background image

14

4.3 - Short-circuit stability current for all units

Short-circuit stability current for all units using the TN 

system (earthing system type): 

50 kA (conditional system 

short-circuit current Icc/Icf at the unit connection point as 
rms value).

All units are equipped with a main disconnect switch located 
in the control box immediately downstream of the unit 
power connection point. 

4.4 - 

Compressor electrical data

Compressor nominal voltage/frequency: 380V/60Hz

Compressor

I Nom 

(A)*

I Max 

(A)**

MHA 

(A)

LRDA 

(A)

Cosine phi 

nom.*

Cosine 

phi max.**

06TUX483

178

250

279

1537

0.88

0.92

06TUX554

205

315

340

1537

0.89

0.92

06TVX680

245

362

390

2179

0.89

0.92

06TVX753

260

400

430

2179

0.89

0.92

*  Value at standard Eurovent conditions: evaporator entering/leaving water tempera-

ture 12°C/7°C, condenser entering/leaving water temperature 30°C/35°C.

**  Value at maximum capacity and nominal voltage.

Legend

MHA 

-  Maximum compressor operating current, limited by the unit (current given 

for maximum capacity at 342 V)

LRDA

 - Locked rotor current for delta connection

4.5 - Compressor usage

30XW-V/30XWHV

580 630 810 880 1150 1280 1470 1570 1710

06TUX483

A

-

-

-

AB

-

-

-

-

06TUX554

-

A

-

-

-

AB

B

-

-

06TVX680

-

-

A

-

-

-

A

AB

-

06TVX753

-

-

-

A

-

-

-

-

AB

Notes, electrical data and operating conditions - 30XW-V/30XWHV units

•  The control box includes the following standard features:

 

-  One main disconnect switch per circuit

 

-  Anti-short cycle protection devices

 

-  Control devices

• 

Field connections:

 

All connections to the system and the electrical installations must be in full 

accordance with all applicable codes.

•  The Carrier 30XW-V/30XWHV units are designed and built to ensure conformance 

with local codes. The recommendations of European standard EN 60204-1 

(corresponds to IEC 60204-1) (machine safety - electrical machine components 

- part 1: general regulations) are specifically taken into account, when designing 

the electrical equipment*.

•  Annex B of EN 60204 1 describes the electrical characteristics used for the 

operation of the machines. The ones described below apply to 30XW-V/30XWHV 

units and complement other information in this document:

1.  Physical environment**: Environment as classified in EN 60721 (corresponds 

to IEC 60721):

 

-  indoor installation

 

-  ambient temperature range: minimum tempe5°C to +42°C, class AA4

 

-  altitude: lower than or equal to 2000 m

 

-  presence of water: class AD2 (possibility of water droplets)

 

-  presence of hard solids, class 4S2 (no significant dust present)

 

-  presence of corrosive and polluting substances, class 4C2 (negligible)

2.  Power supply frequency variation: ± 2 Hz.

3.  The neutral (N) line must not be connected directly to the unit (if necessary use 

a transformer).

4.  Overcurrent protection of the power supply conductors is not provided with the 

unit.

5.  The factory installed disconnect switch(es)/circuit breaker(s) is (are) of a type 

suitable for power interruption in accordance with EN 60947-3 (corresponds to 

IEC 60947-3).

6.  The units are designed for connection to TN networks (IEC 60364). In IT networks 

the use of noise filters integrated into the frequency variator(s) make machine 

use unsuitable. In addition, the short-circuit holding current characteristics have 

been modified. Provide a local earth, consult competent local organisations to 

complete the electrical installation.

7.  Electromagnetic environment: classification of the electromagnetic environment 

is described in standard EN 61800-3 (corresponds to IEC 61800-3):

 

Immunity to external interference defined by the second environment***

 

Interference emission as defined in category C3

•  Due to the harmonic currents the integrated frequency variator in the 30XW-V/ 

30XWHV units is a source of interference. An analysis may be required to verify 

if these interferences exceed the compatibility limits of the other devices 

connected to the same power supply network. The compatibility levels inside 

an electrical installation, that must be met at the in-plant coupling point (IPC) to 

which other loads are connected are described in standard 61000-2-4. 

 

Two characteristics are required for this analysis:

-  The short-circuit ratio (Rsce) of the installation calculated at the in-plant 

coupling point (IPC).

-  The total harmonic current distortion rate (THDI), calculated for the machine at 

maximum capacity.

•  Derived currents: If protection by monitoring the leakage currents is necessary 

to ensure the safety of the installation, the presence of derived currents 

introduced by the use of frequency variators in the unit must be considered. In 

particular the reinforced immunity protection types and a control value not lower 

than 150 mA are recommended to control differential protection devices.

 

NOTE: If particular aspects of an actual installation do not conform to 

the conditions described above, or if there are other conditions which 

should be considered, always contact your local Carrier representative.

*  Generally the recommendations of IEC 60364 are accepted as compliance with 

the requirements of the installation directives. Conformance with EN 60204-1 

is the best means of ensuring compliance with the Machinery Directive.

**  The required protection level for this class is IP21B or IPX1B (according to 

reference document IEC 60529). All 30XW-V/30XWHV have IP23 units fulfil this 

protection condition.

***  Example of installations of the second environment: industrial zones, technical 

locations supplied from a dedicated transformer.

†  Category C3 is suitable for use in an industrial environment and is not designed 

for use in a public low-voltage system that supplies residential locations. As an 

option, conformity with category C2 permits this type of installation.

Summary of Contents for Carrier Touchpilot 30XW-V

Page 1: ...MAINTENANCE INSTRUCTIONS Variable Speed Water Cooled Liquid Chillers Variable Speed Water to Water Heat Pumps 30XW V 30XWHV Nominal cooling capacity 587 1741 kW Nominal heating capacity 648 1932 kW 5...

Page 2: ...wiring 16 5 7 24 and 230 V power reserve for the user 16 6 APPLICATION DATA 16 6 1 Operating limits 16 6 2 Condenser side installation recommendation 16 6 3 Minimum chilled water flow 17 6 4 Maximum c...

Page 3: ...lve 22 9 6 Pressure vessels 22 9 7 High pressure safety switch 23 9 8 Electronic expansion valve EXV 23 9 9 Moisture indicator 23 9 10 Filter drier 23 9 11 Sensors 23 9 12 Frequency variator 23 10 OPT...

Page 4: ...the right place and direction on the unit The units can also be lifted with slings using only the designated lifting points marked on the unit Use slings or lifting beams with the correct capacity an...

Page 5: ...and may cause heart irregularities unconsciousness or death Vapour is heavier than air and reduces the amount of oxygen available for breathing These products cause eye and skin irritation Decomposit...

Page 6: ...witch it is necessary to recover the refrigerant charge these pressure switches are not installed on automatic valves Schraeder type If any maintenance operations are carried out on the unit lock the...

Page 7: ...These regulations permitting condi tioning and recovery of halogenated hydrocarbons under optimum quality conditions for the products and optimum safety conditions for people property and the environ...

Page 8: ...t to repair or recondition any safety devices when corrosion or build up of foreign material rust dirt scale etc is found within the valve body or mechanism If necessary replace the device Do not inst...

Page 9: ...on an even surface maximum tolerance is 5 mm in both axes there is adequate space above the unit for air flow and to ensure access to the components the number of support points is adequate and that...

Page 10: ...ng an installation consult the certified dimensional drawings supplied with the unit or available on request For the positioning of the fixing points weight distribution and centre of gravity coordina...

Page 11: ...re of gravity coordinates refer to the dimensional drawings Condenser Evaporator Dimensions in mm A B C D E F 30XW V 30XWHV 1150 1997 1514 1164 4730 219 1 219 1 1280 1997 1514 1164 4730 219 1 219 1 14...

Page 12: ...tonnes 186 186 257 250 172 172 172 164 157 Capacity control Touch Pilot inverter driven compressor electronic expansion valve EXV Minimum capacity 20 20 20 20 10 10 10 10 10 Evaporator Multi pipe floo...

Page 13: ...380 421 Circuit B A 270 330 330 380 421 With option 81 A 540 660 710 760 842 Maximum power input with option 150B Circuit A kW 141 173 199 221 141 173 199 199 221 Circuit B kW 141 173 173 199 221 Wit...

Page 14: ...with the unit 5 The factory installed disconnect switch es circuit breaker s is are of a type suitable for power interruption in accordance with EN 60947 3 corresponds to IEC 60947 3 6 The units are d...

Page 15: ...l electricity supplier at once and ensure that the unit is not switched on until corrective measures have been taken 5 2 Voltage phase imbalance 100 x max deviation from average voltage Average voltag...

Page 16: ...ort Evaporator pump control signal Condenser pump control signal This does not control condenser pump operation for this function add option 156 and flow switch Heating cooling change over Available a...

Page 17: ...ondenser water flow rates are shown in the table in chapter 6 7 Evaporator and condenser water flow rates If the system flow is higher than the maximum unit flow rate select the option with one pass l...

Page 18: ...ecessary to add a buffer water tank to the circuit in order to achieve the required volume The tank must itself be internally baffled in order to ensure proper mixing of the liquid water or brine Refe...

Page 19: ...fewest elbows and horizontal pipe runs at different levels Below the main points to be checked for the connection Follow the water inlet and outlet connection direction shown on the unit Install manu...

Page 20: ...es destabilisation of copper hydroxides and enlargement of particles Electric conductivity 10 600 S cm pH Ideal case pH neutral at 20 25 C 7 pH 8 7 2 Water connections The water connections are Victau...

Page 21: ...slave units Water inlet Water outlet Water pumps for each unit included as standard for units with hydronic module Additional sensors for leaving water control to be connected to channel 1 of the slav...

Page 22: ...signed for prolonged storage of 15 years under nitrogen charge with a temperature difference of 20 K per day 452000 cycles start ups with a maximum difference of 6 K between two neighbouring points in...

Page 23: ...re switches with manual reset called PZH former DBK are backed up by high pressure switches that require resetting with a tool The high pressure switches that require resetting with a tool are called...

Page 24: ...s the unit by communication bus to a building management system 580 1710 LON gateway 148D Two directional communication board complying with Lon Talk protocol Connects the unit by communication bus to...

Page 25: ...of the connections at the compressor terminals requires special precautions Please refer to the chapter below 11 STANDARD MAINTENANCE Air conditioning equipment must be maintained by profes sional tec...

Page 26: ...is included with the compressor This low pressure switch should be temporarily installed as a hard safety on the high pressure part of the compressor The purpose of this switch is to protect the compr...

Page 27: ...e the fan if a replace fan alert warning is displayed in the alarm list For any other alarm or problem at the frequency variator contact the Carrier service department The frequency variators in the 3...

Page 28: ...properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All chilled water valves are open All chilled water piping is...

Page 29: ...nominal kW capacity for air conditioning 6 5 litres nominal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protec...

Page 30: ...30...

Page 31: ...31...

Page 32: ...es order No 13474 76 05 2013 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union www eurovent cer...

Reviews: