UNITED FIRE SYSTEMS
STANDPIPE-
PAC™ MODEL SSS-101
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 2
(15) A manual air release bleed valve for Fire Department use. This device is to be installed near the siamese
connection feeding the standpipe. A cap and chain is provided to protect the outlet. An instruction
nameplate is also provided. This nameplate is to be securely fastened near the valve.
(16) A remote weatherproof audible / amber visual device with weatherproof backbox and identification
nameplate. This device is required by Boston FD TCM3-51725. The installer must locate this device
immediately outside the location of the
STANDPIPE-
PAC™,
and wire the device in accordance with the
instructions in this manual.
(17) An auxiliary condensate drain device. This device permits manual draining of water in the piping near the
STANDPIPE-
PAC™
unit, to help prevent water entry into the unit and pipe blockage without removing all
air from the standpipe. (Figure 4)
Figure 1
–
STANDPIPE-
PAC™
Unit
(9)
SIGNAL HORN
(10)
JUNCTION BOX
FOR CONNECTION
OF 120 VAC
(12)
POWER DISCONNECT
SWITCH FOR
AIR COMPRESSOR
(4)
HIGH-LIMIT
PRESSURE SENSING
SWITCH
(13)
TEST / SERVICE
DEVICE
(3)
LOW-LIMIT
PRESSURE SENSING
SWITCH
AUTOMATIC CONTROL
SWITCH FOR
AIR COMPRESSOR
(1)
AIR COMPRESSOR
(8)
CONTROL UNIT
(BATTERY INSIDE)
OPERATING
INSTRUCTIONS
LABEL
(6)
CHECK VALVE
(7)
LOCKABLE
SHUTOFF VALVE
(11)
OUTLET FOR
PIPING CONNECTION
(5)
PRESSURE GAUGE
(2)
DESICCANT
AIR DRYER
(14)
SERIAL NUMBER
NAMEPLATE