WirelessHART Toxic & Combustible Gas Detector
IM_TCD60-01
www.ueonline.com/vanguard
29
Request bytes:
Bytes
Format
Description
None
Response byte:
Bytes
Format
Description
0-39
Latin-1
Unit Configuration String, (e.g., UEC100 SW 2.20 HW 1.21)
Command Specific Response Code:
Code
Class
Description
0
Success
No command specific errors
3.3.7 HART Command 132 Read Base Unit Configuration String
Request bytes:
Bytes
Format
Description
None
Response byte:
Bytes
Format
Description
0-39
Latin-1
Sensor Module Configuration String (e.g., H
2
S: 02031 08035278 02
MIPEX-2_25.6)
Command Specific Response Code:
Code
Class
Description
0
Success
No command specific errors
3.3.9 HART Command 138 Read Sensor Type String
Request bytes:
Bytes
Format
Description
0
Unsigned 8
Device Variable Code
Response bytes:
Bytes
Format
Description
0
Unsigned 8
Device Variable Code
1-16
ISO-Latin1
Variable Type String
Command-Specific Response Codes
Code
Class
Description
0
Success
No command specific errors
1
Error
Wrong Number of Data Bytes
2
Error
Invalid Selection
3.3.8 HART Command 133 Read Sensor Module Configuration String
Table 8
Table 9
Table 10