Page 26
DATE
LOCATION INFORMATION
User
Address 1
Address 2
City, State, Zip
System
STANDPIPE-PAC
™ UNIT SERIAL NUMBER
PRELIMINARY
YES
NO
Have all required on-site parties been notified that audible signals will be sounding?
If the control unit dialer is connected to telephone lines, has the party receiving signals been notified that
testing will take place?
Are all valves on the standpipe CLOSED?
Are all manual air release bleed valves CLOSED?
Has an Auxiliary Condensate Drain Device been properly installed?
Has 115 VAC power been connected, and is OFF?
STARTUP
YES
NO
Is the compressor disconnect switch OFF, and is the unit outlet lockable shutoff valve OPEN?
Has the battery been connected to the control unit?
Has 115 VAC power been turned ON?
Has the control unit RESET button been operated, and is the control unit AC POWER indicator ON?
Is the control unit ALARM indicator ON, and are the signal horn and horn/strobe operating?
Has the SILENCE switch been pressed once to acknowledge the alarm, and then pressed again for 2
seconds, turning the signals OFF?
Has the compressor disconnect switch been moved to ON, and is the needle on the pressure gauge
moving upward?
When the pressure gauge needle reaches approximately 18 PSIG, does the compressor automatically
shut off?
Is the control unit clear, with only the AC POWER indicator ON?
COMMISSIONING WORKSHEET AND CHECKLIST
STANDPIPE-PAC
™ SUPERVISORY SYSTEM
UFS-238B REVISION 1.00
– PAGE 1 OF 3