background image

66339-BIM-C-0206

Unitary Products Group

13

Each unit has a low static and a high static option. The
15 Ton unit offers a 3 hp motor and sheave combina-
tion for the low static option and a 5 hp motor and
sheave combination for the high static option. The 20
Ton offers a 5 hp motor to be used with either the low
or high static sheaves.

Each motor pulley has:

1.

A threaded barrel with two flats (or notched
recesses 180º apart).

2.

A movable flange with one set screw.

After the movable flange has been rotated to the
proper number of turns open, the set screw should be
tightened against the flat on the barrel to lock the mov-
able flange in place. If the pulley includes a locking col-
lar, the locking collar must be loosened to adjust the
setting of the movable flange.

Note the following:

1.

The supply of air CFM must be within the limita-
tions shown in the tables. Be sure not to over amp
the motor.

2.

All pulleys can be adjusted in 1/2 turn increments.

3.

The tension on the belt(s) should be adjusted for a
deflection of 3/16” per foot of belt span with an
applied force of 2 to 3 pounds.

Once the supply air blower motor is operating, adjust
the resistances in both the supply and the return duct
system to balance the air distribution throughout the
conditioned space. The job specification may require
that the balancing be done by someone other than the
equipment installer.

To check the supply air CFM after the initial balancing
has been completed:

1.

Drill two 5/16” holes in the side panel as shown in
figure 10 for the 15 Ton or figure 11 for the 20 Ton.

2.

Insert at least 6” of 1/4” tubing into each of these
holes for sufficient penetration into the air flow on
either side of the indoor coil.

NOTE: 

The tubes must be inserted and held in a posi-
tion perpendicular to the air flow so that veloc-
ity pressure will not affect the static pressure
reading.

3.

Using an inclined manometer, determine the pres-
sure drop across a dry coil.

4.

Consult the appropriate coil pressure drop chart to
determine the CFM.

5.

After the readings have been obtained, remove the
tubes and seal up the drilled holes in the side
panel. Dot plugs (P/N 029-13880-000) are avail-
able through Source One parts.

FIGURE 12 - HOLE LOCATIONS FOR PRESSURE 

DROP READINGS (15 TON)

5/16"
HOLE

5/16"
HOLE

18"

7"

22"

10"

EVAPORATOR

COIL

FILTERS

COIL SECTION

Summary of Contents for LL-15

Page 1: ...SAVE THIS MANUAL SPLIT SYSTEM AIR COOLED EVAPORATOR BLOWER MODELS LL 15 LL 20 66339 BIM C 0206 LL 20 LL 15 CONTENTS NOMENCLATURE 3 GENERAL 4 NOTES CAUTIONS AND WARNINGS 4 REPLACEMENT PARTS 4 INSPECTIO...

Page 2: ...DUCT ANGLES 11 DRAIN CONNECTIONS 11 REFRIGERANT MAINS 11 EVAPORATOR SECTION PIPING 12 SUPPLY AIR BLOWER ADJUSTMENT 12 ELECTRICAL CONNECTIONS 14 INDOOR UNIT ELECTRICAL RATINGS 14 LIST OF FIGURES Fig P...

Page 3: ...ump F Product Identifier F R 22 Standard Efficiency 2 Pipe L R 22 Standard Efficiency 4 Pipe 15 Nominal Cooling Capacity MBH 15 15 Ton 20 20 Ton C Heat Type C Cooling Only 00 Nominal Heating Capacity...

Page 4: ...9675 Toll Free Fax 877 379 7920 INSPECTION As soon as a unit is received it should be inspected for possible damage during transit If damage is evident the extent of the damage should be noted on the...

Page 5: ...ages are ordered and shipped separately for field mounting MOTOR MOUNT ARRANGEMENTS The motor mounting arrangement can be changed to allow motor access based on the airflow arrangement required The re...

Page 6: ...nels from the blower section 2 Remove the Phillips machine screws located inside casing corner angles that hold the coil and blower sections together 3 Rotate the blower section for the desired air di...

Page 7: ...ENTS ARRANGEMENT 1 4 8 OR 11 ARRANGEMENT 3 5 OR 10 ARRANGEMENT 2 6 OR 7 NOTE Since the motor mounting assembly can not be secured to the panel with the blower openings the motor cannot be installed in...

Page 8: ...MENTS AIR AIR BLOWER 1 EVAPORATOR COIL AIR AIR 2 AIR AIR AIR AI R 4 AIR AIR 5 AIR AIR 6 3 IF REQUIRED SOME AIR CAN BE BROUGHT THROUGH THE BOTTOM OF THE EVAPORATOR SECTION FIGURE 7 HORIZONTAL AIRFLOW A...

Page 9: ...round the bottom skid A lift truck may be used to raise a unit to a suspended location Refer to table 2 for the total unit operating weight CLEARANCES A 25 inch clearance is required on the end with t...

Page 10: ...the cooling season or through an unheated space during the heating season 2 Include a vapor barrier around the outside to pre vent the absorption of moisture 3 Be no less than 2 inches thick with the...

Page 11: ...e of the cabinet Drain piping should be constructed as shown in figure 9 The 5 inch dimension is intended to exceed the neg ative static pressure developed by the supply air blow ers If it does not th...

Page 12: ...o an access valve or charging tail Choose a procedure that will allow nitrogen to flow continuously through the system and reach all joints to be brazed Begin the refrigerant main piping by installing...

Page 13: ...applied force of 2 to 3 pounds Once the supply air blower motor is operating adjust the resistances in both the supply and the return duct system to balance the air distribution throughout the conditi...

Page 14: ...13 HOLE LOCATIONS FOR PRESSURE DROP READINGS 20 TON Approximate RPM Chart Turns Open LL 15 LL 20 Low Static Drive Kit Hi Static Drive Kit Low Static Drive Kit Hi Static Drive Kit 5 650 840 580 700 4 6...

Page 15: ...ON Pressure Drop Across Indoor Coil 15 Ton 0 0 05 0 1 0 15 0 2 0 25 0 3 0 35 0 4 0 45 0 5 4000 5000 6000 7000 8000 CFM I W C FIGURE 15 PRESSURE DROP ACROSS INDOOR COIL 20 TON Pressure Drop Across Indo...

Page 16: ...8 7600 719 2 8 2 61 792 3 3 3 12 877 4 0 3 7 956 4 6 4 31 7800 730 3 0 2 78 807 3 5 3 31 888 4 1 3 88 960 4 8 4 49 Denotes use of 5 hp motor with high static pulley kit TABLE 4 LL 20 20 TON AIRFLOW 0...

Page 17: ...BLOWER PERFORMANCE 15 TON BLOWER PERFORMANCE 0 4 0 6 0 8 1 1 2 1 4 1 6 4200 4700 5200 5700 6200 6700 7200 7700 CFM ESP FIGURE 17 20 TON BLOWER PERFORMANCE 20 TON BLOWER PERFORMANCE 0 4 0 6 0 8 1 1 2 1...

Page 18: ...MENSIONS LL 15 and LL 20 TABLE 5 UNIT DIMENSIONS LL 15 AND LL 20 MODEL A B C D E F G H J K L M LL 15 89 1 2 85 0 26 0 29 1 2 59 1 7 16 15 7 8 12 7 16 15 13 16 16 16 20 3 4 LL 20 100 1 8 95 5 8 33 1 4...

Page 19: ...66339 BIM C 0206 Unitary Products Group 19 FIGURE 19 PIPING and ELECTRICAL CONNECTION LOCATIONS...

Page 20: ...e without notice Printed in U S A 66339 BIM C 0206 Copyright 2006 by Unitary Products Group All rights reserved Supersedes 66339 BIM B 0304 035 18503 001 B 0304 Unitary 5005 Norman Products York OK Gr...

Reviews: