278806-BIM-A-1106
Unitary Products Group
29
FIGURE 17 - 50 TON CHARGING CHART
50-ton Charging Chart
100
150
200
250
300
350
400
60
70
80
90
100
Suction Pressure (PSI)
Discharge Pressure (PSI)
Outdoor Temperature
115º
105º
95º
85º
75º
65º
1. Ensure all condenser fans are running when charging unit. One fan may shut down at lower ambient temperatures ma
k
ing the chart above
inaccurate.
2. This chart is applicable to the unit with the TX
V
's left to the factory setting. If the TX
V
's have been adjusted in the field, the chart above may no
longer apply.