FLOOR PROTECTOR
This heater must have a non-combustible floor protector
with an R-Value of at least 1.4 installed beneath it if the
floor is constructed of combustible material. If a floor pad
is used, it should be UL listed or equal. The floor protector
should be large enough to extend under the stove and
beyond each side as indicated. If there is a horizontal run
of flue pipe, there needs to be floor protection under it
that extends two inches beyond either side of the pipe.
REAR
FRONT
SIDE
SIDE
Front
26” (661 mm)
Sides
8” (204 mm)
Rear
*2” (51 mm)
*Canadian Installations require
8” (204 mm)
CLEARANCES TO COMBUSTIBLES
It is of utmost importance that the clearances to
combustible materials be strictly adhered to during
installation of the stove.
• Floor to ceiling height must be at least 7’ (2.13m) in all
cases.
• Do not place any combustible material within 4’ (1.2m)
of the front of the unit.
• The clearance between the flue pipe and a wall are valid
only for vertical walls and for vertical flue pipe.
• If there is a horizontal run of flue pipe there must be
at lease 18” of clearance between the pipe and the
ceiling. There also has to be floor protection under the
horizontal run that extends 2” beyond each side of the
flue pipe.
• The chimney connector must not pass through an attic
or roof space, closet or similar concealed space, a floor,
or a ceiling.
• For Canadian installations, where passage through a
wall, or partition of combustible construction is desired,
the installation must conform to CAN/CSA-B365.
• A flue pipe crossing a combustible wall must have a
minimum clearance of 18” (457.2mm).
• To reduce flue clearances from combustible materials,
contact your local safety department.
D
B
A
C
E
F
E
Single Wall Pipe (Double Wall Pipe)
Key
in
mm
A
10 (10)
254 (254)
B
19 (19)
483 (483)
C
13 (13)
331 (331)
D
30 (29)
762 (737)
E
10 (10)
254 (254)
F
20 (20)
508 (508)
OUTSIDE COMBUSTION AIR
Your wood stove is approved to be installed with an
outside air intake (4FAK) which is necessary for a mobile
home. This type of installation is also required in air tight
houses and houses with negative pressure problems.
You can purchase this option through your heater dealer.
Make sure to specify the part number mentioned in this
booklet. Installation instructions are supplied with the air
intake kit. Outside combustion air may be required if:
INSTALLATION
FOR CUSTOMER SERVICE CALL: 800-750-2723 EXT 5050
6