background image

USSC

7

GUIDELINES FOR EXHAUST VENTING SYSTEMS DESIGN


A UL listed 3” or 4” type “PL”  pellet vent exhaust  system must be used for installation and attached to the pipe connector

provided on the back of the stove.  Use a 3” to 4” adapter for 4” pipe.  A cap must be used at the termination of type “L”

vent chimneys.  4” PL is required for elevations above 2,500 feet above sea level.
Do not terminate vent in any enclosed or semi-enclosed area, such as; carports, garage, attic, crawl space, under a

sundeck or porch, narrow walkway or close area, or any location that can build up a concentration of fumes such as a

stairwell, covered breezeway etc.
Vent surfaces can get hot enough to cause burns if touched by children.  Noncombustible shielding or guards may be

required.
Do not install a flue damper in the exhaust vent of this unit.
Termination must exhaust above air inlet elevation.  Installation MUST include three (3) vertical feet of pellet vent pipe.

This will create some natural draft to prevent the possibility of smoke or odor during appliance shutdown and  to keep

exhaust from causing a nuisance or hazard from exposing people or shrubs to high temperatures.  Do not connect

this unit to a chimney flue serving another appliance.  Do not connect directly to a masonry chimney.
The installation must include a cleanout tee to enable collection of fly ash and to permit periodic cleaning of the exhaust

system.  90° elbows accumulate fly ash and soot thereby reducing exhaust flow and performance of the stove.  Each

elbow or tee reduces draft potential by 30% to 50%.  

Use no more than 180 degrees of elbows (two 90-degree elbows,

or two 45-degree and one 90-degree elbow, etc.) to maintain adequate draft.  Clean-out tees and elbows should not

be mounted directly to the rear of the stove.

Total length of horizontal vent must not exceed 48”(4ft.)/1,200mm.  

The maximum recommended vertical venting

height is 12-feet for 3-inch type “PL” vent.

  All joints in the vent system must be fastened by at least 3 screws, and all

joints must be sealed with RTV silicone sealer to be airtight.
The area where the vent pipe penetrates to the exterior of the home must be sealed with silicone or other means to

maintain the vapor barrier between the exterior and the interior of the home.

It is recommended that only an authorized installer install your pellet/corn stove, preferably an NFI certified

specialist.  The following installation guidelines must be followed to ensure conformity with both the safety listing of this

stove and to local building codes.

INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER.

NOTE:  These are guidelines only.  Proper venting is accomplished by design and common sense.  In most

installations 3 inch diameter venting is adequate.  If it does not vent properly you will have to change it to

4 inches.  You should not exceed 4 inch diameter venting.

DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM

VENT TERMINATION CLEARANCES:

A) Min. 4-ft clearance below or beside any door or window

that opens.
B) Min. 1-ft clearance above any door or window that

opens.
C) Min. 3-ft clearance form any adjacent building.
D) Min. 7-ft clearance from any grade when adjacent to

public walkways.
E) Min. 2-ft clearance above any grass, plants, or other

combustible materials.
F) Min. 3-ft clearance from an forced air intake of any

appliance.
G) Min. 2-ft clearance below eves or overhang.
H) Min. 1-ft clearance horizontally from combustible wall.

Must be a minimum of 36-inches above the roof

and 24-inches above the highest point or the roof

within 10-feet.

Summary of Contents for American Harvest 6039

Page 1: ...icials about restrictions and installation requirements peculiar to your area Do Not Plug this appliance into an electrical outlet before reading and understanding all operations and always unplug the...

Page 2: ...NFI Certified Specialist You ve purchased one of America s Finest Multifuel Burning Stoves By heating with fuels such as corn and pellets you re helping CONSERVE AMERICA S ENERGY CONGRATULATIONS BTU...

Page 3: ...er with the bottom flanges turned to the outside as shown Use the four 4 10 Tek Screws provided 5 Assemble the legs using the eight 8 Bolts as shown 6 After all bolts and screws have been tightened pr...

Page 4: ...his product requires simple periodic maintenance for proper operation and long life of the stove Read and follow the maintenance schedule closely DISCONNECT THE POWER CORD BEFORE SERVICING THIS STOVE...

Page 5: ...re consistently with a small to midsize kernel corn If the kernel size of the corn varies greatly or if you switch sources frequently you will get a less consistent burn Therefore purchasing corn from...

Page 6: ...o Top Edge of Unit 6 in 152mm B Sidewall to Flue 5 in 127mm C Backwall to Flue 3 in 75mm D Backwall to Unit 9 in 228mm E Right Sidewall to Top Edge of Unit 2 in 50mm CORNER F Adjacent Wall to Flue 3 i...

Page 7: ...adequate draft Clean out tees and elbows should not be mounted directly to the rear of the stove Total length of horizontal vent must not exceed 48 4ft 1 200mm The maximum recommended vertical ventin...

Page 8: ...o do so could result in a burn back during high winds blowing directly up the air inlet during a simulta neous power failure see diagram above Blockage excessive length or extra bends in the air intak...

Page 9: ...end of the exhaust pipe must extend a minimum of 12 inches from the outside of the building Rodent screen cannot be less than 3 8 opening mesh If installing with combustion air from outside cut a sepa...

Page 10: ...cutting hole in wall 3 Minimum Vertical Pipe Dimensional tolerance 0 25 12 1 8 11 3 4 10 1 16 EXHAUST OULET 3 DIA COMBUSTION AIR INTAKE 1 7 8 DIA 10 1 16 11 5 8 12 EXHAUST OUTLET 3 DIA COMBUSTION AIR...

Page 11: ...CAL PIPE INSTALLATION WITH TERMINATION CAP The Hearth Pad is not required under the unit if the floor is noncombustible but is required 6 inches 152mm beyond the front of the unit and 6 inches 152mm b...

Page 12: ...gasket WARNING Do not operate unit with broken glass Do not substitute original factory glass You must use only factory authorized glass Do not slam door shut Do not strike glass Do not use abrasive...

Page 13: ...d have the starting fuel completely burning in the firepot as the agitator rotates NOTE If the starting fuel is not burning hot enough you may see the fire begin to go out as new fuel is being added I...

Page 14: ...ontent of the corn If this is not cleaned out it could cause the fuel stirrer to jam USSC highly recommends an additive see Fuel Additive Pg 15 be added to your corn to eliminate these clinkers Contac...

Page 15: ...nd the burn box as it may damage the insulation Scrape the fly ash from the clean out chambers toward the front of the burn chamber Remove the fly ash from the burn chamber and replace the clean outs...

Page 16: ...ition or the operating temperature falls below 90 degrees At such time the AMERICAN HARVEST will default to the Automatic Shut Down Adjusting the Air Fuel Mixture The two adjustments necessary for pro...

Page 17: ...rolboardflashing NOTE HILIMIT errors are usually the result of operat ing at the highest heat setting for long periods of time room fan failure or loose wire connection Continues until the operating t...

Page 18: ...burns out of fuel Hopper empty refill Auger jams Remove auger and clean Auger jams can be a prob lem if poor quality fuel is used Or excessive fines sawdust corn cobs or husk are found in hopper Auge...

Page 19: ...USSC 19 WIRING DIAGRAM LIMIT...

Page 20: ...20 USSC REPAIR PARTS DIAGRAM 6039 42 41 4 7 6 51 52 53 50 2 47 22 25 24 23 13 17 18 19 21 20 34 36 37 38 39 40 45 43 44 30 32 26 27 54 16 15 12 55 14 28 29 35 5 3 11 8 9 10 8 48 46 1 31 49 33...

Page 21: ...st Blower 1 25 80473 Blower Exhaust 1 26 80456 Auger Motor 1 27 83511 Washer Rubber 1 28 83533 Roll Pin 1 8 dia X 7 8 1 29 891136 Coupling Shaft 1 30 88106 Gasket Distribution Blower 1 31 80472 Blower...

Page 22: ...g Parts Bag 1 Key Part No Descritption Qty 1 25491 Feed Door 1 2 25492 Handle Door 1 3 83506 Roll Pin 3 8 x 1 1 4 1 4 88112 Gasket 1 2 Sq Rope 5 ft 5 88087 Gasket Glass 1 x 3 16 4 ft 6 891131 Glass Ce...

Page 23: ...USSC 23 Notes...

Page 24: ...GIVE THE FULL MODEL NUMBER WHICH IS ON THE NAMEPLATE ATTACHED TO THE HEATER WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING INFORMATION AS SHOWN IN THIS LIST 1 THE PART NUMBER 2 THE PART DESCRIP...

Reviews: