background image

035-18575-001-A-1102

8

Unitary Products Group

Concrete piers can also support ground level units.
These piers should (1) extend below the frost line, (2)
be located under each of the section's four corners,
and (3) be sized to carry the load of the corner it sup-
ports.

On either rooftop or ground level installations, rubber
padding can be applied under the unit to lessen any
transmission of vibration.

Holes are provided in the base rails for bolting the unit
to its foundation.

For ground level installations, precautions should be
taken to protect the unit from tampering and unautho-
rized persons from injury. Screws on access panels will
prevent casual tampering. Further safety precautions
such as a fenced enclosure or locking devices on the
panels may be advisable. Check local authorities for
safety regulations.

CLEARANCES

The units must be installed with sufficient clearance for
air to enter the condenser coil, for air discharge and for
servicing access. See Table 4 for clearances.

NOTE: Additional clearance is required to remove the

compressors out the side of the unit, unless a
means is available to lift the compressor out
through the top of the unit.

RIGGING

Exercise care when moving the unit. Do not remove
any crating until the unit is near the place of installation.

When preparing to move the unit, always determine the
center of gravity (see Table 3 and Figure 1) of the unit
in order to equally distribute the weight. Slings con-
nected to the compressor end of a unit will usually have
to be made shorter, so the unit will lift evenly (see
Figure 2).

Rig units by attaching chain or cable hooks to the holes
provided on the base rail. See Figure 6 for details on
rigging holes.

The length of the spreader bars must exceed the width
of the unit. Refer to Table 3 for unit weights.

Do not permit overhanging structures or shrubs
to obstruct condenser air discharge.

TABLE 4: MINIMUM CLEARANCES

Clearance Description

Distance in Inches

Overhead (Top)

120

Front (Access Cover)

36

Rear (piping connections)

36

Left Side

30

Right Side

30

Bottom

*

*.

In all installations where snow accumulates and winter
operation is expected, additional height must be provided
to insure normal condenser airflow.

0

Spreaders, longer than the largest dimension
across the unit must be used across the top of
the unit.

Before lifting a unit, make sure that its weight is
distributed equally on the cables so that it will
lift evenly.

FIGURE 2 - TYPICAL RIGGING

Summary of Contents for HA 300

Page 1: ...intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal injury and or equipment dam age may result if in...

Page 2: ...ES 23 CONDENSER FAN OPERATION 23 OPERATION WITH A TWO STAGE THERMOSTAT 24 OPERATION WITH A FOUR STAGE THERMOSTAT 24 SECURE OWNER S APPROVAL 24 MAINTENANCE 24 CLEANING CONDENSER SURFACE 24 LUBRICATION...

Page 3: ...ER OF GRAVITY INCHES 7 4 MINIMUM CLEARANCES 8 5 ELECTRICAL DATA 10 6 SUCTION LINES 13 7 LIQUID LINES 14 Tbl Pg 8 R 22 LINE CHARGE 14 9 UNIT DIMENSIONS INCHES 17 10 PIPING AND ELECTRICAL CONNECTION SIZ...

Page 4: ...egory H Air Conditioner Split System A Product Identifier A R 22 Standard Efficiency 2 Pipe B R 22 Standard Efficiency 4 Pipe 300 Nominal Cooling Capacity MBH 300 25 Ton 360 30 Ton 480 40 Ton 600 50 T...

Page 5: ...and operation of the basic condensing unit For information on the installation and operation of the evaporator blower units refer to instruction Form No 035 18496 000 All accessories come with a sepa...

Page 6: ...50 50 2 60 3 8 16 1598 1648 50 3 1 0 360 System 1 15 2 2 24 36 12600 1 50 25 60 1710 1770 31 5 1 0 System 2 15 2 2 24 36 12600 1 50 25 60 31 5 480 System 1 20 2 2 30 22 16550 1 50 32 5 78 1941 2017 3...

Page 7: ...The beams should 1 be positioned per pendicular to the roof joists 2 Extend beyond the dimensions of the section to distribute the load on the roof 3 Be capable of adequately supporting the con centra...

Page 8: ...e compressor out through the top of the unit RIGGING Exercise care when moving the unit Do not remove any crating until the unit is near the place of installation When preparing to move the unit alway...

Page 9: ...producing a high noise level the scroll is misphased CONTROL WIRING Route the necessary low voltage control wires from the Simplicity control board to the thermostat and also from the low voltage cond...

Page 10: ...ding charge A filter drier MUST be field installed in the liquid line of every system to prevent dirt and moisture from damag ing the system Properly sized filter driers are shipped with each condensi...

Page 11: ...e sealing disk and prepare the joint for connections of the main lines Connect the lines while maintaining a flow of Nitrogen from the liquid line valve service port through the evaporator back to the...

Page 12: ...dehydration charge the required weight of liquid refrigerant into the liquid access connection After refrigerant flow slows start the compressor and continue to charge refrigerant gas through the suct...

Page 13: ...System 2 Full Capacity 15 47 1 3 8 3529 14 3 1 5 8 2498 6 3 2 1 8 1439 1 7 Half Capacity 7 5 23 5 1 3 8 1765 4 3 1 5 8 1249 1 9 2 1 8 720 0 5 HB480 System 1 Full Capacity 20 64 1 5 8 3402 11 1 2 1 8...

Page 14: ...9 1 1 8 141 1 1 Half Capacity 10 32 5 8 174 6 2 7 8 120 1 0 1 1 8 70 0 3 System 2 Full Capacity 20 64 5 8 348 22 1 7 8 240 3 9 1 1 8 141 1 1 Half Capacity 10 32 5 8 174 6 2 7 8 120 1 0 1 1 8 70 0 3 HB...

Page 15: ...035 18575 001 A 1102 Unitary Products Group 15 FIGURE 3 FIELD WIRING DIAGRAM HA 300 UNIT POWER SUPPLY 380 415 3 50 POWER SUPPLY 380 415 3 50...

Page 16: ...035 18575 001 A 1102 16 Unitary Products Group FIGURE 4 FIELD WIRING DIAGRAM HB 360 480 600 UNITS POWER SUPPLY 380 415 3 50 POWER SUPPLY 380 415 3 50...

Page 17: ...nit from the left or right side Electrical connections for power and control wiring is made from the front of the unit left of the electrical con trol box access See Tables 10 11 and 12 and Figures 6...

Page 18: ...75 001 A 1102 18 Unitary Products Group FIGURE 6 25 30 40 TON POWER AND CONTROL WIRING CONNECTIONS Control Wiring Power Wiring FIGURE 7 50 TON POWER AND CONTROL WIRING CONNECTIONS Control Wiring Power...

Page 19: ...12 CONTROL WIRING 7 8 HOLE TABLE 11 PIPING AND ELECTRICAL CONNECTION SIZES 30 40 50T INCHES CONNECTION ENTRY SIZE SUCTION LINE SYS 1 1 5 8 OD LIQUID LINE SYS 1 7 8 OD SUCTION LINE SYS 2 1 5 8 OD LIQUI...

Page 20: ...A 1102 20 Unitary Products Group FIGURE 9 30 40 TON PIPING CONNECTIONS Liquid Sys 2 Suction Sys 2 Liquid Sys 1 Suction Sys 1 FIGURE 10 50 TON PIPING CONNECTIONS Liquid Sys 2 Suction Sys 2 Liquid Sys 1...

Page 21: ...lectrical wire laying against a hot refrigerant line INITIAL START UP 1 Supply power to the unit through the disconnect switch at least 8 hours prior to starting the com pressor 2 Move the system swit...

Page 22: ...lock out the associated compressor and flash an error code see Table 12 An ambient air switch will lock out mechanical cooling at 40 F In order to operate the unit in ambient temper atures below 40 F...

Page 23: ...rol will separate the flash codes with a 2 sec ond off delay between flash codes Under normal oper ation the control will flash the LED at a rate of 1 second on and 1 second off This will be the Heart...

Page 24: ...be connected to stage one and two of the thermostat 2 Terminals Y3 and Y4 of the Simplicity control board controlling system two should be connected to stage three and four of the thermostat SECURE OW...

Page 25: ...with the TXV s left to the factory setting If the TXV s have been adjusted in the field the chart above may no longer apply FIGURE 13 30 TON CHARGING CHART 30 ton Charging Chart 100 150 200 250 300 35...

Page 26: ...with the TXV s left to the factory setting If the TXV s have been adjusted in the field the chart above may no longer apply FIGURE 15 50 TON CHARGING CHART 50 ton Charging Chart 100 150 200 250 300 35...

Page 27: ...035 18575 001 A 1102 Unitary Products Group 27 FIGURE 16 25 TON CONDENSER UNIT WIRING DIAGRAM 380 415 3 50...

Page 28: ...035 18575 001 A 1102 28 Unitary Products Group FIGURE 17 30 or 40 TON CONDENSING UNIT WIRING DIAGRAM 380 415 3 50...

Page 29: ...035 18575 001 A 1102 Unitary Products Group 29 FIGURE 18 50 TON CONDENSER UNIT WIRING DIAGRAM 380 415 3 50...

Page 30: ...035 18575 001 A 1102 30 Unitary Products Group...

Page 31: ...035 18575 001 A 1102 Unitary Products Group 31...

Page 32: ...o change without notice Printed in U S A 035 18575 001 A 1102 Copyright by Unitary Products Group 2002 All rights reserved Supersedes 035 18575 000 A 0402 Unitary 5005 Norman Products York OK Group Dr...

Reviews: