WirelessHART Toxic & Combustible Gas Detector
IM_TCD60-01
www.ueonline.com/vanguard
19
7. Navigating through the handheld HART communicator menu, choose Configure Network ID and enter
the Network ID. The operation will use WirelessHART commands 773-Write Network ID and 774-Read
Network ID.
Note: Use *Quick Code 9, 2, 1 to be taken directly to the Configure Network ID choice.
*
Quick Codes may not work with all handheld HART communicators.
8. Navigating through the handheld HART communicator menu, choose Configure Join Key and enter the
Join Key. This operation will use WirelessHART command 768-Write Join Key.
Note: Use *Quick Code 9, 2, 2 through 9, 2, 5 to be taken directly to the Configure Join Key choice.
9. Upon inputting the Network ID and Join Key, the device initializes connection with the network in the
following phases. The phase status will be indicated on the device display.
A. Idle: The device is accepting configuration commands (see Figure 31).
B. Searching: Once the device receives a join command, it proceeds to the Searching mode. The
device keeps its receiver activated while searching for available networks (see Figure 32).
C. Negotiating: The device has detected the desired network and has received a join request from
the network manager (see Figure 33).
C H
4
: X X X % L E L
B AT T E R Y: X . X X V
N E T: I D L E
B AT T E R Y: X . X X V
N E T: S E A R C H I N G
B AT T E R Y: X . X X V
N E T: N E G OT I AT I N G
Figure 31
Figure 32
Figure 33
*
Quick Codes may not work with all handheld HART communicators.
C H
4
: X X X % L E L
C H
4
: X X X % L E L