

)

5 (13)

19.6 (126)

6 (15)

28.2 (182)

7 (18)

38.4 (248)

8 (20)

50.2 (324)

9 (23)

63.6 (410)

10 (25)

78.5 (506)

11 (28)

95 (613)

12 (30)

113.1 (730)

13 (33)

132.7 (856)

14 (36)

153.9 (993)

 FIGURE 1:  

Combustible Floor Base Accessory

DOWNFLOW
FURNACE

WARM AIR PLENUM
WITH 1” FLANGES

FIBERGLASS
INSULATION

FIBERGLASS TAPE
UNDER FLANGE

COMBUSTIBLE FLOOR
BASE ACCESSORY

Summary of Contents for GY8S*DH

Page 1: ...OF SECTIONS SAFETY 1 DUCTWORK 4 FILTERS 8 GAS PIPING 8 ELECTRICAL POWER 9 TWINNING AND STAGING 12 VENT SYSTEM 14 SAFETY CONTROLS 19 START UP AND ADJUSTMENTS 20 WIRING DIAGRAM 27 LIST OF FIGURES Combus...

Page 2: ...s from combustible materials as listed under Clearances to Combustibles in Table 1 Provide clearances for servicing ensuring that service access is allowed for both the burners and blower These models...

Page 3: ...other cleaning tools 2 Soap powders bleaches waxes or other cleaning com pounds plastic items or containers gasoline kerosene ciga rette lighter fluid dry cleaning fluids or other volatile fluid 3 Pai...

Page 4: ...connec tors are designed to be connected to the rectangular duct under the floor and sealed Refer to the instructions supplied with the duct con nector for proper installation Refer to the separate a...

Page 5: ...in Residential and Modular Home duct designs IMPORTANT If the supply air duct is being connected to the furnace without the use of an accessory duct connector then a transition duct must be installed...

Page 6: ...ld be sealed to prevent air leakage The sheet metal should be cross hatched to eliminate any popping of the sheet metal when the indoor fan is energized On all installations without a coil a removable...

Page 7: ...T OF FURNACE 1 MAX BETWEEN ROD BACK OF FURNACE SUPPORT BRACKET FIGURE 4 Dimensions FRONT LEFT SIDE RIGHT SIDE FRONT FRONT BOTTOM IMAGE TOP IMAGE A B 40 3 4 20 31 1 8 5 3 4 2 1 2 28 1 2 1 1 8 7 3 8 A C...

Page 8: ...d in the duct system using an external duct filter box attached to the furnace plenum Any branch duct rectan gular or round duct attached to the plenum must attach to the vertical plenum above the fil...

Page 9: ...the body of the gas valve will damage the valve causing improper oper ation and or the valve to leak LoNOx furnaces requiring propane LP gas must have the LoNOx screens removed prior to installation...

Page 10: ...field supplied thermostat by following the instructions that come with the thermostat With the thermostat set in the OFF position and the main electrical source disconnected connect the thermostat wi...

Page 11: ...24 Volt Common Optional w Batteries BN11C01124 DP11C40124 PSC FURNACE CONTROL SINGLE STAGE AIR CONDITIONING BN11C00124 BP11C50124 PP11C70224 THERMOSTAT THERMOSTAT THERMOSTAT Single Stage A C w Single...

Page 12: ...11 If furnace staging is desired with two single stage furnaces on a com mon duct where the gas burner on the first furnace operates on W1 and the gas burner on the second furnace operates on W2 then...

Page 13: ...winning func tion of this board ensures that both blowers turn on and off simulta neously and operate on the same blower speed Even when only one furnace is supplying heat both furnace blowers must ru...

Page 14: ...ceeding 45 degrees A vent system having not more than one 60 degree offset is permitted The vent system must be attached to the flue collar with a minimum of two 2 mechanical fasteners such as screws...

Page 15: ...provided by the manufacturer of the power vent This unit may be horizontally vented using 4 10 2 cm diameter pipe with a minimum length of 4 5 feet 1 37 m and a maximum length of 34 5 feet 10 82 m wit...

Page 16: ...pwards and be supported to prevent sagging The vent system may be supported by the use of clamps or hangers secured to a permanent part of the structure every four 4 ft 1 22 m FAN ASSISTED COMBUSTION...

Page 17: ...4 An automatically operated damper or automatically adjustable lou vers shall be interlocked so that the main burner cannot operate unless either the damper or the louver is in the fully open position...

Page 18: ...d Ambient Combustion Air GABLE VENT GAS VENT SOFFIT VENT VENTILATED ATTIC TOP ABOVE INSULATION OPTIONAL INLET a OUTLET AIR a VENTILATED CRAWL SPACE GAS WATER HEATER VENTILATED ATTIC TOP ABOVE INSULATI...

Page 19: ...reset control that provides over temperature protection due to reduced airflow This may be caused by 1 Dirty filter 2 If the indoor fan motor should fail 3 Too many supply or return registers closed o...

Page 20: ...gth 2 pieces of 1 8 0 3 cm tubing that are 4 10 0 cm in length a 1 8 0 3 cm tee and a 1 8 0 3 cm adapter to connect the U tube manometer or the digital pressure measur ing equipment to the gas valve p...

Page 21: ...at the gas meter times a barometric pressure and temperature correction factor of 0 960 times 3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas mul...

Page 22: ...E The regulated outlet pressures both low and high have been calibrated at the factory Additional pressure adjustment should not be necessary If adjustment is necessary set to the following specifica...

Page 23: ...are as follows LED will turn on for 1 4 second and off for 1 4 second This pattern will be repeated the number of times equal to the code For example six on flashes equals a number 6 fault code All fl...

Page 24: ...ide heat for the house NOTE If a flame is detected the control flashes the LED for 1 8 of a second and then enters a flame stabilization period DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL The control...

Page 25: ...1493 1430 1373 1304 1199 1089 967 816 699 44 2 42 3 40 5 38 9 36 9 33 9 30 8 27 4 23 1 19 8 100 1200 B 29 3 34 0 B High 1710 1650 1580 1510 1420 1330 1260 1160 1090 930 48 4 46 7 44 7 42 8 40 2 37 7 3...

Page 26: ...lowing example Example For a 60 000 BTUH 38 06 kW furnace operating on high speed blower it is found that total system static is 0 58 w c To deter mine the system airflow complete the following steps...

Page 27: ...268894 UIM A 0407 Unitary Products Group 27 SECTION X WIRING DIAGRAM FIGURE 30 Wiring Diagram 268834...

Page 28: ...o change without notice Printed in U S A 268894 UIM A 0407 Copyright by York International Corp 2007 All rights reserved Supersedes 167253 UIM C 0706 Unitary 5005 Norman Product York OK Group Drive 73...

Reviews: