Transistor-Servo-Drive TV3.230
14
Caution:
The connection advice concerning the individual attachments of the connections to the
plug numbers or terminals are binding.
All further advices to this are not binding. The input and output lines can be altered or
completed in consideration of the electrical regulations.
Notice:
- connection advice and operation advice
- local technical regulations
- EU-machine regulation 89/392/EWG
Connection with isolation transformer
Notice:
- rate contactor contacts according to transfomer inrush current.
- delay-action fuses before transformer
- fuse value according to transformer current
- quick fuses after transformer
- fuse value for each power supply unitl max. 30AF
Isolation transformer
Transformer-nominal power [VA]=
1.42 x 115 x IM x GLF x nF
IM
= Sum of motor currents (effective)
GLF
= coincidence factor
nF
= speed ratio factor
GLF =
nF =
1
with 1 motor
effective speed
0.5 - 0.7
with 2 motors
maximum speed
0.4 - 0.6
with > 2 motors
Connection compact device X3
auxiliary voltage
clamp X3:6, X3:7
of isolation
transformer
or external 24V
supply
C
o
n
n
e
ct
io
n
A
d
vi
ce
L
N
L
N
6
7
20V~
24V=
Summary of Contents for TV3.230 Series
Page 1: ...MANUAL Servo Drive TV3 230 xx for DC Servomotors with DC Tachometer TV3 230 Edition 0109...
Page 9: ...2 Mechanical Installation TV3 2 9 Multi Axes Combination...
Page 11: ...3 Electrical Installation TV3 2 11 Connection Overview...
Page 22: ...Transistor Servo Drive TV3 230 22 Block Diagram...
Page 26: ...Transistor Servo Drive TV3 2 26 Empty page...