R16 - Installation and Programming Manual
38
PROGRAMMING
This option selects the non-zone events which will report alarms
by dialler.
P75E, 1E, REPORT DURESS ALARM
OFF = Duress Alarm reporting is disabled.
ON = Duress Alarm reporting is enabled.
(Default = OFF).
P75E, 2E, REPORT MEDICAL ALARM
OFF = Medical Alarm reporting is disabled.
ON = Medical Alarm reporting is enabled.
(Default = ON).
P75E, 3E, REPORT PANIC ALARM
This option applies to keypad panic and radio key panic.
OFF = Panic Alarms reporting is disabled.
ON = Panic Alarms reporting is enabled.
(Default = ON).
P75E, 4E, REPORT FIRE ALARM
OFF = Fire Alarm reporting is disabled.
ON = Fire Alarm reporting is enabled.
(Default = ON).
P75E, 5E, REPORT TAMPER ALARM
This option applies to panel tamper and external tamper.
OFF = Tamper Alarm reporting is disabled.
ON = Tamper Alarm reporting is enabled.
(Default = ON).
P75E, 6E,
Not used.
P75E, 7E, REPORT KEYPAD TAMPER ALARM
Reports entry of consecutive invalid codes in Armed mode, alarm
on 4th failed attempt.
OFF = Keypad Tamper Alarm reporting is disabled.
ON = Keypad Tamper Alarm reporting is enabled.
(Default = ON).
P75E, 8E, REPORT EXIT FROM INSTALLER MODE
OFF = Exit From Installer Mode reporting is disabled.
ON = Exit From Installer Mode reporting is enabled.
(Default = OFF).
PROGRAMMING SEQUENCE
1. Press:
P75E
2. Press:
[1-8] E
to toggle each option on or off.
Zone light/s on indicates which option/s are enabled.
PROGRAM MODE LEVEL:
Installer, Remote by PC.
FACTORY DEFAULT:
1E = OFF
2E = ON
3E = ON
4E = ON
5E = ON
6E = not used
7E = ON
8E = OFF
RELATED OPTIONS:
P77E, Report Miscellaneous
Restorals.
P75E
REPORT MISCELLANEOUS ALARMS