Installation, Operation and Maintenance Manual
VariCool EZ-Fit
28
Subject to change without notice.
40.20-IM (0118)
PROBLEM
POSSIBLE CAUSE
POSSIBLE SOLUTION
Suction
pressure
too low
1.
Flash gas in liquid line
2.
Obstructed expansion valve
3.
Loss of fluid in expansion valve bulb
4.
Clogged filter drier
5.
Lack of air flow
6.
Entering WB too low
7.
Evaporator blower running
backwards
1.
Check for refrigerant leak
2.
Repair leak, evacuate and recharge refrigerant
system�
3.
Replace thermal expansion valve
4.
Replace filter drier
5.
Check filters and coil for any blockages
6.
Verify that blower is rotating in the proper direction
7.
Confirm that entering return air conditions fall within
acceptable range
8.
Reset low pressure safety switch if necessary
9.
Check phase of incoming power to unit (3 ph units only)�
Reverse any two incoming power supply wires (except
ground)�
No cooling
1.
Controller not set properly
2.
Control wiring issue
3.
Controls in an alarm condition
4.
High or low pressure switch open
5.
Compressor thermal overload open
1.
Turn on and set controller for desired operation
2.
Check wiring connections against schematic�
3.
Check all connections for tightness�
4.
Check wire continuity�
5.
Refer to controller troubleshooting
6.
Reset high or low pressure switch
7.
Compressor internal overload may require an
extended period of time (1 hour or more) to reset
Condensate
carry over
1.
Air flow too high
1.
Reduce air flow
Condensate
pump does
not run
1.
Check to see that power to the
pump is present
2.
Confirm that float is moves freely
3.
Confirm that dirt or algae is not
interfering with float action
1.
Locate and repair electric issue�
2.
Clean float and sump
Condensate
pump runs
with no
discharge
1.
Tubing blocked or kinked
2.
Check valve blocked
3.
Impeller blocked
4.
Tubing elevation or run exceeds
head capability�
1.
Inspect, clean or straighten as necessary�
2.
Clean check valve
3.
Remove debris from pump impeller
4.
Verify tubing run is within pump head limitations�
Summary of Contents for VariCool EZ-Fit 12