3 Electrical Installation
Q6
11
C
E
A
d
v
ic
e
The devices adhere to the EU guidelines 89/336/EWG and the technical standards
EN 61000-2 and 61000-4 provided that the following conditions are observed:
- The device, the transformer, and filter capacitors are mounted on
a 500x500x2 mm mounting plate.
- The mounting plate must be connected to ground using a 10mm² wire.
- The motor housing must be connected to ground using a 10mm² wire.
- The device ground X1:8 must be connected to the mounting plate
using a 2.5mm² wire.
- Device PE screw must be connected to the mounting plate using a 4mm² wire,
l = 50mm.
Three-phase connection:
Transformer type:
see technical details
Filter capacitors:
3x1
m
F(x) + 0.5x1
m
F (y)
Conductor length between the device and the power choke <250mm
Motor connection:
Motor conductors
l = 1.5m, shielded
Tacho and all control lines l = 1.5m, shielded
Shielding connected to PE