background image

278806-BIM-A-1106

Unitary Products Group

23

SAFETY CONTROLS

The Simplicity™ control board incorporates features to
monitor safety circuits as well as minimize compressor
wear and damage. An anti-short cycle delay (ASCD) is
utilized to prevent operation of a compressor too soon
after its previous run. Additionally, a minimum run time
is imposed anytime a compressor is energized to allow
proper oil return to the compressor. The ASCD is initi-
ated on unit start-up and on any compressor reset or
lockout.

The Simplicity™ control board monitors the following
inputs for each cooling system:

A high-pressure switch is factory installed to pro-
tect against excessive discharge pressure due to a 
blocked condenser coil or a condenser fan motor 
failure. During cooling operation, if a high-pressure 
limit switch opens, the Simplicity™ control board 
will de-energize the associated compressors and 
initiate the 5-minute ASCD. If the call for cool is still 
present at the end of the ASCD, the control board 
will re-energize the halted compressor.

If a high-pressure switch opens three times within 
two hours of operation, the Simplicity™ control 
board will lockout the associated system compres-
sors and will flash an error code (see Table 13).

A low-pressure switch to protect the unit against 
excessively low suction pressure is standard on all 
condensing units.

If the low-pressure switch opens during normal opera-
tion, the Simplicity™ control board will de-energize the
compressor, initiate the ASCD, and shut down the con-
denser fans.

On startup, if the low-pressure switch opens, the Sim-
plicity™ control board will monitor the low-pressure
switch to make sure it closes within one minute. If it
fails to close, the unit will shut down the associated
compressor and begin an ASCD. If the call for cool is
still present at the end of the anti-short cycle time
delay, the control board will re-energize the halted
compressor.

If a low-pressure switch opens three times within one
hour of operation, the Simplicity™ control board will
lock-out the associated compressor and flash an error
code (see Table 13).

An ambient air switch will lock out mechanical cooling
at 40

°

F. In order to operate the unit in ambient temper-

atures below 40

°

F, the optional low ambient kit must be

field installed which will allow the unit to operate during
conditions down to 0

°

F.

The refrigerant systems are independently monitored
and controlled. On any fault, only the associated sys-
tem will be affected by any safety/preventive action.
The other refrigerant system will continue to operate
unless it is affected by the fault as well.

PUMP OUT

The pump out function is a standard feature on the 25
to 50 ton systems. The pump out circuit is activated
each time the first and third compressor stage is called
for by the thermostat. As such, it’s a “Pump Out On
Start Up” design. A normally closed solenoid valve
(POS1, 2, 3 or 4) is placed in the liquid line, just prior to
expansion valve.

When cooling is not being called for by the thermostat,
the pump out solenoid (POS) is not energized, so it’s in
the closed position. When the Simplicity™ control
receives a call for cooling, it energizes a compressor.
With the POS being closed, it causes the pressure on
the low side of the system to begin falling.

When the low pressure switch (LPS) opens, the control
board energizes its on-board pump out relay, providing
a 24vac output to an external relay used to energized
the pump out solenoid. The refrigeration circuit being
controlled is not in normal operating mode.

If the low pressure switch is already open on a call for
cooling, the pump out relay is energized immediately. If
the LPS does not open after 5 minutes, the pump out
relay is energized.

CONTINUOUS BLOWER

By setting the room thermostat to “ON,” the supply air
blower will operate continuously.

INTERMITTENT BLOWER

With the room thermostat fan switch set to “AUTO” and
the system switch set to either the “AUTO” or “HEAT”
settings, the blower is energized whenever a cooling or
heating operation is requested. The blower is ener-
gized after any specified delay associated with the
operation.

When energized, the indoor blower has a minimum run
time of 30 seconds. Additionally, the indoor blower has
a delay of 10 seconds between operations.

Summary of Contents for HF-25 - 25 Ton

Page 1: ...NING Notes are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal injury and or equipment dam age ma...

Page 2: ...PPROVAL 26 MAINTENANCE 27 CLEANING CONDENSER SURFACE 27 LUBRICATION 27 COMPRESSOR REPLACEMENT 27 LIST OF FIGURES Fig Pg 1 CORNER WEIGHTS CENTER OF GRAVITY 7 2 TYPICAL RIGGING 8 3 TYPICAL FIELD WIRING...

Page 3: ...OF GRAVITY INCHES 7 4 MINIMUM CLEARANCES 8 5 ELECTRICAL DATA 10 6 SUCTION LINES 13 7 LIQUID LINES 14 8 R 22 LINE CHARGE 14 Tbl Pg 9 UNIT DIMENSIONS INCHES 18 10 PIPING AND ELECTRICAL CONNECTION SIZES...

Page 4: ...onditioner Split System L Product Identifier F R 22 Standard Efficiency 2 Pipe L R 22 Standard Efficiency 4 Pipe 30 Nominal Cooling Capacity MBH 25 25 Ton 30 30 Ton 40 40 Ton 50 50 Ton C Heat Type C C...

Page 5: ...properly REFERENCE This instruction covers the installation and operation of the basic condensing unit For information on the installation and operation of the evaporator blower units refer to instru...

Page 6: ...8 1658 49 65 1 0 30 System 1 15 2 2 24 36 12690 1 25 25 60 1730 1790 30 08 1 0 System 2 15 2 2 24 36 12690 1 25 25 60 30 08 40 System 1 20 2 2 30 22 15414 1 50 32 5 78 1961 2037 37 83 1 0 System 2 20...

Page 7: ...er pendicular to the roof joists 2 Extend beyond the dimensions of the section to distribute the load on the roof 3 Be capable of adequately supporting the con centrated loads at the corners See Figur...

Page 8: ...ompressor out through the top of the unit RIGGING Exercise care when moving the unit Do not remove any crating until the unit is near the place of installation When preparing to move the unit always d...

Page 9: ...oducing a high noise level the scroll is misphased CONTROL WIRING Route the necessary low voltage control wires from the Simplicity control board to the thermostat and also from the low voltage conden...

Page 10: ...the system Properly sized filter driers are shipped with each condensing section NOTE Installing a filter drier does not eliminate the need for the proper evacuation of a system before it is charged A...

Page 11: ...mage the valve seals Ensure the valve is ade quately protected prior to any brazing on the valve body Unbraze the sealing disk and prepare the joint for connections of the main lines Connect the lines...

Page 12: ...be evacuated After proper evacuation and dehydration charge the required weight of liquid refrigerant into the liquid access connection After refrigerant flow slows start the compressor and continue t...

Page 13: ...2 System 2 Full Capacity 15 47 1 3 8 2873 4 1 1 5 8 2030 1 8 2 1 8 1167 0 5 Half Capacity 7 5 23 5 1 3 8 1437 1 1 1 5 8 1015 0 5 2 1 8 850 0 2 HL 40 System 1 Full Capacity 20 64 1 5 8 3120 4 3 2 1 8 1...

Page 14: ...5 8 440 13 2 7 8 212 2 3 1 1 8 90 0 6 System 2 Full Capacity 20 64 5 8 440 13 2 7 8 212 2 3 1 1 8 90 0 6 HL 50 System 1 Full Capacity 25 76 5 8 400 8 5 7 8 265 3 4 1 1 8 156 1 0 System 2 Full Capacit...

Page 15: ...278806 BIM A 1106 Unitary Products Group 15 FIGURE 3 TYPICAL FIELD WIRING DIAGRAM HF 25 UNIT Note 1 Note 1 See page 16 and 17 for details on wiring HF HL models to non LF LL indoor models...

Page 16: ...278806 BIM A 1106 16 Unitary Products Group FIGURE 4 TYPICAL FIELD WIRING DIAGRAM HL 30 40 50 UNITS...

Page 17: ...els isolation relays must be installed to avoid overloading on 75 VA transformer on condensing unit Non LF LL units may not include any or all of the components required to wire the unit use the diagr...

Page 18: ...t from the left or right side Electrical connections for power and control wiring is made from the front of the unit left of the electrical con trol box access See Tables 10 11 and 12 and Figures 7 th...

Page 19: ...BIM A 1106 Unitary Products Group 19 FIGURE 7 25 30 40 TON POWER AND CONTROL WIRING CONNECTIONS Control Wiring Power Wiring FIGURE 8 50 TON POWER AND CONTROL WIRING CONNECTIONS Control Wiring Power W...

Page 20: ...7 8 HOLE TABLE 11 PIPING AND ELECTRICAL CONNECTION SIZES 30 40 50T INCHES CONNECTION ENTRY SIZE SUCTION LINE SYS 1 1 5 8 OD LIQUID LINE SYS 1 7 8 OD SUCTION LINE SYS 2 1 5 8 OD LIQUID LINE SYS 2 7 8 O...

Page 21: ...1106 Unitary Products Group 21 FIGURE 10 30 40 TON PIPING CONNECTIONS Liquid Sys 2 Suction Sys 2 Liquid Sys 1 Suction Sys 1 FIGURE 11 50 TON PIPING CONNECTIONS Liquid Sys 2 Suction Sys 2 Liquid Sys 1...

Page 22: ...ectrical wire laying against a hot refrigerant line INITIAL START UP 1 Supply power to the unit through the disconnect switch at least 8 hours prior to starting the com pressor 2 Move the system switc...

Page 23: ...ck out the associated compressor and flash an error code see Table 13 An ambient air switch will lock out mechanical cooling at 40 F In order to operate the unit in ambient temper atures below 40 F th...

Page 24: ...es the compressors and condenser fans are de energized Otherwise the unit operates each cooling stage until the ASCD has elapsed Upon the completion of first stage cooling the blower is stopped follow...

Page 25: ...ressor Lockout Off Off On Off On 6 Flashes LPS2 Compressor Lockout Off Off On On Off 7 Flashes FS1 Compressor Lockout Off Off On On On 8 Flashes FS2 Compressor Lockout Off On Off Off Off 10 Flashes Co...

Page 26: ...art immediately upon a call for first stage cooling However fan two is equipped with a fan cycling switch and will not start until the sys tem head pressure reaches 280 psig Condenser fan two will ope...

Page 27: ...ny maintenance COMPRESSOR REPLACEMENT Obtain replacement compressor or parts from your local Distributor FIGURE 14 25 TON CHARGING CHART 25 ton Charging Chart 100 150 200 250 300 350 400 60 70 80 90 1...

Page 28: ...th the TXV s left to the factory setting If the TXV s have been adjusted in the field the chart above may no longer apply FIGURE 16 40 TON CHARGING CHART 40 ton Charging Chart 100 150 200 250 300 350...

Page 29: ...harge Pressure PSI Outdoor Temperature 115 105 95 85 75 65 1 Ensure all condenser fans are running when charging unit One fan may shut down at lower ambient temperatures making the chart above inaccur...

Page 30: ...278806 BIM A 1106 30 Unitary Products Group FIGURE 18 TYPICAL 25 TON CONDENSER UNIT WIRING DIAGRAM 208 230 3 60...

Page 31: ...278806 BIM A 1106 Unitary Products Group 31 FIGURE 19 TYPICAL 25 TON CONDENSER UNIT WIRING DIAGRAM 460 3 60 575 3 60...

Page 32: ...278806 BIM A 1106 32 Unitary Products Group FIGURE 20 TYPICAL 30 or 40 TON CONDENSING UNIT WIRING DIAGRAM 208 230 3 60...

Page 33: ...278806 BIM A 1106 Unitary Products Group 33 FIGURE 21 TYPICAL 30 or 40 TON CONDENSING UNIT WIRING DIAGRAM 460 3 60 575 3 60...

Page 34: ...278806 BIM A 1106 34 Unitary Products Group FIGURE 22 TYPICAL 50 TON CONDENSER UNIT WIRING DIAGRAM 208 230 3 60...

Page 35: ...278806 BIM A 1106 Unitary Products Group 35 FIGURE 23 TYPICAL 50 TON CONDENSER UNIT WIRING DIAGRAM 460 3 60 575 3 60...

Page 36: ...change without notice Printed in U S A 278806 BIM A 1106 Copyright 2006 by Unitary Products Group All rights reserved Supersedes 66410 035 19321 000 B 0404 Unitary 5005 Norman Products York OK Group D...

Reviews: