17 

all possible. If used, make sure the extension cord is rated for 12 Amps. 

!

  .

Determining the Load

 :  

1. Make a list of all equipment that requires protection.  
2. Calculate the sum of all the V x A ratings. (Input voltage/current shown on name plate). 
3. Ensure that the total VA rating does not exceed the rated capacity of the UPS. If rated unit capacities are 
exceeded, an overload condition may occur and cause the UPS unit to shut down or the circuit breaker to trip / AC 
input fuse blown. 

!

 

Connect the Load 

: Plug your primary equipment (e.g. computer, monitor, critical data storage device, etc.) into 

the Backup Power outlets. Leave the power switches of the equipment in the "Off " position for the moment. 

!

 

Connect to Computer

 : Use the enclosed RS-232 (DB9) cable. Plug the 9-pin male end into the UPS. Plug the 9-

pin female end into an open COM port of the computer. 

 

Do not plug a laser printer or copy machine into the outlets of this UPS. The power demands of these particular 
devices are much higher than typical peripherals.  

!

 

Connect the Fax / Modem Lines:  

To protect a fax or modem, connect the telephone cable from the wall outlet to 

the "IN" jack of the UPS. Connect the telephone cable from the "OUT" phone outlet on the UPS to the fax or 
modem. The phone jacks on the UPS accept standard sized phone cables (RJ11 communication cables). 

2.4 Operation and Functional Test 

!

 

AC Mode : 

The UPS delivers power to the loads from the utility and maintains battery properly charged. It also 

regulates the output voltage to within a narrow range and serves to isolate the load from surges and electrical 
noise brought by the utility wiring. 

!

 

On-Battery Mode : 

The UPS operates on battery when the line voltage or frequency has fallen outside the limits. 

Local users are alerted to this mode of operation by visual and audible indicators. The UPS provides power to the 
load from the battery and through its inverter and the output voltage and frequency of the UPS are regulated within 
a narrow band. 

 

Function 

Panel Indicator 

Switch On 

Press and hold the main on/off switch on the front panel for 3 seconds or until you hear a beep 
sound and the "AC normal" green LED will light up. 

Switch Off 

Press and hold the main on/off switch on the front panel for 3 seconds or until hear a beep sound 
and LED will go off. 

Cold Start / 
Start on Battery 

This UPS can be turned on even without the presence of AC utility. Press and hold the main on/off 
switch on the front panel for 3 seconds or until hear a beep sound and the "AC normal" green LED 
will flash every 4 seconds. 

2.5 Manual Simulation of Power Outage for the UPS 

To test the backup function, you may unplug the power cord of the UPS. The UPS will beep once every 4 seconds and 
the LED will flash on and off. 
If the UPS is left to run continuously, it is a good idea to perform a periodic function test (at least once every month) on 
the unit. Observe that your equipment operates properly and uninterrupted during this period. 

To conduct a simulation-test: 

!

  Switch the UPS on and wait for the "AC normal" indicator light up. Then unplug the UPS from the AC outlet to 

simulate a utility failure. 

!

  When utility failure occurs, power is immediately supplied to your equipment from the UPS battery. The alarm will 

beep once every 4 seconds, reminding you that your equipment is running on a limited power source. 

!

  During utility failure, manually save and close the files you are currently working on. Then, switch the UPS off to 

conserve the battery power for additional testing and usage. If the utility power is not restored, the alarm will 
change to rapid beeps alerting the user that the UPS will soon run out of battery power and will shut itself down. 

!

  Restore electrical power to connected equipment by plugging the UPS power cord back into a wall outlet. 

 

Backup all unsaved files before you perform the power outage simulation test. If monitoring software has been 
installed in the computer, then verify if the software can save the file and shut down the UPS automatically 

18 

2.6 Audible / Visual Indicators 

Audible / Visual Indicators

 

 

 

 

 

 

 

 

Buzzer 

Operating status 

"

 

"

 

- - - - 

Buck mode 

"

 

- - - - 

AC Normal 

"

 

"

 

 - - 

Boost mode 

- - - 

"

 

- - 

Beep continuously 

UPS fault 

- - - - 

#

 

Beep every 4 seconds 

On battery (AC utility failure) 

- - - - - 

#

 

Beep intermittently (see the note) 

Overload 

"

 : LED on        - :  LED off       

#

 : LED flashing

 

 

Overload status: 

AC mode : 

Battery mode : 

!

  Beep 2 times every 1 second for 105% 

!

  Beep 2 times every 0.5 second for 140 %

 

!

  Beep 2 times every 1 second for 105%. After 20 seconds UPS 

will shutdown automatically , 

!

  Immediately shutdown for 140%

 

 

3. Interface With Computer for UPS Status Monitoring 

The built-in DB9 communication port on the UPS may be 
connected to a host computer. The intelligent monitoring 
software installed in the computer can get the operating 
parameters and status through this channel and command 
the UPS to conduct pre-defined steps to protect the data in 
computer and inform the user to do all the necessary 
preventive procedures. 
This UPS communicates with the computer by sending out 
RS-232 data streams to one of the serial ports through a 9-
in to 9-pin standard cable. 

 

4. Service and Maintenance 

4.1 Routine Maintenance 

!

  Use dry soft clothes to clean the front panel and plastic parts. Do not use any detergent that contains alcoholic 

ingredient. 

!

  The expected lifetime of the battery is around 3 years. Improper operation and harsh environment will reduce the 

actual lifetime. 

!

  Unplug the UPS from power inlet if the UPS will not operate for a long period of time. 

!

  Charge the battery every 3 months to recover the self discharge capacity when the UPS is in extended storage. 

!

  When replacing batteries, use the sealed lead-acid maintenance free battery with the same voltage and capacity. 

!

  Proper disposal of batteries if required. Refer to your local codes for disposal requirements. 

4.2 Battery Replacement Overview

 

 

1.

Lay down the UPS. Use the screw driver to open the 

battery cover on the bottom of the unit.

 

 

2.

Grasp the tab attached to the battery and slide the 

battery out.

 

 

The pin assignment is shown in the following table: 
Pin # 

Description 

Pin 1 

 

Pin 2 

This pin is used for RS232 transmit pin (TXD).

Pin 3 

This pin is used for RS232 receive pin (RXD). 

Pin 4,6  Short-circuited 
Pin 5 

Common for Pin 8 and 1 

Pin 7 

DTR +5~12V (RTS). 

Pin 8 

 

Pin 9

 

N.C. 

Summary of Contents for ALPHA 500 iC

Page 1: ...pareil sur une prise d pendant d un circuit diff rent de celui du r cepteur Consulter votre distributeur ou un technicien TV Radio Le fonctionnement s r et continu de l onduleur d pend partiellement d...

Page 2: ...anchez vos appareils principaux ordinateur cran syst me de stockage sur les prises de sortie onduleur 7 Laissez vos appareils teints pour le moment Branchement l ordinateur Utilisez le c ble RS 232 DB...

Page 3: ...prise qui fonctionne 2 Le voltage du secteur correspond il aux sp cifications de l onduleur 3 Le fusible l arri re de l onduleur doit il tre remplac N ouvrez pas votre onduleur Il ne contient pas de p...

Page 4: ...mauvais fonctionnements dus a un accident une mauvaise utilisation la n gligence le feu l eau la foudre ou toute autre cause naturelle des modifications du produit sans notre autorisation ou le non su...

Page 5: ...ciones de alta variaci n de voltaje de la energ a el ctrica comercial Como hoy en d a el numero de perif ricos que se conectan al computador ha aumentado esta l nea de productos provee recept culos pr...

Page 6: ...del UPS El equipo sonar cada 4 segundos y el LED se pondr intermitente Es una buena idea realizar este tipo de pruebas por lo menos una vez al mes para asegurarse de que el UPS esta funcionando correc...

Page 7: ...comunicaci n con la computadora Utilizaci n de un cable inapropiado Utilice el cable recomendado por su distribuidor Se recomienda que el reemplazo de las bater as sea realizado por personal autorizad...

Page 8: ...eripheral devices from surges spikes and electromagnetic interference Beside providing power protection and EMI RFI to output load this series also provides surge and lightning protection for data fax...

Page 9: ...the AC normal indicator light up Then unplug the UPS from the AC outlet to simulate a utility failure When utility failure occurs power is immediately supplied to your equipment from the UPS battery...

Page 10: ...is suggested that the battery replacement should be conducted by authorized technician and with the same type and capacity of battery For more information and contact www unitek europe com 6 Specific...