 R16 - Installation and Programming Manual

38

PROGRAMMING

This  option  selects  the  non-zone  events  which  will  report  alarms 
by dialler.

P75E, 1E, REPORT DURESS ALARM

OFF = Duress Alarm reporting is disabled. 
ON = Duress Alarm reporting is enabled.
(Default = OFF).

P75E, 2E, REPORT MEDICAL ALARM

OFF = Medical Alarm reporting is disabled. 
ON = Medical Alarm reporting is enabled.
(Default = ON).

P75E, 3E, REPORT PANIC ALARM

This option applies to keypad panic and radio key panic.
OFF = Panic Alarms reporting is disabled. 
ON = Panic Alarms reporting is enabled.
(Default = ON).

P75E, 4E, REPORT FIRE ALARM

OFF = Fire Alarm reporting is disabled. 
ON = Fire Alarm reporting is enabled.
(Default = ON).

P75E, 5E, REPORT TAMPER ALARM

This option applies to panel tamper and external tamper.
OFF = Tamper Alarm reporting is disabled. 
ON = Tamper Alarm reporting is enabled.
(Default = ON).

P75E, 6E, 

Not used.

P75E, 7E, REPORT KEYPAD TAMPER ALARM

Reports entry of consecutive invalid codes in Armed mode, alarm 
on 4th failed attempt.
OFF = Keypad Tamper Alarm reporting is disabled. 
ON = Keypad Tamper Alarm reporting is enabled.
(Default = ON).

P75E, 8E, REPORT EXIT FROM INSTALLER MODE

OFF = Exit From Installer Mode reporting is disabled. 
ON = Exit From Installer Mode reporting is enabled.
(Default = OFF).

PROGRAMMING SEQUENCE

1. Press: 

P75E

2. Press: 

[1-8] E

 to toggle each option on or off.

Zone light/s on indicates which option/s are enabled.

PROGRAM MODE LEVEL:

Installer, Remote by PC.

FACTORY DEFAULT:

1E = OFF
2E = ON
3E = ON
4E = ON
5E = ON
6E = not used
7E = ON
8E = OFF

RELATED OPTIONS:

P77E, Report Miscellaneous 
Restorals.

P75E

REPORT MISCELLANEOUS ALARMS

Summary of Contents for R16

Page 1: ...INSTALLER S MANUAL R16 Radio Control Panel INSTALLATION AND PROGRAMMING MANUAL Revision 1 8QLWHFK...

Page 2: ...mary 13 Alarm Type Descriptions 14 System Alarm Descriptions 15 Quick Start Panel Programming 16 Quick Start RADIO Programming 17 PROGRAMMING 19 How to enter Program Mode 19 PANEL PROGRAMMING OPTIONS...

Page 3: ...esigned to provide at least 48 hours service running on the backup battery alone This includes one full alarm condition with sirens strobe and dialler The built in dialler uses Contact ID format for c...

Page 4: ...s as shown below All late model8QLWHFK transmitters send encrypted transmissions to prevent eavesdropping and substitution 8QLWHFK fixed transmitters can send a regular supervision signal which the R1...

Page 5: ...t the 12 way wire loom to the main board 5 Connect the plug pack wiring to the Terminal Board making sure that mains power is not turned on at this stage Connect siren wires and external tamper inputs...

Page 6: ...ia cavity wall Cable entry via conduit Lid Assembly CABLE ENTRY Cable for the plug pack and optional accessories can be drawn through a cavity wall into the rear of the R16 or on the surface via condu...

Page 7: ...EARTH AC TAMP STR PIEZ 0V ZONE PIEZ STR SIREN 17V AC Earth External Horn Speaker Max Qty 1 Strobe Light Max Qty 1 Hardwired Zone Input 2K2 EOL resistor 0V ground for accessories 100mA max External Scr...

Page 8: ...S SIREN Timed siren output for connection of maximum one 1 8 Ohm horn speaker STR Output for connection of 1 x strobe light As a power saving feature the strobe output times out after 11 hours If main...

Page 9: ...eypad Acknowledge key press Keypad Valid entry end of Exit Time Keypad Invalid entry Low battery AC Fail Medical Alarm Alarm Entry Delay etc Arm Disarm The Doorbell has been pressed Alarm condition Pa...

Page 10: ...5 seconds Turns on all LCD icons while the button is pressed Zone is sealed Not ready to arm unsealed zones or system faults Disarmed Disarmed Normal Normal Normal Normal Normal Normal Normal Normal...

Page 11: ...on DISARMED The system is Off This is the normal mode when the premises are occupied Day Zones and 24 Hour Zones if configured are active DAY MODE The system is Disarmed and a zone or zones have been...

Page 12: ...ss both star keys together Panic shortcut must be on P62E 3E Press the Panic button for at least 2 seconds DURESS ALARM Duress alarm should only used by arrangement with your monitoring station User C...

Page 13: ...h a radio key programmed as Duress press and hold the device PANIC button for the required length of time No sirens or strobe are active MEDICAL Keypad Press and hold Right Hand keypad Star key for 2...

Page 14: ...turn them off when a transmission from a device without a low battery is received LOW BATTERY Radio PIR Indicates a low battery condition A low battery alarm occurs when the detector operates Flash t...

Page 15: ...press 1 0 0 2 0 0 3 0 0 To program the Master Code Example to program the Master Code to be 1234 P11E is the option for the Master Code Press Enter the new Master Code followed by E Enter the new Mast...

Page 16: ...mmed Beep beep 3 beeps will be heard if the RADIO PIR was successfully learned Zone icon 1 will then be on steady To program a Radio Key Example to program a Radio Key to user slot 2 P10E is the optio...

Page 17: ...R16 Installation and Programming Manual 18 This page is intentionally blank...

Page 18: ...m Mode PROGRAM light is ON 2 Then press INSTALLER CODE The keypad will respond with 3 beeps This is Installer Program Mode PROGRAM light is FLASHING HOW TO EXIT PROGRAM MODE 1 Press then This is Opera...

Page 19: ...hone No 1 to be 03 1234 1234 Press P00E 0312341234E TO CLEAR A TELEPHONE NUMBER To clear a telephone number enter the MEMORY key in place of the telephone number E g to clear Voice Dialling Phone No 2...

Page 20: ...to choose from The doorbell is activated by the optional Radio Doorbell transmitter Most 8QLWHFK transmitters can be programmed to operate the Doorbell function see page 25 Extra Option for Radio Keys...

Page 21: ...EXAMPLE TO TEST THE SIGNAL STRENGTH OF A RADIO PIR ON ZONE 2 1 Press P08E 2E Radio icon and numeric icon 2 is flashing waiting for radio data 2 Trigger the radio device on zone 2 3 The display will a...

Page 22: ...de A long beep indicates that the radio device may already be programmed on another zone 3 Connect the battery in the radio device Three beeps indicates device has been successfully programmed EXAMPLE...

Page 23: ...o Key button to send the Learn message See How To Send The Learn Message Three beeps indicates the radio key has been successfully programmed EXAMPLE To program a Radio Key to user slot 2 Press P10E 2...

Page 24: ...is currently selected 2 Press 1 5 E This selects a new Extra Option EXAMPLE A Radio Key is programmed to User Code slot 2 To change the Extra Option to Ignore Panic press P12E 4E USER CODE SLOT KEYPA...

Page 25: ...when the control panel is central station monitored Shortcut arming ARM E if enabled is sent as User 25 RELATED OPTIONS P10E Program Radio Keys P11E P25E PROGRAM KEYPAD CODES Options P11E P25E allow...

Page 26: ...it Delay time PROGRAMMING SEQUENCE 1 Press P28E The digits of the existing value will be displayed 2 Press new time E The digits of the new value will be displayed EXAMPLE To program the exit delay ti...

Page 27: ...ROGRAMMING SEQUENCE 1 Press P41E 2 Press 1 16 E to enable each zone for this option To deselect a zone from this option program it to be Instant or Handover Zone light s on indicates which option is e...

Page 28: ...e Example Upstairs zones are Disarmed while downstairs zones are Armed in Monitor mode PROGRAMMING SEQUENCE 1 Press P51E 2 Press 1 16 E to toggle each zone on or off Zone light s on indicates which op...

Page 29: ...MMING SEQUENCE 1 Press P53E 2 Press 1 16 E to enable each zone for this option To deselect a zone from this option program it to be Delayed Instant or Handover Zone light s on indicates which option s...

Page 30: ...The 2 sec Siren burst can be disabled by option P62E 7E Default ON P60E 7E KEYPAD BACKLIGHT BLANKING OFF Keypad Backlighting is always on ON Keypad Backlighting blanking enabled The backlighting on t...

Page 31: ...RTCUT To enable or disable the Arming shortcut OFF Shortcut disabled ARM USER CODE E ON Shortcut enabled ARM E Default ON PROGRAMMING SEQUENCE 1 Press P62E 2 Press 1 5 E to toggle each option on or of...

Page 32: ...ing 3 chirps disarming OFF Siren chirps disabled ON Siren chirps enabled Default OFF P64E 5E Not used P64E 6E KEYPAD PANIC ALARM Keypad Panic can be triggered by pressing both star keys together The d...

Page 33: ...defeat the system If 2 consecutive identical valid encrypted messages are received a minimum time apart the alarm is raised 2 Encryption Hacking In this case an attempt is made to crack the encrypted...

Page 34: ...s P67E 6E PROGRAM MODE LEVEL Installer Remote by PC FACTORY DEFAULT 0 disabled NOTES RELATED OPTIONS P88E 6E Report Supervision Alarms P67E RADIO SUPERVISION TIME PROGRAMMING Setting this option on al...

Page 35: ...1 to be 03 1234 1234 Press P70E 0312341234E TO CLEAR A TELEPHONE NUMBER To clear a telephone number enter the MEMORY key in place of the telephone number E g to clear Central Station Telephone Number...

Page 36: ...e on or off Zone light s on indicates which option s are enabled PROGRAM MODE LEVEL Installer Remote by PC FACTORY DEFAULT 1 16 ON All zones report Alarms RELATED OPTIONS P76E Report Zone Restorals P7...

Page 37: ...ARM This option applies to panel tamper and external tamper OFF Tamper Alarm reporting is disabled ON Tamper Alarm reporting is enabled Default ON P75E 6E Not used P75E 7E REPORT KEYPAD TAMPER ALARM R...

Page 38: ...SEQUENCE 1 Press P78E 2 Press 1 16 E to toggle each zone on or off Zone light s on indicates which option s is enabled PROGRAM MODE LEVEL Installer Remote by PC FACTORY DEFAULT 1 16 OFF All zones rep...

Page 39: ...Enter a value between 0 and 255 A value of 0 zero triggers the next test call immediately on exit from Installer program Mode PROGRAMMING SEQUENCE 1 Press P84E The digits of the existing value will be...

Page 40: ...ccess remain enabled This option is useful for temporary disabling of the dialler without affecting other dialler options OFF The dialler is enabled The dialler will still remain disabled if no teleph...

Page 41: ...Cancel Report enabled PROGRAMMING SEQUENCE 1 Press P88E 2 Press 5E to turn the option on or off Zone light s on indicates the option is enabled PROGRAM MODE LEVEL Installer Remote by PC FACTORY DEFAU...

Page 42: ...aded by a remote computer OFF Remote Access is disabled ON Remote Access is enabled Default OFF P90E 2E Not used P90E 3E REMOTE ARMING Allows the remote Arming of the control panel using a standard DT...

Page 43: ...for Remote Access Programmable from 1 to 16 rings Enter a value between 1 and 16 PROGRAMMING SEQUENCE 1 Press P91E The digits of the existing value will be displayed 2 Press required rings E The digit...

Page 44: ...PROGRAMMING SEQUENCE 1 Press P97E 2 Press 1E Factory defaults are restored PROGRAM MODE LEVEL Installer Remote by PC FACTORY DEFAULT not applicable P97E 1E FACTORY DEFAULT PANEL OPTIONS This option er...

Page 45: ...new installer code will be displayed One beep will sound on the first entry of the new code three beeps will sound on the second entry of the new code if the code was successfully programmed PROGRAM M...

Page 46: ...e at 1 No more than 20 dial events will be reported between each disarming of the panel MESSAGE QUEUE The panel places event reports in a queue Multiple simultaneous reports or reports previously unsu...

Page 47: ...ry 383 Tamper Detector 381 Radio device supervision poll fail Restores are always sent for the following alarms on disarming when a valid code is entered if Restores are enabled 101 Radio Key Medical...

Page 48: ...and then hang up 2 Call the number again within 60 seconds 3 The R16 will answer the second call immediately sound a beep for 2 seconds then after a pause it will sound a lower frequency tone The R16...

Page 49: ...io reed switch for wireless window and door protection Transmits Alarm Restore Tamper and Low Battery reports 3V lithium battery supplied RK4 RADIO KEY The RK4 is a full sealed waterproof radio key wi...

Page 50: ...upplied R15 RADIO PIR The 8QLWHFK R15 Radio PIR has a detection range of 15m and vertical creep zones Features Radio Supervision and Encryption when used with compatible 8QLWHFK control panels Pulse C...

Page 51: ...E Program Keypad Codes 2 15 none P26E Entry Delay Time 20 sec 27 P28E Exit Delay Time 60 sec P29E Siren Reset Time 5 min P40E Instant Zones Zones 3 16 28 P41E Entry Delay Zones Zone 1 P42E Handover Zo...

Page 52: ...not used 4E Siren chirps Arm Disarm OFF 6E Keypad Panic Alarm ON 7E Fire Alarm OFF 8E Medical Alarm OFF P65E 1E Radio Jamming Alarm OFF 34 2E Radio Substitution Alarm OFF P67E Radio Supervision Time...

Page 53: ...P75E for full list All ON 39 P78E Report Multiple Zone Alarms 1 16 All OFF P82E 1E Send Restoral Immediately when Resealed OFF 2E Send Restoral After Siren Time Resealed OFF 3E Send Restoral on Disarm...

Page 54: ...e Monitor OFF 43 P90E 1E Remote Access OFF 43 2E not used OFF 3E Remote Arming OFF 4E Remote Disarming OFF P91E Required Rings to answer incoming calls 1 44 P96E Clear Event Memory 45 P97E 1E Factory...

Page 55: ...transmitted or stored in a retrieval system in any form or by any means electronic mechanical photocopying recording or otherwise without the prior written permission of 8QLWHFK 8QLWHFK reserves the r...