background image

5

Chimney Connection

MASONRY CHIMNEY

The masonry chimney must comply with UL codes.  Before using an existing masonry chimney, clean the chimney and inspect the flue 

liner to be sure it is safe to use. Make repairs before attaching the heater. See Page 3, Item 5.  Look at Fig. 5. The connector pipe and 

fittings you will need to connect directly to a masonry chimney are shown.  If the connector pipe must go through a combustible wall before 

entering the masonry chimney, consult a qualified mason or chimney dealer. The installation must conform to local fire codes, and NFPA 

211.  Do not connect this heater into the same chimney flue as the fireplace or flue from another heater.  The chimney used for a heater 

must not be used to ventilate the cellar or basement. If there is a cleanout opening at the base of the chimney, close it tightly.

UL LISTED CHIMNEY

Carefully follow chimney manufacturer's instructions. Use only listed type HT 

per UL 103, 6-in diameter black or blued chimney connector, minimum 24 gauge 

steel. If your chimney starts at the ceiling (Fig. 7), you will need enough 6" pipe 

to reach the ceiling.

The top of the chimney must be at least 3 feet above the roof and be at least 

2 feet higher than any point of the roof within 10 feet. (Fig 7)

RULES FOR CONNECTOR PIPE INSTALLATION

1.  Crimped end of the pipe must be installed away from the heater. The 

pipe should be firmly attached to the collar top with 3 screws and sealed 

with furnace cement.

2.  Slope any horizontal pipe upward toward the chimney at least 1/4 " inch 

for each foot of horizontal run.

3.  You must have at least 18" inches clearance between any horizontal 

piping and the ceiling. (Fig. 3)

4. 

The pipe cannot extend into the chimney flue.(Fig. 5)

5.  Seal each connector pipe joint with furnace cement. Also seal the pipe 

at the chimney.

6.  Use 3 sheet metal screws at each joint to make the piping rigid.

7.  It is recommended that no more than two (2) 90 degree bends be used 

in the stove pipe installation as more than two (2) may decrease the 

amount of draw and possibly cause smoke spillage.

NOTE:  The chimney connector shall not pass through an attic, 

roof space, floor, ceiling, or similar concealed space.  Where 

passage through a wall or partition of combustible construction is 

desired, the installation must conform with NFPA 211.

Operation of the Stove

1.  Fully open slide draft on ash door and keep spin damper on feed door 

closed.

2.  Burn coal only. Use wood for coal ignition purposes only. Build six (6) 

small fires upon initial firing.  Light wood using paper, twigs, etc.

3. 

After the fire has been started and is burning satisfactorily, close slide 

draft almost all the way.

4.  Open/adjust spin draft on feed door to allow additional air into the stove 

(on top of the fire).  This will allow a more efficient burn cycle.

5. 

Never build extremely large fires in this type stove as damage to the 

stove or smoking may result.

6. 

DO NOT touch the stove after firing

7. 

Never over fire this stove by building excessively hot fires as a house/

building fire may result.

8.  Inspect stove pipe every 90 days.  Replace immediately if stove pipe is 

rusting or leaking smoke into the room.

9.  This is a cast iron stove.  It does not have welded seams.  From time to 

time you may have to "tune-up" the stove  by refilling and/or replacing 

the stove cement or mortar along the seams.

10. 

If stove begins to glow or turn red, you are over firing.

FIG. 6

FLUE CONNECTION-NON-COMBUSTIBLE WALL

FLOOR PROTECTOR

PIPE

BAROMETRIC

DRAFT REGULATOR

ELBOW

PIPE

COLLAR

THIMBLE

NON-COMBUSTIBLE WALL

FIG. 7

CHIMNEY CAP MANDATORY

3 FT. MIN.

2 FT. MIN

10 FT.

PIPE  REDUCER

11 FT. MINIMUM

PIPE

FLOOR PROTECTOR

BAROMETRIC

DRAFT REGULATOR

NON-COMBUSTIBLE

CONSTRUCTION IN

ACCORDANCE WITH

NFPA 211

FLOOR

PROTECTOR

(60"

 MIN

.)

FIG. 4

FLOOR

PROTECTOR

10-1/4

36"

18"

FIGURE 2

FIGURE 3

42"

36"

39-1/2"

14-1/2"

FLOOR

PROTECTOR

NON- COMBUSTIBLE

CONSTRUCTION IN

ACCORDANCE WITH

NFPA 211

DASHED LINES

SHOW STRAIGHT

OUT CHIMNEY

CONNECTOR

36"

54"

36"

Summary of Contents for 1869 Caboose Potbelly

Page 1: ...Park Road P O Box 151 South Pittsburg TN 37380 423 837 2100 851499D 1501G Owners Manual 1869 Caboose Potbelly COAL ONLY STOVE CAUTION Read All Instructions Carefully Before Starting The Installation o...

Page 2: ...screw Connect bal ance of stove pipe into a class A chimney Specifications Height Overall 36 Width 21 6 Depth 19 5 Firebox Capacity 40 lbs Firebox Depth 10 Flue Size 6 Door Opening 8 x 10 Material 100...

Page 3: ...ied inspector Your insurance company may be able to recommend a qualified inspector 6 Creosote or soot may build up in the chimney connector and chimney and can cause a house building fire Inspect the...

Page 4: ...otector accordingly and carefully place the stoveinyourselectedlocation Installstovepipe elbows and thimble as necessary utilizing either a recently cleanedandinspectedmasonrychimneyoraUL103HT Listed...

Page 5: ...gid 7 It is recommended that no more than two 2 90 degree bends be used in the stove pipe installation as more than two 2 may decrease the amount of draw and possibly cause smoke spillage NOTE The chi...

Page 6: ...baking soda or cool ashes on top of the fire in the firebox CAUTION A chimney fire may cause ignition of wall studs or rafters which you thought were a safe distance from the chimney If you have a chi...

Page 7: ...4 8 89986 Ash Door 1 IN ORDER TO MAINTAIN WARRANTY COMPONENTS MUST BE REPLACED USING ORIGINAL MANUFACTURERS PARTS PURCHASED THROUGH YOUR DEALER OR DIRECTLY FROM THE APPLIANCE MANUFACTURER USE OF THIRD...

Page 8: ...th the highest portion of your fire bed in the center of the firebox The first flames will be long and generally orange or yellow and produce quite a bit of smoke As the gases burn off the flames beco...

Page 9: ...ave the spin damper or thermostat open for a few minutes until the volatile gases have burned off It is not necessary to shake down the ashes each time you refuel the furnace Experience will be your b...

Page 10: ...implied warranty 2 Should the heater be replaced by United States Stove Company free of charge all further warranty obligations are thereby met 3 Parts and or service replacements made under the terms...

Page 11: ...07 Date _____________________ Engineer Name ________________________________ License No ____________________________________ Company _____________________________________ Telephone No _______________...

Page 12: ...PLATE ATTACHED TO THE BACK OF THE HEATER WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING INFORMATION AS SHOWN IN THIS LIST 1 The PART NUMBER ___________________________________ 2 The PART DESCRIP...

Reviews: