background image

035-20499-001 Rev. B (1004)

Unitary Products Group

23

FILTER PERFORMANCE

The airflow capacity data published in Table 15 represents blower per-
formance WITHOUT filters. To determine the approximate blower per-
formance of the system, apply the filter drop value for the filter being
used or select an appropriate value from the Table 16.

NOTE: 

The filter pressure drop values in Table 16 are typical values for

the type of filter listed and should only be used as a guideline.
Actual pressure drop ratings for each filter type vary between fil-
ter manufacturers.

* Washable Fibers are the type supplied with furnace (if supplied).

APPLYING FILTER PRESSURE DROP TO 

DETERMINE SYSTEM AIRFLOW

To determine the approximate airflow of the unit with a filter in place, fol-
low the steps below:

1.

Select the filter type.

2.

Select the number of return air openings or calculate the return
opening size in square inches to determine the proper filter pres-
sure drop.

3.

Determine the External System Static Pressure (ESP) without the
filter.

4.

Select a filter pressure drop from the table based upon the number
of return air openings or return air opening size and add to the
ESP from Step 3 to determine the total system static.

5.

If total system static matches a ESP value in the airflow table (i.e.
0.20 w.c. (50 Pa), 0.60 w.c. (150 Pa), etc,) the system airflow cor-
responds to the intersection of the ESP column and Model/Blower
Speed row.

TABLE 16: 

Filter Performance - Pressure Drop Inches W.C. and (kPa)

AIRFLOW 

RANGE

MINIMUM OPENING SIZE

FILTER TYPE

DISPOSABLE

WASHABLE FIBER*

PLEATED

1 Opening

2 Openings

1 Opening

2 Opening

1 Opening

2 Opening

1 Opening

2 Opening

Sq. in.   

m

2

Sq. in.

m

2

In w.c.

Pa

In w.c.

Pa

In w.c.

Pa

In w.c.

Pa

In w.c.

Pa

In w.c.

Pa

0 - 750

230

.15

0.01

2.5

0.01

2.5

0.15

37

751 - 1000

330

.21

0.04

10

0.03

7.5

0.20

50

1001 - 1250

330

.21

0.08

20

0.07

17

0.20

50

1251 - 1500

330

.21

0.08

20

0.07

17

0.25

62

1501 - 1750

380

.25

658

.42

0.14

35

0.08

20

0.13

32

0.06

15

0.30

75

0.17

42

1751 - 2000

380

.25

658

.42

0.17

42

0.09

22

0.15

37

0.07

17

0.30

75

0.17

42

2001  &  Above

463

.30

658

.42

0.17

42

0.09

22

0.15

37

0.07

17

0.30

75

0.17

42

FIELD INSTALLED ACCESSORIES - NON-ELECTRICAL 

MODEL NO.

DESCRIPTION

USED WITH

1NP0580

PROPANE (LP) CONVERSION KIT

ALL MODELS 

1SF0101

EXTERNAL SIDE FILTER RACK

ALL MODELS

1CT0302

CONCENTRIC INTAKE/VENT 2”

60, 80, 100 INPUT MBH

1CT0303

CONCENTRIC INTAKE/VENT 3”

100, 120 MBH

1HT0901

SIDEWALL VENT TERMINATION

ALL MODELS

1PS0501

HIGH ALTITUDE PRESSURE SWITCH KIT 

(Does Not Include Orifices)

FOR APPLICATION 

INFORMATION SEE FORM 

035-20506-001

1PS0502
1PS0503
1PS0504
1PS0505
1PS0506
1BR0317

EXTERNAL BOTTOM FILTER RACK

17-1/2” CABINETS

1BR0321

21” CABINETS

1BR0324

24-1/2” CABINETS

1NK0301

CONDENSATE NEUTRALIZER KIT

ALL MODELS

Summary of Contents for PV9

Page 1: ...des TABLE OF CONTENTS SAFETY 1 DUCTWORK 3 FILTERS 6 GAS PIPING 6 ELECTRICAL POWER 8 COMBUSTION AIR AND VENT SYSTEM 9 CONDENSATE PIPING 16 SAFETY CONTROLS 16 START UP AND ADJUSTMENTS 17 WIRING DIAGRAM...

Page 2: ...tional vehicles Failure to carefully read and follow all instructions in this manual can result in furnace malfunction death personal injury and or property damage Furnaces for installation on combust...

Page 3: ...is required for passage to the front when servicing or for inspection or replacement of flue vent connections In all cases accessibility clearances shall take precedence over clear ances for combustib...

Page 4: ...ABLES 2 AND 3 are to be used as a guide only to help the installer determine if the duct sizes are large enough to obtain the proper air flow CFM through the furnace TABLES 2 and 3 ARE NOT to be used...

Page 5: ...rn End 5 Be sure to seal the furnace to plenum connections to prevent air leakage Refer to Figure 1 for unit and plenum dimensions Attic installations must meet all minimum clearances to combustibles...

Page 6: ...28 27 25 2000 57 C 16 x 25 41 x 64 20 x 25 51 x 64 120 112 2000 35 14 32 80 2000 57 D 2 16 x 25 2 41 x 64 22 x 25 56 x 64 All installations must have a filter installed Toe Plate Removable Rectangula...

Page 7: ...4 National Fuel Gas Code or in Canada CAN CGA B149 1 00 Natural Gas and Propane Installation Code HIGH ALTITUDE PRESSURE SWITCH CONVERSION For installation in locations where the altitude is less than...

Page 8: ...furnace s control system requires correct polarity of the power supply and a proper ground connection Refer to Figure 6 IMPORTANT The power connection leads and wiring box may be relo cated to the le...

Page 9: ...hese instructions IMPORTANT The VENT SYSTEM must be installed as specified in these instructions for Residential and Non HUD Modular Homes The sealed combustion air vent system is the only configurati...

Page 10: ...is as follows 1 Cut piping to the proper length beginning at the furnace 2 Deburr the piping inside and outside 3 Chamfer bevel the outer edges of the piping 4 Dry fit the vent piping assembly from th...

Page 11: ...1 US Installation2 A Clearance above grade veranda porch deck or balcony 12 inches 30 cm 12 inches 30 cm B Clearance to window or door that may be opened 6 inches 15 cm for applications 10 000 Btuh 3k...

Page 12: ...bustion air systems must be installed so the vent and the combustion air pipes terminate in the same atmospheric zone Refer to Figures 13 or 14 VENTING MULTIPLE UNITS Multiple units can be installed i...

Page 13: ...STION AIR Combustion air is supplied through a PVC or ABS pipe that is connected to the PVC coupling attached to the burner box and is terminated in a ventilated attic or crawl space The combustion ai...

Page 14: ...ion smaller than 0 25 6 4 mm 3 A manually operated damper or manually adjustable louvers are not permitted for use 4 A automatically operated damper or automatically adjustable lou vers shall be inter...

Page 15: ...w usage Follow all notes procedures and required materials in the SEALED COMBUS TION AIR SUPPLY section in these instructions when installing the combustion air pipe from the unit and into a ventilate...

Page 16: ...densate sump pump must be approved for use with acidic condensate CONDENSATE DRAIN TRAP AND DRAIN FREEZE PROTECTION Special precautions MUST be made if installing furnace in an area which may drop bel...

Page 17: ...bing 2 pieces of 4 10 cm length x 1 8 0 3 cm diameter tubing 1 5 16 0 8 cm tee 1 5 16 0 8 cm x 1 8 0 3 cm reducing coupling 1 1 8 0 3 cm adapter 1 Dwyer Manometer These items are required in order to...

Page 18: ...ivided by the time it took to measure 2 cubic ft 0 0566 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 14 times 0 00283 m3 of gas measured at...

Page 19: ...as shown in Figure 24 The procedure below is used to adjust either the high fire manifold pressure or the low fire manifold pressure IMPORTANT The cap for the pressure regulator must be removed entir...

Page 20: ...Heating and Cooling Airflow The heating and the cooling airflows are preset at the factory The heat ing airflow is set to the maximum CFM The cooling airflow is set to pro vide 90 percent of the maxi...

Page 21: ...all for cooling the motor will ramp up to 63 of full capacity and will stay there for 90 seconds then will ramp up to full capacity At the end of the cooling cycle the motor will ramp down to 63 of fu...

Page 22: ...4 1880 1250 53 2 35 4 A C 1560 1010 44 2 28 6 1620 1030 45 9 29 2 C B 1470 940 41 6 26 6 1500 960 42 5 27 2 B C 1370 890 38 8 25 2 1410 880 39 9 24 9 D B 1460 930 41 3 26 3 1490 920 42 2 26 1 C A 125...

Page 23: ...the airflow table i e 0 20 w c 50 Pa 0 60 w c 150 Pa etc the system airflow cor responds to the intersection of the ESP column and Model Blower Speed row TABLE 16 Filter Performance Pressure Drop Inc...

Page 24: ...ed in U S A 035 20499 001 Rev B 1004 Copyright by York International Corp 2004 All rights reserved Supersedes 035 20499 001 Rev A 0904 Unitary 5005 Norman Product York OK Group Drive 73069 SECTION X W...

Reviews: