background image

4.  Reinstall the main burners in the assembly by reversing

the removal process.

5.  Install the high altitude conversion labels as described in

the LABELS sections of this instruction.

6.  Refer to the unit installation instructions to complete the

installation before continuing with these procedures.

TESTS AND ADJUSTMENTS

The following tests must be performed at the time of conversion
following completion of the installation.

WARNING: Make sure both gas and power supplies
are shut off before proceeding.

1.  Connect a manometer to the pressure tap on both the inlet

and the outlet side of the gas valve. Connect a power
supply and a gas supply to the unit, if not already con-
nected.

CAUTION: On 90+ AFUE models, refer to unit instal-
lation instructions for proper procedure for connecting
manometer to furnace.

2.  Turn on the gas supply and bleed air from the gas supply lines

at a point as close to the inlet or the gas valve as is practical.

WARNING: Make sure the space is free of  gas
before proceeding.

3.  Turn the gas valve control knob to the ON position.

4.  Make sure unit electrical disconnect switch is in the OFF

position.

5.  Set the room thermostat to call for heat.

6.  Turn unit electrical disconnect switch to ON. The combus-

tion blower should start and the hot surface igniter should
start glowing.

7.  After air has been purged from the gas supply line, ignition

should occur. Shortly after ignition, the manifold and gas
inlet pressures can be checked on the manometers. Main
burner ignition may be delayed on the first ignition cycle
due to air in the gas manifold.

8.  Adjust manifold pressure to the specifications shown in

Table 6. This setting will result in an input which is properly
derated for your altitude. Supply gas must be within the
range shown in Table 6. If required, adjust the incoming
regulator spring  so that the pressure falls within the range.

WARNING:  On 90+ AFUE furnaces, the gas valve
regulator cap must be in place to determine final gas
pressure setting.

9.  Observe several ignition cycles. All main burners must

ignite without delayed ignition or burning at the orifices. If
delayed ignition is observed, verify that the igniter is prop-
erly mounted (not loose or crooked on bracket, and that
bracket screws are not loose).

10. If burning at the orifices, excessive yellow tipping, or

excessive noise is observed during any phase of main
burner operation, verify unit operation.

11.  With the main burners ignited, check for gas leaks, espe-

cially in the following locations: gas valve inlet and outlet
connections, manifold union in the burner compartment,
and main burner orifices where they thread into the mani-
fold. Repair any leaks found and recheck.

WARNING: Do not use an open flame or any source
of ignition to check for leaks.

12. Operate the furnace for 15 minutes and measure the

supply and return air temperatures. Verify that the tem-
perature rise (supply air - return air rise) is within the
allowable range. See the unit data plate for the mini-
mum/maximum allowable temperature rise. If the meas-
ured rise is in excess of the maximum shown on the data
plate, a higher blower speed must be selected. See the
unit wiring diagram to make this change.

Burner Orifices

Size # 

Source 1 Part Number

Blank

029 - 20423 - 000

41

029 - 20423 - 041

42

029 - 20423 - 042

43

029 - 20423 - 043

44

029 - 20423 - 044

45

029 - 20423 - 045

46

029 - 20423 - 046

47

029 - 20423 - 047

48

029 - 20423 - 048

49

029 - 20423 - 049

50

029 - 20423 - 050

51

029 - 20423 - 051

52

029 - 20423 - 052

55

029 - 20423 - 055

56

029 - 20423 - 056

57

029 - 20423 - 057

58

029 - 20423 - 058

59

029 - 20423 - 059

60

029 - 20423 - 060

NATURAL GAS

PROPANE (LP) GAS

TABLE 6 - GAS PRESSURES

TABLE 5 - ORIFICE PART NUMBERS

INLET GAS PRESSURE MUST BE

AT 4.5"-13.8" WC AT FURNACE.

SET MANIFOLD PRESSURE AT 1.6" WC FOR LOW FIRE

SET MANIFOLD PRESSURE AT 3.5" WC FOR HIGH FIRE

INLET GAS PRESSURE MUST BE

AT 11-13.8" WC AT FURNACE.

SET MANIFOLD PRESSURE AT 5.5" WC FOR LOW FIRE

SET MANIFOLD PRESSURE AT 10" WC FOR HIGH FIRE

650.78-N2.1V

Unitary Products Group

3

Reviews: