INSTALLATION

FLOOR PROTECTOR

This heater must have a non-combustible floor protector 

(ember protection) installed beneath it if the floor is of 

combustible material. If a floor pad is used, it should 

be UL listed or equal. The floor pad or non-combustible 

surface should be large enough to extend under the stove 

and beyond each side as indicated. If there is a horizontal 

run of flue pipe, there needs to be floor protection under 

it that extends two inches beyond either side of the pipe.

REAR

FRONT

SIDE

SIDE

Front

*16” (407 mm)

Sides

8” (204 mm)

Rear

2” (51 mm)

*Canadian Installations require 

18” (457 mm) 

CLEARANCES TO COMBUSTIBLES

It is of utmost importance that the clearances to 

combustible materials be strictly adhered to during 

installation of the stove.
•  Do not place any combustible material within 4’ (1.2m) 

of the front of the unit.

•  The clearance between the flue pipe and a wall are valid 

only for vertical walls and for vertical flue pipe.

•  The chimney connector must not pass through an attic 

or roof space, closet or similar concealed space, a floor, 

or a ceiling.

•  For Canadian installations, where passage through a 

wall, or partition of combustible construction is desired, 

the installation must conform to CAN/CSA-B365.

•  A flue pipe crossing a combustible wall must have a 

minimum clearance of 18” (457.2 mm).

•  To reduce flue clearances from combustible materials, 

contact your local safety department.

•  Floor to ceiling height must be at least 7’ (2.13m).

D

B

A

C

E

F

E

Key

in

mm

A

17

432

B

21

534

C

20

508

D

29

737

E

14

356

F

22

559

OUTSIDE COMBUSTION AIR

Your wood stove is approved to be installed with an 

outside air intake (4FAK) which is necessary for a mobile 

home. This type of installation is also required in air tight 

houses and houses with negative pressure problems. 

You can purchase this option through your heater dealer. 

Make sure to specify the part number mentioned in this 

booklet. Installation instructions are supplied with the air 

intake kit. Outside combustion air may be required if:
1.  Your stove does not draw steadily, smoke roll-out 

occurs, wood burns poorly, or back-drafts occur 

whether or not there is combustion present.

2.  Existing fuel-fired equipment in the house, such as 

fireplaces or other heating appliances, smell, do 

not operate properly, suffer smoke roll-out when 

opened, or back-drafts occur whether or not there is 

combustion present.

3.  Opening a window slightly on a calm (windless) day 

alleviates any of the above symptoms.

FOR CUSTOMER SERVICE CALL: 800-750-2723 EXT 5050

Summary of Contents for US1100E-BL

Page 1: ...e shift compromises during the installation of this heater Contact local building or fire officials about permits restrictions and installation requirements in your area NEVER OPERATE THIS PRODUCT WHI...

Page 2: ...ght US1100E Leg 21 3 542 mm 24 5 623 mm 30 9 785 mm US1100E Pedestal 21 1 536 mm 22 5 572 mm 31 7 806 mm Combustion Chamber Width x Depth 18 25 x 11 5 464 mm X 293 mm Firebox Volume Cubic Feet 1 31 cu...

Page 3: ..._________________________________________ If no Date of inspection of the existing chimney system ___________________________________________________________ COMMISSIONING Confirm Hearth Pad Installat...

Page 4: ...BLOWER ASSEMBLY The blower assembly must be disconnected from the source of electrical supply before attempting the installation The blower assembly is intended for use only with a stove that is marke...

Page 5: ...SOURCE OF FRESH AIR INTO THE ROOM OR SPACE HEATED SHALL BE PROVIDED WHEN REQUIRED US Stove highly recommends your stove be installed by a qualified NFI US or WETT Canada technician To find the nearest...

Page 6: ...on of combustible construction is desired the installation must conform to CAN CSA B365 A flue pipe crossing a combustible wall must have a minimum clearance of 18 457 2 mm To reduce flue clearances f...

Page 7: ...ed for your specific flooring 3 Install one bracket per leg or consult your local authority having jurisdiction to determine how many points of attachment are required In addition to the previously de...

Page 8: ...ctor joints An uncontrollable burn or excessive temperature indicates an excessive draft CHIMNEY Your wood stove may be hooked up with a 6 factory built or masonry chimney If you are using a factory b...

Page 9: ...ction Association NFPA by having it inspected by a professional Make sure there are no cracks loose mortar or other signs of deterioration and blockage Be sure to the chimney cleaned before the stove...

Page 10: ...nd cover its opening with a 24 gage minimum sheet metal support Maintain the 6 152 4 mm space There should also be a support sized to fit and hold the metal chimney connector See that the supports are...

Page 11: ...ific varieties have better energy yields than others Higher efficiencies and lower emissions generally result when burning air dried seasoned hardwoods as compared to softwoods or too green or freshly...

Page 12: ...ced in the stove your wood is correctly dried If ignition takes longer your wood is damp If your wood hisses and water or vapor escapes at the ends of the piece your wood is soaked or freshly cut gree...

Page 13: ...f wood during start up and a high burn rate to increase the stove temperature 3 5 4 lbs Pull the air control out fully in the HI position Light the newspaper and leave the door slightly open for about...

Page 14: ...rly and has a high wood moisture content will produce excess visible smoke and burn poorly AIR TUBES The air tubes assembled in this unit are designed to provide an accurate mix of secondary air to en...

Page 15: ...Leave the air control fully open for about 5 min every time you reload the stove to bring it back to proper operating temperatures The secondary combustion can only take place if the firebox is hot e...

Page 16: ...r uses a 1 diameter rope gasket It is recommended that you change the door gasket which makes your stove door air tight once a year in order to ensure good control over the combustion maximum efficien...

Page 17: ...D TAILS TECHNIQUES 120VAC 60 Hz CA 0 55AMP BLACK NOIR BLACK NOIR NOTICE DO NOT ALLOW THE POWER CORD TO TOUCH HOT SURFACES KEEP THE POWER CORD AT LEAST 12 30 5CM FROM THE STOVE OR PIPE SURFACES DANGER...

Page 18: ...E BL 4 IN ORDER TO MAINTAIN WARRANTY COMPONENTS MUST BE REPLACED USING ORIGINAL MANUFACTURERS PARTS PURCHASED THROUGH YOUR DEALER OR DIRECTLY FROM THE APPLIANCE MANUFACTURER USE OF THIRD PARTY COMPONE...

Page 19: ...ption Qty 1 893241 US Complete Door Handle 1 2 40887 Medium Arched Door 1 3 88324 1 Rope Gasket 1 4 893159 Clear Glass 1 5 29229 Glass Retainer Sides 2 6 29227 Glass Retainer Top 1 7 29230 Gasket Clam...

Page 20: ...____________________ Engineer Name _____________________________________ License No _________________________________________ Company ___________________________________________ Telephone No _________...

Page 21: ...____________________ Service de 07 Date ______________________ Nom de l ing nieur _________________________________ N de licence ______________________________________ Compagnie ______________________...

Page 22: ...secondaire 1 6 891414 Demi brique r fractaire 4 7 89066 Brique r fractaire 4 1 2 X 9 4 8 891095 Brique r fractaire 6 X 8 1 4 3 9 23783 Brique r fractaire 1 1 4 X 2 9 16 X 9 4 10 86903 Tube secondaire...

Page 23: ...8 Soudure d amortisseur 1 8 86709 Tige amortisseur 1 9 891987 Bouton en plastique 1 10 610918 Panneau d acc s US1100E BP 1 11 610944 Soudure de logement en cendrier US1100E BL 1 12 40566 Pied en fonte...

Page 24: ...R BLACK NOIR AVIS NE PERMETTEZ PAS AU CORDON D ALIMENTATION DE TOUCHER LES SURFACES CHAUDES GARDER LE CORDON D ALIMENTATION AU MOINS 12 po 30 5CM DES SURFACES DU PO LE OU DU TUYAU DANGER RISQUE D LECT...

Page 25: ...cet appareil utilise un joint de corde de 1 po de diam tre Il est recommand de changer le joint de porte qui rend la porte de votre po le tanche l air une fois par an afin d assurer un bon contr le d...

Page 26: ...contr le d air compl tement ouvert pendant environ 5 min chaque fois que vous rechargez le po le pour le ramener des temp ratures de fonctionnement appropri es La combustion secondaire ne peut avoir...

Page 27: ...air assembl s dans cette unit sont con us pour offrir un m lange pr cis d air secondaire et assurer une plus grande efficacit Tout dommage ou d t rioration de ces conduits peuvent r duire l efficacit...

Page 28: ...et un taux de combustion lev pour augmenter la temp rature du po le 3 5 4 lbs Tirez compl tement la commande d air en position HI Allumez le journal et laissez la porte l g rement ouverte pendant envi...

Page 29: ...xtr mit s de la pi ce votre bois est tremp ou fra chement coup vert N utilisez pas ce bois dans votre po le De grandes quantit s de cr osote pourraient se d poser dans votre chemin e cr ant des condit...

Page 30: ...ts nerg tiques que d autres Des rendements plus lev s et des missions plus faibles r sultent g n ralement de la combustion de bois durs s ch s l air par rapport aux r sineux ou aux feuillus trop verts...

Page 31: ...ord de chemin e m tallique V rifiez que les supports soient fix s de fa on s re aux surfaces de la paroi sur tous les c t s Assurez vous que les l ments de fixation utilis s pour maintenir le raccord...

Page 32: ...as de fissures de mortiers perdus ou d autres signes de d t rioration et de blocage Faites nettoyer la chemin e avant d installer et de faire fonctionner le po le Lors du raccordement du po le travers...

Page 33: ...nad quat causera des fuites de fum e par l appareil dans la pi ce s infiltrant par l appareil et les joints du conduit de raccordement Un br lage incontr lable ou une temp rature excessive indique un...

Page 34: ...n de nivellement ins r dans le pied 2 Une fois l appareil nivel positionnez le support et fixez le au sol l aide du mat riel appropri n cessaire pour votre rev tement de sol sp cifique 3 Installez un...

Page 35: ...lations canadiennes o le passage travers un mur ou une cloison de construction combustible est souhait l installation doit tre conforme la norme CAN CSA B365 Un conduit de fum e traversant un mur comb...

Page 36: ...SI N CESSAIRE US Stove recommande fortement que votre po le soit install par un technicien qualifi NFI US ou WETT Canada Pour trouver l installateur qualifi le plus proche acc dez https nficertified o...

Page 37: ...urce d alimentation lectrique avant de tenter l installation L ensemble sou eur est destin tre utilis uniquement avec un po le qui est marqu pour indiquer une telle utilisation Ne faites pas passer le...

Page 38: ...ion du syst me de chemin e existant ____________________________________________________________________ MISE EN SERVICE Confirmer l installation du tapis de foyer conform ment aux instructions d inst...

Page 39: ...po 785 mm US1100E pi destal 21 1 po 536 mm 22 5 po 572 mm 31 7 po 806 mm Chambre de combustion Largeur x profondeur 18 25 po X 11 5 po 464 mm X 293 mm Volume Firebox Pieds cubes 1 31 pieds cubes Ouve...

Page 40: ...S UTILISER CE PRODUIT SANS SURVEILLANCE MISE EN GARDE Veuillez lire l int gralit de ce manuel avant d installer ou d utiliser votre nouveau radiateur Le non respect des instructions peut entra ner des...

Reviews: