background image

Installation, Operation and Maintenance Manual

VariCool EZ-Fit

36

Subject to change without notice.

Start-Up Procedures 

(R-410a Systems)

1� 

Start up must be performed by a qualified HVAC 

Technician

2� 

Make certain that all power is disconnected at the main 

power circuit breaker or service disconnect before 

starting any of this procedure

3� 

Check all electrical screw terminals and wiring lugs 

for tightness internal to the equipment Components 

may have loosened due to vibration during transit 

or handling Verify that the main power block lug 

connections made in the field are tight and secure

4� 

Confirm that the voltage rating of the equipment data 

tag coincides with the power that will be delivered to 

the unit

5� 

Verify that the circuit protection for the unit satisfies 

Local and National Codes according to the unit data 

tag Minimum Circuit Ampacity (MCA) and Maximum 

Fuse Size (MFS)

6� 

Leak check the refrigerant system While the unit was 

leak checked at the factory, leaks can develop during 

transit and / or handling

7� 

Confirm that the unit condensate has been adequately 

trapped and taken to a suitable point for disposal

8� 

Verify that the filters are in place, clean and usable

9� 

Apply power to the unit Switch the circuit breaker or 

field supplied electrical service disconnect switch to the 

on position

NOTE: If the unit has crankcase heaters and the surrounding 

ambient is 70˚ F or lower, let the compressors sit for 

approximately 24 hours before proceeding�

10� 

Record the voltage at the unit terminals

11� 

On the wall controller, navigate to the system enables 

menu Set the compressor to OFF Set the system  

ON/OFF menu to the ON position

12� 

Verify that the evaporator blower(s) are rotating in the 

correct direction (three phase units only)

NOTE: If the evaporator blower motor runs backwards, 

shut off all power to the unit. Switch any two of the 

incoming power leads at the unit main power terminal 

block. The unit has been wired and phased properly 

at the factory� DO NOT change any factory wiring to 

correct for a phase problem�

NOTE: Before conducting the following start up sections 

connect a refrigerant gauge set to the unit Schrader 

connections� Install temperature sensors or probes to 

record the appropriate refrigerant line temperatures�

13� 

Set the wall controller to a temperature set point 

approximately 5˚ lower than the entering air 

temperature This should energize the compressor(s)

NOTE: Dependent upon the options and/or the thermostat, 

there may be a delay for the compressor(s) operation�

14� 

While waiting for the compressor(s) to stabilize, record 

the External Static Pressure (ESP) for the evaporator 

blower

NOTE: Make sure all the unit access panels are in place when 

taking these readings.

WARNING

HEAT EXCHANGER FREEZE RISK:

 

Heat Exchanger will fail if operated at or 

near  the  freezing  point  of  water/glycol 

mixture
The following precautions must be taken:

•  At startup, fluid side must be started 

first

•  At shutdown, refrigerant side must be 

shut down first

•  Fluid side outlet must have temperature 

monitoring and emergency shutdown 

equipment in case temperature 

approaches too close to the freezing 

point

15� 

Verify that the incoming water / fluid pressure does not 

exceed the rating for the water / fluid control valves

16� 

Verify that the unit piping and heat exchangers will not 

be subjected to freezing conditions

17� 

Confirm that no joints are leaking in the cooling fluid 

circuit(s)

18� 

Document the type of fluid being used as the cooling 

medium If glycol is being used, make sure the mixture 

is adequate for any low ambient conditions that may be 

possible

Continued on next page

Summary of Contents for VariCool EZ-Fit Series

Page 1: ...VariCool EZ Fit Series Installation Operation and Maintenance Manual Effective March 2023 Variable Air Volume Water Cooled Water Source Heat Pump...

Page 2: ......

Page 3: ...ments 19 Water Piping 20 Electrical and Controls 21 Power Wiring 21 Transformer 22 Voltage Unbalance 22 High Duct Static Pressure Switch 22 Low Voltage Control Devices 22 Wall Display 22 BMS Applicati...

Page 4: ...w unitedcoolair com website Scroll down to the Serial Search box and enter the unit serial number The serial number is a combination of the year month and sequential order of build date This will retu...

Page 5: ...s IMPORTANT and INFORMATION will be used in areas where there is important information but not hazard related These instructions local codes and ordinances and applicable standards that apply to pipin...

Page 6: ...litate handling most units or modules are shipped on a wooden skid Use caution when moving the unit or modules so that damage does not occur when moving each piece to the final installation location w...

Page 7: ...apply to all air path configurations b Service clearances apply to all size units SERVICE ACCESS TOP VIEW Additional Clearance required for ECM DDP Fans Only SERVICE ACCESS SERVICE ACCESS FILTER ACCES...

Page 8: ...fficient depth in water column to permit the condensate to flow from the drain pan Failure to have a sufficient drain trap will cause the condensate to overflow the drain pan or to cause the unit to s...

Page 9: ...5 3 6 14x24 25x25 6 14 2 27 Dual Module Nominal Tons Blower Type Filter Size Evap Coil Compressor R 410A ECM iDDP DWDI Qty Size in Rows FPI Qty Lbs Ckt 30 8 4 15x20 20x20 4 14 4 7 40 12 18x25 4 14 4 1...

Page 10: ...8 6280 6280 N A 35 77 1 2 60 1 8 105 1 8 3660 3780 N A 70 153 58 5 8 105 1 8 7320 7560 N A 40 45 77 59 1 2 112 4220 4350 N A 80 90 152 1 2 58 112 8440 8700 N A Single Module Nominal Tons Condensing Se...

Page 11: ...8 3 4 60 1 8 34 460 80 90 2 77 34 1 2 78 1850 2 77 25 78 1450 4 38 1 2 59 1 2 34 460 1 Dimension in includes hardware 2 Dimension in does not include depth of removeable Filter Rack Filter rack depth...

Page 12: ...notice that the middle beam supports the mid section of the unit Field supplied spring vibration isolators are to be installed on each corner of each frame per module 2 Channel Steel with Waffle Pads...

Page 13: ...Z Fit 13 Subject to change without notice Figure 3C Base Option 2 Channel Steel with Waffle Pads Bottom View Figure 3D Base Option 2 Unit View Single Module Figure 3F Base Option Unit View Single Modu...

Page 14: ...ide opposite the filters Each section is also alphabetically labeled so that each section can be mated properly Set the sections so that point A aligns to A B aligns to B C aligns to C Evaporator Sect...

Page 15: ...flow between the evaporator and compressor condensing section For shipping purposes the refrigerant fittings are held in place to the cabinet using vinyl coated hangers and a mounting bracket These a...

Page 16: ...they ensure perfect alignment of the mating section surfaces Once adjacent sections have been put into place use the included hardware to pull sections together until the curved surfaces of the 3D Int...

Page 17: ...Installation Operation and Maintenance Manual VariCool EZ Fit 17 Subject to change without notice Figure 5A Single Module TYPICAL 8 PLACES...

Page 18: ...Installation Operation and Maintenance Manual VariCool EZ Fit 18 Subject to change without notice Figure 5B Dual Module TYPICAL 16 PLACES...

Page 19: ...or local codes Typically these units are installed using the mechanical room as the return air plenum However return ductwork can be applied Sufficient duct flange area exists on the filter frame for...

Page 20: ...in case temperature approaches too close to the freezing point INFORMATION Do not reduce the water inlet or outlet connection size as this will restrict water flow and increase water pressure drop CA...

Page 21: ...accordance with NEC National Electrical Code and NFPA National Fire Protection Agency most current versions as well as any applicable state or local codes INFORMATION The correct phase sequence of th...

Page 22: ...ted and resolved for the unit power supply the building manager or owner should be notified of the issue to get the proper power supplied to the unit High Duct Static Pressure Switch A high duct stati...

Page 23: ...lled shipped loose item The return air temp sensor should be placed in an area that can properly average all of the return air preferably right before the filters if possible For maintenance room plen...

Page 24: ...pipe feeding condenser water to the unit A reduction of water flow from the unit head pressure control valve operation may cause nuisance trips Water flow switch trips will cause loss of water flow al...

Page 25: ...jury CAUTION Any maintenance should be conducted by qualified HVAC service personnel only Potentially hazardous situations may result in personal injury equipment or property damage Lubrication Belt D...

Page 26: ...nsioning below Figure 8 Belt Tensioning For proper tensioning use the following equation Deflection Belt Span 64 Belt span is in inches from center pulley to center pulley see Figure 8 Belt tension is...

Page 27: ...higher operating costs or occupant discomfort The finned coils in a unit should be checked at least every six 6 months or more frequently based on experience of the specific application Before cleani...

Page 28: ...rigerant system glass If the color of this indicator is green or blue the refrigerant is normal When the indicator is yellow an abnormal condition exists such as moisture within the refrigerant circui...

Page 29: ...operating parameters to obtain the CFM 3 Water balance verification Ensure that the unit has 3 gpm per ton available to it at all times if a pump is of variable speed it must be able to ramp up its sp...

Page 30: ...enser 5 Resolve incoming voltage issue 6 Resolve alarm condition Note Compressor internal overload may require an extended period of time 1 hour or more to reset Compressor short cycles 1 Reduced air...

Page 31: ...mal expansion valve bulb is tight on suction line 5 Confirm thermal expansion valve bulb is located properly on suction line 6 Replace thermal expansion valve 7 Replace filter drier 8 Check filters an...

Page 32: ...rly 2 Control wiring issue 3 Controls in an alarm condition 4 High or low pressure switch open 5 Compressor thermal overload open 1 Turn on and set controller for desired operation 2 Check wiring conn...

Page 33: ...es due to i failure to install operate or maintain deliverables as directed in any instruction manual provided or under applicable law or regulation ii misuse abuse neglect or modification of a delive...

Page 34: ...eliverable by Seller whichever occurs first Except as set forth in these terms Seller makes no representation or warranty of any type express or implied including any warranty of merchantability warra...

Page 35: ...been adjusted to the voltage being applied Yes No 11 Has overcurrent protection breakers fuses been installed to match the unit nameplate requirement Yes No 12 Do all fans rotate freely Yes No 13 Does...

Page 36: ...in the correct direction three phase units only NOTE If the evaporator blower motor runs backwards shut off all power to the unit Switch any two of the incoming power leads at the unit main power ter...

Page 37: ...nce between the liquid line temperature and the saturation temperature corresponding to the liquid line pressure 11 Record the Amps for the evaporator blower motor and each compressor If the system is...

Page 38: ...lters are in place clean usable Yes ____________ No ____________ Three Phase Measured Voltage L1 L2_____________ L2 L3_ ____________ L1 L3__________ Evaporator Blower Motor Rotation OK Yes ___________...

Page 39: ...________ Suction Superheat _ ________ _ ________ _ ________ _ ________ Liquid Line Pressure psi________ psi________ psi________ psi________ Saturation Temperature Liquid Line Temperature F_________ F_...

Page 40: ...in Tons Single Module 30 40 50 60 70 80 or 90 Nominal Cooling Capacity in Tons Dual Module e G Common to all f 3 208 230 3 60 4 460 3 60 g A Two Compressors D Four Compressors h T Traditional Cabinet...

Page 41: ...7 00 PM Eastern Standard Time Saturday 8 00 AM 4 00 PM Call 717 843 4311 and Dial extension 165 This log must be kept with the unit It is the responsibility of the owner and or maintenance service con...

Page 42: ...Installation Operation and Maintenance Manual VariCool EZ Fit 42 Subject to change without notice NOTES...

Page 43: ...ITED WARRANTY United CoolAir Units are backed by a 1 year limited warranty on parts and a 5 year limited warranty on the compressor labor not included Maintenance items such as filters and belts are e...

Reviews: